Air Handing Unit Controller
NAT version for Natural Ventilation Control
Feature Notes |
Configuration Tables | Data Sheet Not yet Released |
Wiring | History |
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
C1 |
SPAH |
Occupied Setpoint:
|
Deg C |
20 |
10 to 35 |
C2 |
SPDB |
Setpoint Deadband |
Deg C |
1 |
0 to 10 |
C3 |
SPTR |
Setpoint Trim; is added to the Occupied Setpoint (C1) to produce the working setpoint, used when setpoint is slaved from a Zone Controller |
Deg C |
0 |
-10 to 10 |
C4 |
SPTY |
Setpoint Type; used to select mode of control :
|
- |
FRE Type:-
|
0 to 7 |
C5 |
SPFR |
Frost Protection Setpoint; opens valves to 50% if OAT< SPFR |
Deg C |
10 |
0 to 20 |
C6 |
INMD |
Input Mode; decides influence of external Volt Free Contact
|
- |
0 |
0 to 3 |
C7 |
MAXS |
Maximum supply air setpoint |
Deg C |
30 |
2 to 70 |
C8 |
MINS |
Minimum supply air setpoint |
Deg C |
10 |
0 to 30 |
C9 |
CUTS |
Supply Air safety cutoff;
|
Deg C |
4 |
0 to 20 |
C10 |
NTCL |
Night Cooldown Setpoint; if Return Air sensor fitted, can be used to
pre-cool the building using free cooling at night:
|
Deg C |
0 |
0 to 25 |
C11 |
MIND |
Minimum Demand necessary to run the AHU; (SUP version only)
|
% |
0 |
0 to 10 |
C12 |
MRUN |
Minimum Run Time for AHU |
Mins |
5 |
0 to 20 |
C13 |
HPRD |
Heating Valve Stroke Time (for Wet Coils) or Minimum-On Time for Electric Heater |
Secs/10 |
18 |
2 to 60 |
C14 |
CPRD |
Cooling Valve Stroke Time (for Wet Coils) or Minimum-On Time for Electric Cooling stage |
Secs/10 |
18 |
2 to 60 |
C15 |
SFRT |
Supply First; used to ensure positive pressurisation of building:
|
- |
1 |
0 to 1 |
C16 |
OCCO |
Occupancy Only; (FRE and RET versions only)
|
- |
1 |
0 to 1 |
C17 |
RTRY |
Retry Delay after fan failure has shut down AHU (before AHU restarts) |
Hours |
0 |
0 to 24 |
C18 |
HTSC |
Heat Source; defines source of heat for Heater Battery:
|
- |
1 |
0 to 20 |
C19 |
CLSC |
Cool Source;
|
- |
0 |
0 to 20 |
C20 |
OCDS |
Occupancy Destination; Occupancy demand signal pointer points
to other AHUs or
|
- |
0 |
0 to 255 |
C21 |
MXCT |
Maximum CT demand to Heat Source |
Deg C |
70 |
20 to 100 |
C22 |
MNCT |
Minimum CT demand to Heat Source |
Deg C |
50 |
20 to 100 |
C23 |
HTSG |
Number of Heating Stages (not used if wet heating battery) |
- |
2 |
1 to 5 |
C24 |
CSTG |
Number of Cooling Stages (not used if wet cooling battery) |
- |
2 |
1 to 5 |
C25 |
HCOK |
Heat/Cool OK;
|
- |
0 |
0 to 1 |
C26 |
ALRM |
Alarm Mode:
|
- |
0 |
0 to 3 |
C27 |
ALST |
Alarm State: State of inputs for Fan Failure/Filter Blocked:
|
- |
0 |
0 to 1 |
C28 |
MANL |
Manual Level |
% |
0 |
-100 to 100 |
C29 |
CMDE |
Control Mode:
|
- |
0 |
0 to 3 |
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
I1 (C30) |
INPA |
Input A (fan fail) input status (Contact Closure = 1) |
- |
- |
0 to 1 |
I2 (C31) |
INPB |
Input B (filter blocked) input status (Contact Closure = 1) |
- |
- |
0 to 1 |
I3 (C32) |
RLYA |
Heating relay 1 status |
- |
- |
0 to 1 |
I4 (C33) |
RLYB |
Heating relay 2 status |
- |
- |
0 to 1 |
I5 (C34) |
RLYC |
Cooling relay 1 status |
- |
- |
0 to 1 |
I6 (C35) |
RLYD |
Cooling relay 2 status |
- |
- |
0 to 1 |
I7 (C36) |
SFAN |
Supply Fan status |
- |
- |
0 to 1 |
I8 (C37) |
EFAN |
Extract Fan Status |
- |
- |
0 to 1 |
W1 (C38) |
AUTO |
Automatic/Manual Status |
- |
- |
0 to 1 |
W2 (C39) |
OVRD |
Override |
- |
- |
0 to 1 |
W3 (C40) |
RSET |
Reset AHU after Fan failure shutdown (auto resetting after use) |
- |
- |
0 to 1 |
W4 (C41) |
DHDM |
Enable dehumidification demand from the Humidity Controller |
- |
- |
0 to 1 |
W5 (C42) |
HAND |
Manual Hand from Doorway or InSite |
- |
- |
0 to 1 |
W6 (C43) |
TWOP |
Two Pipe Operation (when set to 1) |
- |
- |
0 to 1 |
W7 (C44) |
SERV |
Remote initiation of service pin message (SeaChange diagnostic use) |
- |
- |
0 to 1 |
W8 (C45) |
CGST |
Configuration mode status |
- |
- |
0 to 1 |
|
|
W1 and W2 used together with Doorway Auto/Manual dialog box |
|
|
|
S1* (C50) |
SPLA |
Supply Air Temperature |
Deg C |
- |
0 to 35 |
S2* (C51) |
RTNA |
Return Air Temperature |
Deg C |
- |
0 to 35 |
S3* (C52) |
HCOP |
Heat / Cool output to Batteries |
% |
- |
-100 to 100 |
S4 (C53) |
INCL |
Inter-coil temperature (not used in this application) |
Deg C |
- |
0 to 50 |
S5 (C54) |
OUTS |
Outside Temperature (locally wired or via network) |
Deg C |
- |
-30 to 35 |
S6 (C55) |
SPSL |
Current Supply temperature Setpoint |
Deg C |
- |
5 to 30 |
S7 (C56) |
SPRT |
Current Return Temperature Setpoint |
Deg C |
- |
5 to 30 |
S8 (C57) |
SPLH |
Supply Air Humidity |
% |
- |
0 to100 |
S9 (C58) |
RTNH |
Return Air Humidity |
% |
- |
0 to100 |
S10.(C59) |
OUTH |
Outside Air Humidity |
% |
- |
0 to100 |
K1 (C60) |
SPOC |
Occupied Setpoint |
Deg C |
20 |
5 to 35 |
K2 (C61) |
SPFR |
Frost Protection Setpoint |
Deg C |
0 |
5 to 20 |
K3 (C62) |
SPSV |
Supervised Setpoint from Zone Controller (overrides C60) |
Deg C |
0 |
0 - 50 |
K4 (C63) |
SPTR |
Setpoint Trim; added to C62 to form current setpoint |
Deg C |
0 |
-10 to 10 |
K5 (C64) |
RHSP |
RH Setpoint for Return Air Humidity;
|
% |
0 |
10 to 100 |
K6 (C65) |
RHDB |
RH deadband for Dehumidification |
% |
5 |
2 to 50 |
|
|
Engineering Parameters; only accessible via Doorway and InSite |
|
|
|
C90 |
NOAL |
No Alarms; all alarms cleared when set to 1 |
- |
- |
0 to 1 |
C91 |
FANF |
Fan Failure Alarm current (when set to 1) |
- |
- |
0 to 1 |
C92 |
FLTF |
Filter Blocked Alarm current (when set to 1) |
- |
- |
0 to 1 |
C93 |
FREZ |
Danger of Freezing Alarm current (when set to 1) |
- |
- |
0 to 1 |
C94 |
OUTF |
No Outside Temperature Available Alarm current (when set to 1) |
- |
- |
0 to 1 |
C95 |
SUPF |
Supply Sensor Failed (when set to 1) |
- |
- |
0 to 1 |
C96 |
STOP |
Controller shut down due to System Stop Alarm received (when set to 1) |
- |
- |
0 to 1 |
|
|
These parameters are factory set; refer to SeaChange for special applications before changing these settings |
|
|
|
C154 |
HRMN |
Heating Driver input rescale minimum |
% |
0 |
0 to 100 |
C155 |
HRMX |
Heating Driver input rescale maximum |
% |
100 |
0 to 100 |
C156 |
CRMN |
Cooling Driver input rescale minimum |
% |
0 |
0 to 100 |
C157 |
CRMX |
Cooling Driver input rescale maximum |
% |
100 |
0 to 100 |
|
|
Night Purge Settings |
|
|
|
C180 |
HFLW |
Heating (cooling) Medium Temperature from Heat/Cool source, used for two pipe selection and start up interlocks |
Deg C |
- |
0 to 140 |
C181 |
SILK |
Start Up Interlock |
- |
- |
0 to 1 |
C182 |
DHON |
De-Humidification On |
- |
- |
0 to 1 |
C183 |
PHRS |
Purge Test Time; checks that the Outside temperature is greater than POUT at this time to enable night purge to run if all other conditions are met |
Hrs |
16 |
0 to 24 |
C184 |
HHRS |
Heat Enable Time if Purge ran the previous night |
Hrs |
10 |
0 to 24 |
C185 |
POUT |
Test level for Outside temperature checked at Purge Test |
Deg C |
18 |
0 to 25 |
C186 |
NPEN |
Night Purge: enabled |
- |
read only |
0 to 1 |
C187 |
NPOP |
Night Purge: operating |
- |
read only |
0 to 1 |
C188 |
NPHD |
Night Purge: heating disabled |
- |
read only |
0 to 1 |
C189 |
NPSD |
Night Purge: send demand to sub modules |
- |
0 |
0 to 1 |
|
|
* 24 hour plots available for these values by default |
|
|
|
|
|
Plotting interval and plotted variable changeable via Doorway or InSite |
|
|
|