Air Handing Unit Controller
NAT version for Natural Ventilation Control

Feature
Notes
Configuration Tables Data Sheet
Not yet Released
Wiring History

Configuration Tables

Latest released version is 4c1 (beta 4cu)

Document last updated 18/10/2002
Features introduced in latest issue are in
RED text

Configuration Parameters

Doorway / InSite Code

Label

Description

Units

Default Value

Range

C1
SPAH
Occupied Setpoint:
FRE Type:-
Occupied Supply Air Setpoint
RET Type:-
Occupied Return Air Setpoint
SUP Type:-
Not used in this applicaion
Deg C
20
10 to 35
C2
SPDB
Setpoint Deadband
Deg C
1
0 to 10
C3
SPTR
Setpoint Trim; is added to the Occupied Setpoint (C1) to produce the working setpoint, used when setpoint is slaved from a Zone Controller
Deg C
0
-10 to 10
C4
SPTY
Setpoint Type; used to select mode of control :
FRE Type:-
3: Constant Supply Temp; setpoint = C1 / K1 .
4: Constant Supply Temp; setpoint slaved from a Zone Controller
RET Type:-
0: Constant Return Temp using Cascade (aka Reset) control; setpoint = C1/K1
1: Constant Return Temp using Cascade (aka Reset) control; setpoint slaved from a Zone Controller
6: Constant Return Temp only (no Cascade/Reset control); setpoint = C1/K1
7: Constant Return Temp only (no Cascade/Reset control); setpoint slaved from a Zone Controller
SUP Type:-
2: Variable Supply Temp based on heat/cool demands from one or more Zones/Terminal Units
5: Variable Supply Temp; supply setpoint slaved from another AHU
-
FRE Type:-
3
RET Type:-
1
SUP Type:-
2
0 to 7
C5
SPFR
Frost Protection Setpoint; opens valves to 50% if OAT< SPFR
Deg C
10
0 to 20
C6
INMD
Input Mode; decides influence of external Volt Free Contact
0: Normal operation, external signal ignored
1: Occupied is External AND normal occupation
(window contact or contact used to stop AHU)
2: Occupied is External OR normal occupation
(Occupancy extension switch for outside normal hours)
3: Occupation controlled by external signal only
-
0
0 to 3
C7
MAXS
Maximum supply air setpoint
Deg C
30
2 to 70
C8
MINS
Minimum supply air setpoint
Deg C
10
0 to 30
C9
CUTS
Supply Air safety cutoff;
0: This feature inactive; AHU will not shut down
>0: If Supply Air falls below this value, AHU will shut down
Deg C
4
0 to 20
C10
NTCL
Night Cooldown Setpoint; if Return Air sensor fitted, can be used to pre-cool the building using free cooling at night:
0: Night Cooling disabled
>0: value used as Night Cooldown Setpoint
Deg C
0
0 to 25
C11
MIND
Minimum Demand necessary to run the AHU; (SUP version only)
0: AHU will run if any Zone is in Occupation or Warm-Up
(used for plants that are supplying Fresh Air)
>0: AHU will only run if max Zone demand is higher than MIND
(used for plants not supplying Fresh Air)
Not used, set to 0 in this application (FRE and RET versions only)
%
0
0 to 10
C12
MRUN
Minimum Run Time for AHU
Mins
5
0 to 20
C13
HPRD
Heating Valve Stroke Time (for Wet Coils) or Minimum-On Time for Electric Heater
Secs/10
18
2 to 60
C14
CPRD
Cooling Valve Stroke Time (for Wet Coils) or Minimum-On Time for Electric Cooling stage
Secs/10
18
2 to 60
C15
SFRT
Supply First; used to ensure positive pressurisation of building:
0 : Extract Fan starts before Supply Fan
1 : Supply Fan starts before Extract Fan
-
1
0 to 1
C16
OCCO
Occupancy Only; (FRE and RET versions only)
0 : AHU Runs in Warm-Up, Occupation and Fabric Protection
1: AHU Runs in Occupation only
Not used, set to 1in this application (SUP version only)
-
1
0 to 1
C17
RTRY
Retry Delay after fan failure has shut down AHU (before AHU restarts)
Hours
0
0 to 24
C18
HTSC
Heat Source; defines source of heat for Heater Battery:
0: for Electric Battery or non-SeaChange Boiler plant
1-20: to indicate source of heat (Boiler, Secondary Circuit
Controller etc.), set automatically during registration
-
1
0 to 20
C19
CLSC
Cool Source;
0: for Electric Battery or non-SeaChange cooling plant,
1-20: to indicate source of cooling (Chiller etc.)
-
0
0 to 20
C20
OCDS
Occupancy Destination; Occupancy demand signal “pointer” points to other AHUs or
other controllers:
0: feature is inactive
51-100 : will send Occupancy Status to AHU 1 - 50
(for AHU 1, set to 51, AHU2, set to 52 etc.)
101-200: will send Occupancy Status to Zones 1-100
(for Zone 1, set to 101, Zone 2, set to 102 etc.)
-
0
0 to 255
C21
MXCT
Maximum CT demand to Heat Source
Deg C
70
20 to 100
C22
MNCT
Minimum CT demand to Heat Source
Deg C
50
20 to 100
C23
HTSG
Number of Heating Stages (not used if wet heating battery)
-
2
1 to 5
C24
CSTG
Number of Cooling Stages (not used if wet cooling battery)
-
2
1 to 5
C25
HCOK
Heat/Cool OK;
1: allows heating and cooling to run simultaneously for closer
control when using staged DX battery with modulating
heating coil (not to be set when using DeHum control)
0: simultaneous heating and cooling not allowed (unless
DeHum control is enabled using RHSP)
-
0
0 to 1
C26
ALRM
Alarm Mode:
0: Ignore Alarms
1: Report Alarms to supervisor
(Fan Failure, Filter Blocked, Danger of Freezing, Outside Temperature sensor fault)
2: Report Alarms, shut down all outputs on STOP Alarm
3: as 2) above, and shut down TP or Staged outputs on Fan Failure
-
0
0 to 3
C27
ALST
Alarm State: State of inputs for Fan Failure/Filter Blocked:
0: Contact Closure generates alarm
1: Contact Opening generates alarm
-
0
0 to 1
C28
MANL
Manual Level
%
0
-100 to 100
C29
CMDE
Control Mode:
0: heating and cooling supply loop in bypass
1: heating supply loop active; cooling bypass
2: heating bypass; cooling supply loop active
3: heating and cooling supply loops active
-
0
0 to 3

 

Monitoring Parameters

Doorway / InSite Code

Label

Description

Units

Default Value

Range

I1 (C30)
INPA
Input A (fan fail) input status (Contact Closure = 1)
-
-
0 to 1
I2 (C31)
INPB
Input B (filter blocked) input status (Contact Closure = 1)
-
-
0 to 1
I3 (C32)
RLYA
Heating relay 1 status
-
-
0 to 1
I4 (C33)
RLYB
Heating relay 2 status
-
-
0 to 1
I5 (C34)
RLYC
Cooling relay 1 status
-
-
0 to 1
I6 (C35)
RLYD
Cooling relay 2 status
-
-
0 to 1
I7 (C36)
SFAN
Supply Fan status
-
-
0 to 1
I8 (C37)
EFAN
Extract Fan Status
-
-
0 to 1
W1 (C38)
AUTO
Automatic/Manual Status
-
-
0 to 1
W2 (C39)
OVRD
Override
-
-
0 to 1
W3 (C40)
RSET
Reset AHU after Fan failure shutdown (auto resetting after use)
-
-
0 to 1
W4 (C41)
DHDM
Enable dehumidification demand from the Humidity Controller
-
-
0 to 1
W5 (C42)
HAND
Manual Hand from Doorway or InSite
-
-
0 to 1
W6 (C43)
TWOP
Two Pipe Operation (when set to 1)
-
-
0 to 1
W7 (C44)
SERV
Remote initiation of service pin message (SeaChange diagnostic use)
-
-
0 to 1
W8 (C45)
CGST
Configuration mode status
-
-
0 to 1
 
 
W1 and W2 used together with Doorway Auto/Manual dialog box
 
 
 
S1* (C50)
SPLA
Supply Air Temperature
Deg C
-
0 to 35
S2* (C51)
RTNA
Return Air Temperature
Deg C
-
0 to 35
S3* (C52)
HCOP
Heat / Cool output to Batteries
%
-
-100 to 100
S4 (C53)
INCL
Inter-coil temperature (not used in this application)
Deg C
-
0 to 50
S5 (C54)
OUTS
Outside Temperature (locally wired or via network)
Deg C
-
-30 to 35
S6 (C55)
SPSL
Current Supply temperature Setpoint
Deg C
-
5 to 30
S7 (C56)
SPRT
Current Return Temperature Setpoint
Deg C
-
5 to 30
S8 (C57)
SPLH
Supply Air Humidity
%
-
0 to100
S9 (C58)
RTNH
Return Air Humidity
%
-
0 to100
S10.(C59)
OUTH
Outside Air Humidity
%
-
0 to100
K1 (C60)
SPOC
Occupied Setpoint
Deg C
20
5 to 35
K2 (C61)
SPFR
Frost Protection Setpoint
Deg C
0
5 to 20
K3 (C62)
SPSV
Supervised Setpoint from Zone Controller (overrides C60)
Deg C
0
0 - 50
K4 (C63)
SPTR
Setpoint Trim; added to C62 to form current setpoint
Deg C
0
-10 to 10
K5 (C64)
RHSP
RH Setpoint for Return Air Humidity;
0: Disables Dehumidification
10 - 100: forms setpoint for Dehum control
%
0
10 to 100
K6 (C65)
RHDB
RH deadband for Dehumidification
%
5
2 to 50
 
 
Engineering Parameters; only accessible via Doorway and InSite
 
 
 
C90
NOAL
No Alarms; all alarms cleared when set to 1
-
-
0 to 1
C91
FANF
Fan Failure Alarm current (when set to 1)
-
-
0 to 1
C92
FLTF
Filter Blocked Alarm current (when set to 1)
-
-
0 to 1
C93
FREZ
Danger of Freezing Alarm current (when set to 1)
-
-
0 to 1
C94
OUTF
No Outside Temperature Available Alarm current (when set to 1)
-
-
0 to 1
C95
SUPF
Supply Sensor Failed (when set to 1)
-
-
0 to 1
C96
STOP
Controller shut down due to System Stop Alarm received (when set to 1)
-
-
0 to 1
 
 
These parameters are factory set; refer to SeaChange for special applications before changing these settings
 
 
 
C154
HRMN
Heating Driver input rescale minimum
%
0
0 to 100
C155
HRMX
Heating Driver input rescale maximum
%
100
0 to 100
C156
CRMN
Cooling Driver input rescale minimum
%
0
0 to 100
C157
CRMX
Cooling Driver input rescale maximum
%
100
0 to 100
 
 
Night Purge Settings
 
 
 
C180
HFLW
Heating (cooling) Medium Temperature from Heat/Cool source, used for two pipe selection and start up interlocks
Deg C
-
0 to 140
C181
SILK
Start Up Interlock
-
-
0 to 1
C182
DHON
De-Humidification On
-
-
0 to 1
C183
PHRS
Purge Test Time; checks that the Outside temperature is greater than POUT at this time to enable night purge to run if all other conditions are met
Hrs
16
0 to 24
C184
HHRS
Heat Enable Time if Purge ran the previous night
Hrs
10
0 to 24
C185
POUT
Test level for Outside temperature checked at Purge Test
Deg C
18
0 to 25
C186
NPEN
Night Purge: enabled
-
read only
0 to 1
C187
NPOP
Night Purge: operating
-
read only
0 to 1
C188
NPHD
Night Purge: heating disabled
-
read only
0 to 1
C189
NPSD
Night Purge: send demand to sub modules
-
0
0 to 1
 
 
* 24 hour plots available for these values by default
 
 
 
 
 
Plotting interval and plotted variable changeable via Doorway or InSite
 
 
 

 

 