Name |
SNVT type |
in/ out |
normal connection |
nciNetConfig | SNVT_config_src | in | when set TRUE disables inbuilt binding |
nciLocation | SNVT_str_asc | in | node label string.. application updates it when address changed |
nviConfigPara | single byte parameter number | in | used to read config parameter, node replies
with data in SeaChange data structure |
nviConfigData | SeaChange data structure | in | writes new config parameter data |
nviHeatDmnd | SNVT_lev_cont | in | heat demand from Master Fan Coil or Zone Controller |
nviCoolDmnd | SNVT_lev_cont | in | cool demand from Master Fan Coil or Zone Controller |
nviFanSpeed | SNVT_lev_cont | in | fan speed selection 0 off, speeds 1 to 3 |
nviRoomState | unsigned int | in | Room State used for Hotel Rooms in conjunction with Room Controller |
nviOccupancy | SNVT_occupancy | in | Occupancy control when using OCDS or Open binding |
nviClock | SNVT_date_time | in | connected to nvoClock on Boiler controller |
nviDayofWeek | SNVT_date_day | in | connected to nvoDayofWeek on Boiler controller |
nviOutsideTemp | SNVT_temp | in | connected to nvoOutsideTemp on Boiler Controller |
nviBoilerTemp | SNVT_temp | in | connected to nvoBoilerTemp on Boiler Controller |
nviInstallZone | SNVT_lev_cont | in | used to display installed zone number |
nvoHeatTrim | SNVT_lev_cont | out |
connected to nviHeatTrim on Boiler controller heat demand% from this Zone |
nvoSetDay | SNVT_date_day | out |
connected to nviSetDay on Boiler Controller set day of week on Boiler Controller |
nvoSetTime | SNVT_date_time | out |
connected to nviSetTime on Boiler Controller set real time clock |
nvoConstTempSP | SNVT_temp | out | connected to nviConstTempSP on Boiler controller. Sets a minimum flow temperature setpoint for Hot water circuits or Constant temperature heating circuits |
nvoCoolTrim | SNVT_lev_cont | out | connected to nviCoolTrim on Floor Controller
or Cool Demand input on Chiller Controller |
nvoOccupancy | SNVT_occupancy | out | current occupancy state |
nvoZoneHeatOp | SNVT_lev_cont | out | connected to nviHeatTrim on an Actuator controller |
nvoZoneCoolOp | SNVT_lev_cont | out | connected to nviCoolTrim on an Actuator controller |
nvoFanSpeed | SNVT_lev_cont | out | Fan Speed, used to connect to nviFanSpeed on a slave FCU |
nvoRoomState | unsigned int | out | Room State special use in Hotel Rooms |
nviRemoteTemp | SNVT_temp_p | in | connected to optional networked sensor |
nviOccSetPoint | SNVT_temp_p | in | Occupied setpoint, changes EEPROM value so update rate needs to be carefully considered |
nvoSetPtOffset | SNVT_temp_p | in | Occupied Setpoint trim, allows setpoint of each FanCoil to be indiviually trimmed |
nvoSpaceTemp | SNVT_temp_p * | out | current return air temperature |
nvoDischAirTemp | SNVT_temp_p * | out | current supply air temperature |
nvoHeatOutput | SNVT_lev_percent * | out | Heating Demand |
nvoCoolOutput | SNVT_lev_percent * | out | Cooling Demand |
nvoEffectSetPt | SNVT_temp_p | out | current setpoint |
nviCondensation | SNVT_lev_percent | in | not yet supported |
nvoDigIn | single byte | out poll |
Eight status signals, one per bit Frost; Occupied; Warm up; Optimum off; Cool; Condensation; spare;
spare |
nvoSwitch | single byte | out poll |
Status of eight switches one per bit Automatic; Override; spare; spare; spare; spare; spare; Config mode |
nviSwitch | single byte | in | Writes to eight switches one per bit as above |
nviPlotRequest | SeaChange plot request | in | proprietory data structure |
nciSndHrtBt | SNVT_time_sec | in | heartbeat setting for update time of SNVT values marked with a * |