Configuration Tables CSCVT3a5

Monitoring Parameters

Label Doorway code Secondary Controller (VTC3a)
FRST I1 (C30) Frost Protect
OCC I2 (C31) Occupied
COOL I5 (C34) Control in cooling mode
RLYA I6 (C35) relay A
RLYB I7 (C36) relay B
RLYC I8 (C37) relay C
AUTO W1 (C38) Automatic, control mode
OVRD W2 (C39) Override
CGST W8 (C45) config mode
HTMP S1 (C50) Heating temperature (CTMP cooling temp for CSCVT version)
DMND S2 (C51) Control output
REQD S3 (C52) Current setpoint
ZDMD S4 (C53) Highest demand from the zones
AVDM S5 (C54) Average demand from the zones
NOCC S6 (C55) Number of zones occupied
FLOW S7 (C56) Flow temperature
RTRN S8 (C57) Return Temperature
MAXF K1 (C60) Maximum Flow setpoint
MINF K2 (C61) Minimum Flow setpoint

Configuration Parameters

ref. Neumonic description default range
C1 NOSP Non Occupied setpoint 10 2 to 15C
C2 MAXF maximum Flow setpoint 18 5 to 100C
C3 MINF minimum Flow setpoint 8 1 to 100C
C4 SACT sensor action

0 either

1 average

2 maximum

3 minimum

0  
C5 SCAL sensor calibration 0.0 C
C6 SPTY setpoint type

0 CT control Flow fixed at Flow Max

1 scheduled between FlowMin and FlowMax with respect to Maximum cooling demand from the zones

2 scheduled between Flow Min and Flow Max with respect to average cooling demand from the zones

1 0 to 2
C7 MIND minimum demand 5 0 to 100%
C8 MNOC minimum number of occupied zones 0 0 to 200
C9 MNAV minimum value for average demand 0 0 to 100%
C10 GAIN CT setpoint to chiller is this amount below own setpoint 2 0 to 10C
C11 PERD stroke time or minimum on time 18 1 to 240secs/10
C12 CMDE control mode

0 driver only, disable control loops

1 control loops active

1 0 to 1
C13 INLK driver interlock 0 0 to 4
C14 ALRM alarm mode 0 0 to 4
C15 ALST alarm state 0 0 to 1
C16 CLSC cool source 0 0 to 100
C17 TYPE driver type, default VP plus oss switch 7 0 to 9