Configuration Parameters -  Fan Coil Controller

Types:FCU/DIN/3R/xxx, FCU/DIN/4R/xxx, FCU/DIN/7R/xxx

Software Release: FCUD4c1, FCUA4c1, FCUF4c1

Configuration Parameters


ref
 
Description

default

range

C1

SPFC

Occupied Setpoint

20

10.0 to 35.0C

C2

SPDB

Setpoint Deadband

1.0

0.0 to 10.0C

C3

SPTR

Setpoint Trim

0

-10.0 to 10.0 C

C4

SPTY

Setpoint Type, control mode
0 control to SPFC, occupation from Master Zone
1 SPFC supervised from Master Zone
2 Off Coil temperature control, Heat/Cool demands from Zone Controller or another Fan Coil

1

0 to 2

C5

INMD

Input Mode use of terminals 'temp a'
0 supply temperature
1 window contact (short = occupied) AND internal occ
2 Time Clock OR internal clock
3 External occupation signal only
4 Alarm input


0

0 to 4

C6

MAXH

Maximum Supply Heating setpoint

30

0 to 90C

C7

MINH

Minimum Supply Heating setpoint

20

0 to 90C

C8

MAXC

Maximum Supply Cooling setpoint

18

2 to 30C

C9

MINC

Minimum Supply Heating setpoint

10

2 to 30C

C10

MIND

Supply minimum demand, used for switching between heating and cooling

4

0.0 to 10.0

C11

OCCO

When set controller will only run during the occupied period

0

0 to 1

C12

HPRD

heating valve period or minimum on time

depends on driver type

1 to 60 secs/10

C13

HDLY

Interlock delay
negative value delays fan after heating starts
positive value cause run on of fan after heating shuts down

0

-30.0 to 30.0 minutes

C14

CPRD

cooling valve period or minimum on time

depends on driver type

1 to 60 secs/10

C15

CDLY

Interlock delay
negative value delays fan after cooling starts
positive value cause run on of fan after cooling shuts down

0

-30.0 to 30.0 minutes

C16

FPRD

Fan period, minimum time to change fan speed steps (7R only)

12 (2 minutes)

1 to 60 secs/10

C17

FRPT

Frost protect
0 no action
1 open heating valve 50%
2 open heating valve and run fan

0

0 to 2

C18

MANL

Manual level , from Doorway

0

-100 to 100 %

C19

HTSC

Heat source; points to source of Heating Energy

1

8255

C20

CLSC

Cool source; points to source of Cooling Energy

0

8255

C21

HTCT
Value of CT setpoint sent to Heat Source, % value sent if 0 0 0 to 100 C

C22

CLCT

Not supported

Reserved for Value of CT setpoint sent to Cool Source

0 0 to 20C
C23 MIDP

-1: selects two pipe operation

-2: Two pipe plus electric heater( heating mode only)

-3: Two pipe plus electric heater (heating and cooling mode)

0: normal operation

1 to 99: Mid position for Airside Damper control

0 -3 to 99%
C24 TRRG Sontay Trim Pot +/- range 5 0.0 to 10.0C

C25

ALRM

alarm mode 
0 ignore alarms
1 report alarms
2 report alarms, shut down all outputs on alarm
3 report alarms, shut down all outputs on STOP alarm or sensor fail alarm

1

0 to 3

C26

ALST

not used

0

0 to 1

Monitoring Parameters

Input Monitoring (3R and 4R variants)


ref

Description

default

range

C30

EXTI

external input  occupation/window contact et al

0 to 1

C31

OCCD

occupied

0 to 1

C32

not used

0 to 1

C33

not used

0 to 1

C34

COOL

cooling mode

0 to 1

C35

RLYA

relay A

0 to 1

C36

RLYB

relay B

0 to 1

C37

RLYC

relay C

0 to 1

C38

AUTO

Automatic/manual mode

0 to 1

C39

OVRD

override

0 to 1

C42

HAND
Manual Hand Mode 0
0 to 1

C43
POT Potentiometer fitted to board 0
0 to 1
C44 SERV operation of Registration button from Doorway self resets 0 to 1

C45

CGST

configuration mode

Input Monitoring (7R variants)


ref
 
Description

default

range

C30

EXTI

input A occupation/window contact et al
 
0 to 1

C31

OCCD

occupied
 
0 to 1

C32

CRSE
SeaChange diagnostic use (cool raise)  
0 to 1

C33

CLWR
SeaChange diagnostic use (cool lower)  
0 to 1

C34

HSEL
SeaChange diagnostic use (heating select)  
0 to 1

C35

RLYD

relay D (fan 1) status
 
0 to 1

C36

RLYE

relay E (fan 2) status
 
0 to 1

C37

RLYF

relay F (fan 3) status
 
0 to 1

C38

AUTO

Automatic/manual mode
 
0 to 1

C39

OVRD

override
 
0 to 1

C40

FSWM


Sontay Fan Switch Mode
0 Intelligent Occupation switching changing fan switch after hours will bring unit back on. Select AUTO to switch off

1 Forced Occupation if Fan Switch is 1-3

0
0 to 1
C42 HAND Manual Hand mode from Doorway   0 to 1

C44
SERV
operation of Registration button from Doorway self resets
 
0 to 1

C45

CGST

configuration mode
   

Sensors


ref
 

Description

default

range

C50

SPLA

supply air temperature
 

5.0 to 35.0 C 

C51

RTNA

return air temperature
 

5.0 to 35.0 C

C52

HCOP

heat cool output to drivers (cooling negative)
 

-100 to 100 %

C53

SPSL

supply (off coil) setpoint
 

5.0 to 35.0 C

C54

SPRT

return air setpoint
 

5.0 to 35.0 C

C55

HDMD

heat demand from return loop or from Zone Controller
 

0 to 100%

C56

CDMD

cool demand from return loop or from Zone Controller
 

0 to 100%

Knobs


ref
 
Description

default

range

K1

SPOC

Occupied setpoint

20.0

5.0 to 35.0 C

K2

SPNO

Non Occupied setpoint

10.0

5.0 to 20.0 C

K3

SPSV

Supervised setpoint from Master controller
 
0 to 35.0 C

K4

SPTR

Setpoint Trim

0

-10.0 to 10.0 C

K5

MXVA*

Maximum voltage channel A

10.0

0.0 to 10.0 volt

K6

MNVA*

Minimum voltage channel A

0.0

0.0 to 10.0 volt

K7

MXVB*

Maximum voltage channel B

10.0

0.0 to 10.0 volt

K8

MNVB*

Minimum voltage channel B

0.0

0.0 to 10.0 volt

* /AOP versions only (to special order)