ref | Description | default | range | |
C1 | SPRH | Occupied setpoint | 50 | 0 to 100 %RH |
C2 | SPMD | Midpoint of setpoint adjustment range | 50 | 10 to 90 |
C3 | SPRG | Range of setpoint adjustment about midpoint | 20 | 0 to 40 |
C4 | SPDB | Setpoint deadband between humidification and de_humidification setpoints. If zero disables de-hum | 10 | 0 to 20 |
C5 | RDLY | Recirculation delay , hours of continuous running before water recircualtion is allowed | 2.0 | 0 to 10.0 hours |
C6 | HPRD | heating valve period or minimum on time | depends on driver type | 1 to 60 secs/10 |
C7 | HDLY | Interlock delay negative value delays fan (or pump) after heating starts positive value cause run on of fan after heating shuts down |
0 | -30.0 to 30.0 minutes |
C8 | CPRD | cooling valve period or minimum on time | depends on driver type | 1 to 60 secs/10 |
C9 | CDLY | Interlock delay negative value delays fan (or pump) after cooling starts positive value cause run on of fan after cooling shuts down |
0 | -30.0 to 30.0 minutes |
C10 | FPRD | Fan or pump period, minimum time to change fan speed steps | 12 (2 minutes) | 1 to 60 secs/10 |
C11 | MIND | Minimum demand | 4 | 0 to 100 |
C12 | MANL | Manual level , from Doorway | 0 | -100 to 100 % |
C13 | ALRM | alarm mode 0 ignore alarms 1 report alarms 2 report alarms, shut down all outputs on alarm 3 report alarms, shut down all outputs on STOP alarm or sensor fail alarm |
1 | 0 to 3 |
C14 | ALST | not used | 0 | 0 to 1 |
C15 | CMDE | control mode 0 driver only mode 1 closed loop control of humidity 2 closed loop control of Humidity and DeHum (see Close Control for setup details) |
0 | 0 to 2 |
C16 | MXSH | Maximum Supply Humidity setpoint | 60 | 0 to 100 %RH |
C17 | MNSH | Minimum Supply Humidity setpoint | 40 | 0 to 100 %RH |
C18 | DHOF | Supply DeHum setpoint offset | 2.0 | 0 to 10.0 %RH |
C19 | TRGT | Target mean value for Humidifier control minimum output | 10 | 3 to 100 % |
C20 | ICGN | InterCoil setpoint Gain (controls rate of adjustment) | 10 | 1 to 255 |
C21 | ICSP | InterCoil temperature setpoint for monitoring | 30 | 0 to 50.0 degC |
C22 | MXVA* | Maximum voltage channel A | 10.0 | 0.0 to 10.0 volt |
C23 | MNVA* | Minimum voltage channel A | 0.0 | 0.0 to 10.0 volt |
C24 | MXVB* | Maximum voltage channel B | 10.0 | 0.0 to 10.0 volt |
C25 | MNVB* | Minimum voltage channel B | 0.0 | 0.0 to 10.0 volt |
ref | Description | default | range | |
INPUTS | ||||
I2 (C31 | OCC | Occupied | 0 to 1 | |
I3 (C32) | OSRT | Optimum Start in operation | 0 to 1 | |
I8 (C37) | XOCC | External Occupation signal | 0 to 1 | |
I6 (C35) | RLYA | relay A | 0 to 1 | |
I7 (C36) | RLYB | relay B | 0 to 1 | |
i8 (C37) | RLYC | relay C | 0 to 1 | |
SWITCHES | ||||
W1 (C38) |
AUTO | Controller in automatic control | ||
W2 (C39) |
OVRD | Override W1 and W2 used together with Doorway Auto/manual dialog box |
||
W8 (C45) |
CGST | Configuration mode | ||
SENSORS | ||||
S1 (C50) | RTRH | Return Relative Humidity | 0 to 100 %RH | |
S2 (C51) | SLRH | Supply Relative Humidity | 0 to 100 %RH | |
S3 (C52) | DMND | Controller output | -100 to 100 | |
S4 (C53) | RTSP | Return Humidity Setpoint | 0 to 100 %RH | |
S5 (C54) | SLSP | Supply Humidity Setpoint | 0 to 100 %RH | |
S6 (C55) | HDMD | Humidification output demand | 0 to 100 | |
S7 (C56) | CDMD | De-humudification output demand | 0 to 100 | |
S8 (C57) | RDMD | Recirculation demand | 0 to 100 | |
S9 (C58) | HTIP | Heat demand from AHU | 0 to 100 | |
S10 (C59) | CLIP | Cool demand from AHU | 0 to 100 | |
KNOBS | ||||
K1 (C60) | SPRH | Occupied setpoint | 50 | 0 to 100 %RH |
ref | Description | default | range | |
C69 | RTLP | selects parameters for Return RH loop and InterCoil loop | 0 | 0 to 1 |
C70 | UNDH | sets very Low muzzy level for humidity loop | 6.0 | 10 to 200 |
C71 | OVRH | sets very High muzzy level for humidity loop | 6.0 | 10 to 200 |
C72 | DBBH | deadband sets limit for OK band for humidity loop | 2.0 | 10 to 200 |
C73 | RCGH | max rate of change humidity | 1 to 250 | |
C74 | GN H | gain humidity | 20 | 1 to 250 |
C75 | UNDC | sets very Low muzzy level for de-hum loop | 6.0 | 10 to 200 |
C76 | OVRC | sets very High muzzy level for de-hum loop | 6.0 | 10 to 200 |
C77 | DBBC | deadband sets limit for OK band for de-hum loop | 2.0 | 10 to 200 |
C78 | RCGC | max rate of change de-hum | 1 to 250 | |
C79 | GN C | gain de-hum | 20 | 1 to 250 |
ref | Description | default | range | |
C130 | PN A | config variable number for channel A | 51 | 0 to 255 |
C131 | PT A | period code for plot A | 1 | 1 to 4 |
C132 | PN B | config variable number for channel B | 52 | 0 to 255 |
C133 | PT B | period code for plot B | 1 | 1 to 4 |
ref | Description | default | range | |
C150 | HTYP | Channel 1 (heating) driver type | 0 to 5 | |
C151 | HSTG | Channel 1 number of (heating) stages | 0 to 8 | |
C152 | CTYP | Channel 2 (cooling) driver type | 0 to 5 | |
C153 | CSTG | Channel 2 number of (cooling) stages | 0 to 8 | |
C154 | FTYP | fan/pump driver type | 0 to 7 | |
C155 | FSTG | number of fan stages | 0 to 5 |