Name |
SNVT type |
in/ out |
normal connection |
nciNetConfig | SNVT_config_src | in | when set TRUE disables inbuilt binding |
nciLocation | SNVT_str_asc | in | node label string.. application updates it when address changed |
nviConfigPara | single byte parameter number | in | used to read config parameter, node replies
with data in SeaChange data structure |
nviClock | SNVT_date_time | out | connected to nviClock on all registered modules (group broadcast) |
nviDayofWeek | SNVT_date_day | out | connected to nviDayofWeek on all registered modules (group broadcast) |
nvoAhuOutTemp | SNVT_temp | out | connected to nviOutsideTemp on all registered modules (group broadcast) |
nvoBoilerTemp | SNVT_temp | out | reserved for future use |
nvoInstallZone | SNVT_lev_cont | out | used to confirm registration allocation |
nviHeatTrim | SNVT_lev_cont | in |
heat demand from Master AHU or Zone Controller |
nvoSetDay | SNVT_date_day | out |
connected to nviSetDay on Boiler Controller set day of week on Boiler Controller |
nvoSetTime | SNVT_date_time | out |
connected to nviSetTime on Boiler Controller set real time clock |
nvoConstTempSP | SNVT_temp | out | connected to nviConstTempSP on Boiler controller. Sets a minimum flow temperature setpoint for Hot water circuits or Constant temperature heating circuits |
nviCoolTrim | SNVT_lev_cont | in | cool demands from Master AHU or Zone controller |
nviOccupancy | SNVT_occupancy | in | Occupancy from Zone or another AHU |
nvoOccupancy | SNVT_occupancy | out | current Occupancy state |
nvoZoneHeatOp | SNVT_lev_cont | out | connected to nviHeatTrim on an Actuator controller |
nvoZoneCoolOp | SNVT_lev_cont | out | connected to nviCoolTrim on an Actuator controller |
nvoAHUstructOp | SeaChange structure ahu_op | out | AHU data to sub modules |
nviPreHeatStatus | SeaChange structure ahp_op | in | Interlock data from preheater, mixing damper, fan changeover controllers |
nvoHeatTrim | SNVT_lev_cont | out |
heat demand % to heat source |
nvoCoolTrim | SNVT_lev_cont | in |
cool demand % to cool source |
nviOutsideTemp | SNVT_temp_p | in | Outside temperature connected to optional networked sensor |
nviOutsideRH | SNVT_lev_percent | in | Outside Relative Humidity connected to optional networked sensor |
nviSpaceTemp | SNVT_temp_p | in | Space or Return Air temperature connected to optional networked sensor |
nviSpaceRH | SNVT_lev_percent | in | Space or Return Air Relative Humidity connected to optional networked sensor |
nviSupplyTemp | SNVT_temp_p | in | Supply Air temperature connected to optional networked sensor |
nviSupplyRH | SNVT_lev_percent | in | Supply Air Relative Humidity connected to optional networked sensor |
nviSetPoint | SNVT_temp_p | in | Occupied setpoint, changes EEPROM value so update rate needs to be carefully considered |
nvoSetPtOffset | SNVT_temp_p | in | Occupied Setpoint trim, allows setpoint of each AHUl to be indiviually trimmed |
nvoEffectSetPt | SNVT_temp_p | out | current setpoint |
nvoSpaceTemp | SNVT_temp_p * | out | current return air temperature |
nvoSupplyTemp | SNVT_temp_p * | out | current supply air temperature |
nvoOutsideTemp | SNVT_temp_p * | out | current outside air temperature |
nvoOutsideRH | SNVT_lev_percent * | out | current outside RH |
nvoHeatOutput | SNVT_lev_percent * | out | Heating Demand |
nvoCoolOutput | SNVT_lev_percent * | out | Cooling Demand |
nvoDigIn | single byte | out poll |
Eight status signals, one per bit Frost; Occupied; heat relay 1; heat relay 2; cool relay 1; cool
relay 2; supply fan; extract fan |
nvoSwitch | single byte | out poll |
Status of eight switches one per bit Automatic; Override; spare; spare; spare; spare; spare; Config mode |
nviSwitch | single byte | in | Writes to eight switches one per bit as above |
nviPlotRequest | SeaChange plot request | in | proprietory data structure |
nviClock | SNVT_date_time | in | receive time updates from other system masters for time syncronisation |
nciSndHrtBt | SNVT_time_sec | in | heartbeat setting for update time of SNVT values marked with a * |