Engineering Parameters FCUx4c1loop parameters
|
ref |
Description |
default |
range |
|
C69 |
RTLP |
selects Return Loop parameters |
0 |
0 to 1 |
C70 |
UNDH |
sets very Low muzzy level for heating loop |
3.5 :1.00 |
10 to 200 |
C71 |
OVRH |
sets very High muzzy level for heating loop |
3.5 :1.00 |
10 to 200 |
C72 |
DBBH |
deadband sets limit for OK band for heating loop |
1.5 :0.50 |
10 to 100 |
C73 |
RCGH |
max rate of change heating |
5 to 100 |
|
C74 |
GN H |
gain heating |
20 :50 |
1 to 200 |
C75 |
UNDC |
sets very Low muzzy level for cooling loop |
3.5 :1.00 |
10 to 200 |
C76 |
OVRC |
sets very High muzzy level for cooling loop |
3.5 :1.00 |
10 to 200 |
C77 |
DBBC |
deadband sets limit for OK band for cooling loop |
1.5 :0.50 |
10 to 100 |
C78 |
RCGC |
max rate of change cooling |
5 to 100 |
|
C79 |
GN C |
gain cooling |
20 :50 |
1 to 200 |
ref |
Description |
default |
range |
|
C80 |
XCFG |
forces exit from config mode |
||
C81 |
GRP |
own group number |
||
C82 | ---- | not used | ||
C83 | MANL | fixed HAND Manual | 0 | -100 to 100 % |
C84 | NCRS | number of no comms resets | 0 | 0 to 255 |
C85 | SWRS | number of software resets | 0 | 0 to 255 |
C86 | MANS | manual state locally from buttons | 0 | 0 to 99 |
C87 | SNDD | send demand delay | 6 (1 minute) | 0 to 255 seconds/10 |
C88 | CSTP | control step | 0 to 99 |
ref |
Description |
default |
range |
|
C90 |
NOAL |
no alarm |
0 to 1 | |
C91 |
SENF |
sensor fail |
0 to 1 | |
C92 |
EXTN |
alarm for external input |
0 to 1 | |
C93 |
STOP |
STOP alarm received |
0 to 1 | |
C93 |
INVD |
Invalid Configuration settings, check INMD |
0 to 1 |
ref |
Description |
default |
range |
|
C100 |
#ACT |
number of Actuators registered to this controller |
||
C101 |
HTSC |
heat source |
0 | 0 to 8255 |
C102 |
CLSC |
cool source |
0 | 0 to 8255 |
C103 |
OCDS |
occupation destination |
0 | 0 to 8255 |
ref |
Description |
default |
range |
|
C120 |
TEST |
sets Test Mode |
0 |
0 to 1 |
C121 |
MZON |
zone number of master zone |
0 |
0 to 200 |
ref |
Description |
default |
range |
|
C130 |
PN A |
config variable number for channel A |
51 |
0 to 255 |
C131 |
PT A |
period code for plot A |
1 |
1 to 4 |
C132 |
PN B |
config variable number for channel B |
52 |
0 to 255 |
C133 |
PT B |
period code for plot B |
1 |
1 to 4 |
C134 |
PN C |
config variable number for channel C |
53 |
0 to 255 |
C135 |
PT C |
period code for plot C |
1 |
1 to 4 |
ref |
Description |
default |
range |
|
C150 |
HTYP |
heating driver type |
0 to 5 |
|
C151 |
HSTG |
number of heating stages |
0 to 8 |
|
C152 |
CTYP |
cooling driver type |
0 to 5 |
|
C153 |
CSTG |
number of cooling stages |
0 to 8 |
|
C154 |
FTYP |
fan driver type |
0 to 7 |
|
C155 |
FSTG |
number of fan stages |
0 to 5 |
|
C156 |
HDRV |
heating driver input |
0 to 5 |
|
C157 |
CDRV |
cooling driver input |
0 to 5 |
|
C158 |
FDRV |
fan driver input |
0 to 5 |
ref |
Description |
default |
range |
|
C170 |
ACH1 input |
analogue input channel 1 |
0 to 60000 |
|
C171 |
ACH2 input |
analogue input channel 2 |
0 to 60000 |
|
C172 |
ACH3 input |
analogue input channel 3 (potentiometer) |
0 to 60000 |
|
C173 | ACH4 | analogue input channel 4 | 0 to 60000 |