Configurable Plots

The number of plots varies with product type, but the standard setup will plot the first n sensors where n is the number of plots.
e.g. for an AHU Controller
Plot 1 Supply air temperature
Plot 2 Return Air temperature
Plot 3 Heat/cool output -100 to +100 (negative for cooling)
The plot routine has been enhanced and the plotting period is now selectable by changing the plot Period Type parameter PT . This matches Doorway (and TREND) and is as follows
PT (A,B,C or D)
Period type
1
Every 15 minutes
2
Once per day at 0100
3
Every minute
4
Every hour on the hour
It is recommended that period type 3 is not generally used except while commissioning since frequent plot re-scaling (every 90 minutes) will eventually wear out the EEPROM memory.
The plots are now automatically re-scaled within the controller to achieve the best resolution for the data recorded. This happens at the end of every 96 readings when new maximum and minimum settings are calculated and also if a new value is outside the current range settings.
The parameter to be plotted can be changed form the standard settings, by setting the configuration parameter PN to the config number of the parameter to be plotted. The config numbers can be found in the Config Tables for the particular product.
 

Plot configuration

*The plots are designated by letter A,B,C or D. Many products only support two plots A and B.

ref

 

Description

default

range

C130
PN A
config variable number for channel A
51
0 to 255
C131
PT A
period code for plot A
1
1 to 4
C132
PN B
config variable number for channel B
52
0 to 255
C133
PT B
period code for plot B
1
1 to 4
C134
PN C
config variable number for channel C
53
0 to 255
C135
PT C
period code for plot C
1
1 to 4
C136
PN D
config variable number for channel D
54
0 to 255
C137
PT D
period code for plot D
1
1 to 4
 

 