| ref | Description | default | range | |
| C1 | SACT | sensor action 0 use local sensor unless remote sensor connected see use of nviRemoteTemp for Open systems 1 average valid sensor values 2 maximum of valid sensor values 3 minimum of valid sensor values |
0 | 0 to 3 |
| C2 | HPRD | heating valve period or minimum on time | depends on driver type | 1 to 60 secs/10 |
| C3 | HDLY | Interlock delay negative value delays fan (or pump) after heating starts positive value cause run on of fan after heating shuts down |
0 | -30.0 to 30.0 minutes |
| C4 | MIND | Minimum demand | 4 | 0 to 100 |
| C5 | MNFA | Minimum Fresh Air | 0 | -100 to 100 % |
| C6 | MXAQ | maximum Fresh Air when Air Quality reading equal to or greater than this value | 80 | 0 to 100% |
| C7 | MNAQ | minimum value for Air Quality overide | 20 | 0 to 100% |
| C8 | DMPC | percentage of the AHU heating and cooling demand which is used to modulte the dampers. Zero disables this feature. | 0 | 0 to 100% |
| C9 | ALRM | alarm mode 0 ignore alarms 1 report alarms 2 report alarms, shut down all outputs on alarm 3 report alarms, shut down all outputs on STOP alarm or sensor fail alarm |
1 | 0 to 3 |
| C10 | ALST | not used | 0 | 0 to 1 |
| C11 | MXVA* | Maximum voltage channel A | 10.0 | 0.0 to 10.0 volt |
| C12 | MNVA* | Minimum voltage channel A | 0.0 | 0.0 to 10.0 volt |
| C13 | MXVB* | Maximum voltage channel B | 10.0 | 0.0 to 10.0 volt |
| C14 | MNVB* | Minimum voltage channel B | 0.0 | 0.0 to 10.0 volt |
| ref | Description | default | range | |
| INPUTS | ||||
| I1 (C30) | FRST | Frost | 0 to 1 | |
| I2 (C31) | OCCD | AHU Occupied | 0 to 1 | |
| I3 (C32) | OSRT | Optimum Start not used | 0 to 1 | |
| I5 (C34) | COOL | Cool mode | ||
| I6 (C35) | RLYA | relay A | 0 to 1 | |
| I7 (C36) | RLYB | relay B | 0 to 1 | |
| I8 (C37) | RLYC | relay C | 0 to 1 | |
| SWITCHES | ||||
| W1 (C38) |
AUTO | Controller in automatic control | ||
| W2 (C39) |
OVRD | Override W1 and W2 used together with Doorway Auto/manual dialog box |
||
| SENSORS | ||||
| S1 (C50) | TEMP | Mixed Air temperature | 0 to 95 deg C | |
| S2 (C51) | HCOP | Controller output | -100 to 100 | |
| S3 (C52) | REQD | Controller current setpoint | 0 to 95 deg C | |
| S4 (C53) | AIRQ | Air Quality sensor value | 0 to 100 | |
| S5 (C54) | POSN | Demand to damper | 0 to 100 | |
| KNOBS | ||||
| K1 | MNFA | Minimum Fresh Air | 0 | -100 to 100 % |
| K2 | MXAQ | maximum Fresh Air when Air Quality reading equal to or greater than this value | 80 | 0 to 100% |
| K3 | MNAQ | minimum value for Air Quality overide | 20 | 0 to 100% |
| ref | Description | default | range | |
| C70 | UNDH | sets very Low muzzy level for heating loop | 6.0 | 10 to 200 |
| C71 | OVRH | sets very High muzzy level for heating loop | 6.0 | 10 to 200 |
| C72 | DBBH | deadband sets limit for OK band for heating loop | 2.0 | 10 to 200 |
| C73 | RCGH | max rate of change heating | 1 to 250 | |
| C74 | GN H | gain heating | 20 | 1 to 250 |
| C75 | UNDC | sets very Low muzzy level for cooling loop | 6.0 | 10 to 200 |
| C76 | OVRC | sets very High muzzy level for cooling loop | 6.0 | 10 to 200 |
| C77 | DBBC | deadband sets limit for OK band for cooling loop | 2.0 | 10 to 200 |
| C78 | RCGC | max rate of change cooling | 1 to 250 | |
| C79 | GN C | gain cooling | 20 | 1 to 250 |
| ref | Description | default | range | |
| C130 | PN A | config variable number for channel A | 51 | 0 to 255 |
| C131 | PT A | period code for plot A | 1 | 1 to 4 |
| C132 | PN B | config variable number for channel B | 52 | 0 to 255 |
| C133 | PT B | period code for plot B | 1 | 1 to 4 |
| ref | Description | default | range | |
| C150 | HTYP | Channel 1 (heating) driver type | 1 | 0 to 9 |
| C151 | HSTG | Channel 1 number of stages | 2 | 0 to 8 |
| C152 | CTYP | Channel 2 (cooling) driver type | 1 | 0 to 9 |
| C153 | CSTG | Channel 2 number of stages | 0 | 0 to 8 |
| C154 | FTYP | not used | 0 to 7 | |
| C155 | FSTG | not used | 0 to 5 |