ref. |
Neumonic |
description |
default |
range |
C1 |
NOSP |
Non Occupied setpoint |
30 |
10 to 50C |
C2 |
MAXF |
maximum Flow setpoint |
18 |
5 to 100C |
C3 |
MINF |
minimum Flow setpoint |
8 |
1 to 100C |
C4 |
SACT |
sensor action
0 either
1 average
2 maximum
3 minimum
|
0 |
0 to 4 |
C5 |
SCAL |
sensor calibration |
0.0 |
-10.0 to 10.0 C |
C6 |
SPTY |
Setpoint Type:
for CTU:
0: Constant temperature setpoint (value set in MAXF)
for VTU:
1: Setpoint varies linearly based on Maximum Demand Signal from Consumers
2: Setpoint varies linearly based on Average Demand Signal from Consumers
|
1 |
0 to 2 |
C7 |
INMD |
Input Mode use of terminals
'temp a'
- 0 additional temperature
input for max,min,average using SACT
- 1 External occupation (short
= occupied) AND internal occ
- 2 External occupation OR
internal occ
- 3 External occupation signal
only
- 4 Alarm input
- 5 Pump Alarm
|
0 |
0 to 5 |
C8 |
MIND |
Minimum Demand:
When highest demand from all registered zones is less than this value,controller
uses non occupied FRST setpoint
0: controller runs to Occupied setpoint for Occupation period |
5 |
0 to 100% |
C9 |
MNAV |
minimum value for average demand |
0 |
0 to 100% |
C10 |
MNOC |
minimum number of occupied zones |
0 |
0 to 200 |
C11 |
MNDV |
minimum driver demand, effects control
of Fan or Pump |
0 |
0 to 100% |
C12 |
GAIN |
Flow Gain:
amount subtracted from the Controllers setpoint and sent as a CT setpoint
to Cool Provider; offsets distribution temperature gains |
2 |
0 to 25C |
C13 |
CPRD |
stroke time or minimum on time |
depends on driver type |
1 to 240secs/10 |
C14 |
CDLY |
Interlock delay;
0: Pump starts as valve opens; no delay.
Negative value: Valve opens before Pump starts.
Positive Value: Pump runs on after valve shuts down.
|
0 |
-60.0 to 60.0 minutes |
C15 |
FPRD |
not used in this application; set to 12 |
12 |
1 to 240secs/10 |
C16 |
FRPT |
frost protect mode
0 none
1 valve only
2 valve and pump
3 pump only
|
0 |
0 to 3 |
C17 |
MANL |
manual level |
0 |
-100 to 100 % |
C18 |
CMDE |
Control Mode, when set to 0 disables control
loop, sensors can be used for monitoring. Demands passed direct to outputs. |
1 |
0 to 1 |
C19 |
ALRM |
alarm mode
0 ignore alarms
1 report alarms
2 report alarms, shut down all outputs on local alarm
3 report alarms, shut down all outputs on STOP alarm
or local alarm
4 report alarms, shut down all outputs on STOP alarm
only
|
0 |
0 to 4 |
C20 |
ALST |
Alarm State sets the state which is considered to
be the Alarm state for the External Alarm input:
0 open circuit
1 short circuit
|
0 |
0 to 1 |
C21 |
CLSC |
Cool Source; points Energy Demand to source
of Cooling energy |
0 |
0 to 8255 |
C22
|
OCDS |
Occupation Destination:
points Occupancy Demand at another controller |
0 |
0 to 8255 |
C23 |
CLCT |
Cooling Demand Selector:
Set to1 if CLSC is pointing Energy Demand at a Provider
module (Chiller Controller) - demand sent as a CT setpoint
Set to 0 if CLSC is pointing to another Secondary
Circuit Controller - demand sent as a % signal
|
0 |
0 to 1 |
Label |
Doorway code |
Description |
EXTI |
I1 (C30)
|
External input (function depends on input
mode) |
OCC |
I2 (C31) |
Occupied |
COND |
I4 (C33) |
Condensation Alarm (cooling version only) |
RLYA |
I6 (C35) |
relay A |
RLYB |
I7 (C36) |
relay B |
RLYC |
I8 (C37) |
relay C |
AUTO |
W1 (C38) |
Automatic, control mode |
OVRD |
W2 (C39) |
Override |
INLP |
W3 (C40) |
Interlock Pump (PCO sub module) |
ESTF |
W4 (C41) |
Establish Flow (PCO sub module) |
HAND |
W5 (C42) |
Manual HAND Override from Doorway |
POT |
W6 (C43) |
enable use of optional
potentiometer (special order hardware) |
SERV |
W7 (C44) |
remote operation
of registration (service) button |
CGST |
W8 (C45) |
config mode status |
|
SENSORS |
|
CTMP |
S1 (C50) |
Chilled Water Temperature for control (resultant
of processing by SACT) |
DMND |
S2 (C51) |
Control output |
REQD |
S3 (C52) |
Current setpoint |
ZDMD |
S4 (C53) |
Highest demand from the zones |
AVDM |
S5 (C54) |
Average demand from the zones |
NOCC |
S6 (C55) |
Number of zones occupied |
FLOW |
S7 (C56) |
Flow temperature |
RTRN |
S8 (C57) |
Return Temperature (2 input hardware only
- available by special order) |
|
KNOBS |
|
MAXF |
K1 (C60) |
Maximum Flow setpoint (for VTU and CTU)
|
MINF |
K2 (C61) |
Minimum Flow setpoint (for VTU only) |