Earlier Issue controllers do not have OCDS
Issue 3c controllers do not have Humidity parameters or HCOK
ref | Description | default | range | |
C1 | SPAH | Occupied setpoint (Return or Supply depending on SPTY) | 20.0 | 10.0 to 35.0 degC |
C2 | SPDB | Setpoint deadband | 1.0 | 0.0 to 10.0 C |
C3 | SPTR | setpoint trim | 0 | -10.0 to 10.0 C |
C4 | SPTY | setpoint type (control mode) 0 setpoint from SPFC, occupancy control from 1 or more Zone Controllers 1 setpoint supervised from Zone Controller 2 Room control from Zone Controller(s), supply air setpoint from Heat%, Cool% between MAXS and MINS 3 Supply Air control from setpoint SPAH occupancy controlled from 1 or more Zone Controllers 4 as 3 but setpoint can be supervised from a selected Zone Controller 5 Supply Air control, setpoint ans occupancy from a master AHU controller (Slave AHU mode) 6 Return Air control, no supply air sensor, occupancy from one or more Zone Controllers 7 Return Air Control, no supply air sensor, setpoint supervision from one Zone Controller |
1 | 0 to 7 |
C5 | SPFR | frost/fabric protect setpoint | 10 | 0.0 to 20.0 C |
C6 | INMD | Input mode allows use of trim pot and or occupation
control 0
normal operation
1 Occupied is External AND normal occupation (window contact)2 Occupied is External OR normal occupation (outside normal hours)3 Occupation controlled by external signal only |
0 | 0 to 3 |
C7 | MAXS | maximum supply air setpoint | 30 | 0 to 70 C |
C8 | MINS | minimum supply air setpoint | 10 | 2 to 30C |
C9 | NTCL | night cool doown setpoint | 0 | 0 to 25.0 C |
C10 | MIND | minimum demand | 4 | 0 to 10% |
C11 | MRUN | minimum run time | 5 | 1 to 20 mins |
C12 | HPRD | heating valve period or minimum on time | depends on driver type | 2 to 60 secs*10 |
C13 | CPRD | cooling valve period or minimum on time | depends on driver type | 2 to 60 secs*10 |
C14 | SFRT | supply fan starts first when set (1) | 1 | 0 to 1 |
C15 | OCCO | run in Occupied period only when set | 0 | 0 to 1 |
C16 | RTRY | retry delay after fan fail | 0 | 0.0 to 24.0 hours |
C17 | HTSC | heat source | 0 | 0 to 100 |
C18 | CLSC | cool source | 0 | 0 to 100 |
C19 | OCDS | occupation destination | 0 | 0 to 100 |
C20 | MXCT | maximum CT setpoint to heat source when AHU demanding 100% | 70 | 20 to 100 C |
C21 | MNCT | minimum CT setpoint to heat source when AHU demanding 0% | 30 | 20 to 100 C |
C22 | HSTG | number of heat stages | 2 | 1 to 5 |
C23 | CSTG | number of cool stages | 2 | 1 to 5 |
C24 | HCOK | allow heat and cool demands at the same time for De-hum control | 0 | 0 to 1 |
C25 | ALRM | alarm mode 0 ignore alarms 1 report alarms 2 report alarms, shut down all outputs on alarm 3 report alarms, shut down all outputs on STOP alarm or sensor fail alarm |
1 | 0 to 3 |
C26 | ALST | not used | 0 | 0 to 1 |
ref | Description | default | range | |
INPUTS | ||||
I1 (C30) | INPA | input A fan fail | 0 to 1 | |
I2 (C31) | INPB | input B filter blocked | 0 to 1 | |
I3 (C32) | RLYA | relay A heat raise | 0 to 1 | |
I4 (C33) | RLYB | relay B heat lower | 0 to 1 | |
I5 (C34) | RLYC | relay C cool raise | 0 to 1 | |
I6 (C35) | RLYD | relay D cool lower | 0 to 1 | |
I7 (C36) | SFAN | relay E supply fan | 0 to 1 | |
I8 (C37) | EFAN | relay F extract fan | 0 to 1 | |
SWITCHES | ||||
W1 (C38) |
AUTO | Controller in automatic control | ||
W2 (C39) |
OVRD | Override W1 and W2 used together with Doorway Auto/manual dialog box |
||
W3 (C40) |
RSET | reset AHU fan failure | 0 to1 | |
W7 (C44) |
SERV | remote initiation of registration button | 0 to1 | |
W8 (C45) |
CGST | remote initiation of registration button | 0 to1 | |
SENSORS | ||||
S1 (C50) | SPLA | supply air temperature | 0 to 35.0C | |
S2 (C51) | RTNA | return air temperature | 0 to 35.0 C | |
S3 (C52) | HCOP | Controller output | -100 to 100 | |
S4 (C53) | INCL | inter coil temperature | 0 to 50.0 C | |
S5 (C54) | OUTS | Outside air temperature | -30 to 35.0C | |
S6 (C55) | SPSL | current supply air setpoint | 5 to 30.0 C | |
S7 (C56) | SPRT | current return air setpoint | 5 to 30.0 C | |
S8 (C57) | SPLH | supply humidity | 0 to 100.0% | |
S9 (C58) | RTNH | return humidity | 0 to 100.0% | |
S10(C59) | OUTH | outside humidity | 0 to 100.0% | |
KNOBS | ||||
K1 (C60) | SPOC | occupied setpoint | 20.0 | 5.0 to 35.0 C |
K2 (C61) | SPFR | non occupied setpoint | 10.0 | 5.0 to 20.0 C |
K3 (C62) | SPSV | supervised setpoint (from master) | 0 | 0.0 to 50.0 C |
K4 (C63) | SPTR | setpoint trim | 0 | -10.0 to 10.0 C |
K5 (C64) | RHSP | relative humidity setpoint, zero setpoint disables de-humidification control | 0 | 10 to 100 %RH |
K6 (C65) | RHDB | relative humidity deadband | 5 | 2 to 50 %RH |
ref | Description | default | range | |
C69 | RTLP | selects display of Return loop parameters when set | 0 | 0 to 1 |
C70 | UNDH | sets very Low muzzy level for heating loop | 4.5 (1.00) | 10 to 200 |
C71 | OVRH | sets very High muzzy level for heating loop | 4.5 (1.00) | 10 to 200 |
C72 | DBBH | deadband sets limit for OK band for heating loop | 2.0 (5.0) | 10 to 200 |
C73 | RCGH | max rate of change temperature | 1 to 250 | |
C74 | GN H | gain heating | 30 (50) | 1 to 250 |
C75 | UNDC | sets very Low muzzy level for cooling loop | 4.5 (1.00) | 10 to 200 |
C76 | OVRC | sets very High muzzy level for cooling loop | 4.5 (1.00) | 10 to 200 |
C77 | DBBC | deadband sets limit for OK band for cooling loop | 2.0 (5.0) | 10 to 200 |
C78 | RCGC | max rate of change temperature | 1 to 250 | |
C79 | GN C | gain cooling | 30 (50) | 1 to 250 |
ref | Description | default | range | |
C90 | NOAL | no alarms | 0 | 0 to 1 |
C91 | FANF | fan fail | 0 | 0 to 1 |
C92 | FLTF | filter blocked | 0 | 0 to 1 |
C93 | FREZ | heater battery failed or no hot water (will stop fans) | 0 | 0 to 1 |
C94 | OUTF | no outside air reading available | 0 | 0 to 1 |
C95 | SUPF | no valid supply air temperature reading | 0 | 0 to 1 |
C96 | STOP | shut down due to master STOP alarm | 0 | 0 to 1 |
ref | Description | default | range | |
C130 | PN A | config variable number for channel A | 51 | 0 to 255 |
C131 | PT A | period code for plot A | 1 | 1 to 4 |
C132 | PN B | config variable number for channel B | 52 | 0 to 255 |
C133 | PT B | period code for plot B | 1 | 1 to 4 |
C134 | PN C | config variable number for channel C | 53 | 0 to 255 |
C135 | PT C | period code for plot C | 1 | 1 to 4 |
ref | Description | default | range | |
C150 | HTYP | heating driver type | 1 | 0 to 5 |
C151 | HINT | number of internal heating stages | 2 | 0 to 8 |
C152 | CTYP | cooling driver type | 1 | 0 to 5 |
C153 | CINT | number of internal cooling stages | 2 | 0 to 8 |
C154 | HRMN | heating driver input rescale minimum | 0 | 0 to 100% |
C155 | HRMX | heating driver input rescale maximum | 100 | 0 to 100% |
C156 | CRMN | cooling driver input rescale minimum | 0 | 0 to 100% |
C157 | CRMX | cooling driver input rescale maximum | 100 | 0 to 100% |