Secondary Circuit Controller
for Temperature Control of Heating or Cooling Circuits
with 3 x Triac Outputs (3T version)

with 2 x 0-10V DC Outputs (AOP version)
Chiller Controller
with 3 x Triac Outputs

Notes
(Sec. Circ.)
Notes
(Chiller)
Configuration Tables Data Sheet M3
(731kb PDF) s/w version 4c1
Wiring History

Configuration Tables
(for cooling variants and chiller controller)

Latest released version is 4d1 (beta)
Document last updated 01/02/2002
New features this issue are in
RED text

Configuration Parameters

Doorway / InSite Code Label Description Units Default Value Range
C1 NOSP Non Occupied Setpoint
Deg C 40 10 to 50
C2 MAXF Maximum Flow Setpoint
Deg C 16 5 to 100
C3 MINF Minimum Flow Setpoint
Deg C 11 1 to 100
C4 SACT Sensor Action
0: Use ‘temp b’ sensor for control and optionally use ‘temp a’ sensor for monitoring or VFC using INMD
1: Use average of valid sensor values (INMD = 0)
2: Use maximum of valid sensor values (INMD = 0)
3: Use minimum of valid sensor values (INMD = 0)
- 0 0 to 3
C5 SCAL Sensor Calibration
Deg C 0 -10 to +10
C6 SPTY Setpoint Type (CTU type only)
0: Constant temperature setpoint (value set in MAXF)
- 0 0 to 2
    Setpoint Type (VTU types only)
1: Setpoint varies linearly based on Maximum Demand Signal from Consumers
2: Setpoint varies linearly based on Average Demand Signal from Consumers
- 1 0 to 2
C7 INMD Input Mode for input terminals 3 and 4 ‘temp a’
0: Additional temperature input for max, min, ave using SACT
1: External occupation (input linked = Occupied) AND with internal Occupation
2: External occupation (input linked = Occupied) OR with internal Occupation
3: External Occupation signal only
4: Alarm input
5: Pump alarm
- 0 0 to 5
C8 MIND Minimum Demand
% 5 0 to 100
C9 MNAV Minimum Average Demand
% 0 0 to 100
C10 MNOC Minimum number of Occupied Zones
- 0 0 to 200
C11 MNDV Minimum demand for driver, affects control of Fan or Pump % 5 0 to 100
C12 GAIN Flow Gain added to setpoint and sent to Cooling Provider Deg C 2 0 to 20
C13 CPRD Cooling Driver Stroke/Minimum On Time Secs/10 18 1 to 240
C14 CDLY Cooling Interlock Delay
Negative value opens valve before pump starts
Positive value runs pump on after valve shuts down
Mins 5 - 30 to 30
C15 FPRD Not used in this application Secs/10 12 1 to 240
C16 FRPT

Frost Protection Mode
0: No action
1: Open heating valve 50%
2: Open heating valve and run pump
3: Run pump only

- 2 0 to 3
C17 MANL Manual Level, set by Doorway or InSite % 0 -100 to 100
C18 CMDE Control Mode
0: Control loop disabled, demand passed direct to outputs
1: Normal control
- 1 0 to 1
C19 ALRM Alarm Mode
0: Ignore alarms
1: Report all alarms to Doorway/InSite,
no control action, no flashing Temp indicator
2: Report all alarms, shut down all outputs on local alarm
3: Report all alarms, shut down on STOP alarm or local alarm
4: Report all alarms, shut down on STOP alarm only
- 0 0 to 4
C20 ALST Alarm report sense
0: Alarm if input = 0, pump running if input = 1
1: Alarm if input = 1, pump running if input = 0
- 1 0 to 1
C21 CLSC Cool Source - 0 0 to 8255
C22 OCDS Occupation Destination - 0 0 to 8255
C23 CLCT Cooling Demand sent as CT
0: CLSC interconnects to Secondary Circuit, demand sent as %
1: CLSC interconnects to Chiller, demand sent as CT temp

- 1 0 to 1
C24
XCSC
Allows demand to be sent to an addtional cool source used primarily in Natural ventilation applications, leave at 0 to disable.
cool source number 1-25 send control demand
cool source +100 send Max Zone Demand
cool source +200 send Average incoming Demand
-
0
0 to 225

 

Monitoring Parameters

Doorway / InSite Code Label Description Units Default Value Range
I1 (C30) EXTI External Input (function depends on INMD setting) - - 0 to 1
I2 (C31) OCCD Occupied - - 0 to 1
I3 (C32) HTOR Heating Override, when ON this controller has been overriden OFF by the interlocked Heating controller. See knob IHSC - - 0 to 1
I4 (C33) COND Condensation Alarm - - 0 to 1
I5 (C34) COOL Cooling Mode - - 0 to 1
I6 (C35) RLYA Triac A Status (for 3T types only - - 0 to 1
I7 (C36) RLYB Triac B Status (for 3T types only - - 0 to 1
I8 (C37) RLYC Triac C Status (for 3T types only - - 0 to 1
W1 (C38) AUTO Automatic/Manual Status - - 0 to 1
W2 (C39) OVRD Override - - 0 to 1
W3 (C40) ILKP Interlock Pump (PCO submodule) - - 0 to 1
W4 (C41) ESTF Establish Flow (PCO submodule) - - 0 to 1
W5 (C42) HAND Manual Hand; use with MANL to set output level - 0 0 to 1
W6 (C43) POT Not used in this application - 0 0 to 1
W7 (C44) SERV Service Pin Message (to Doorway and InSite, self resetting) - - 0 to 1
W8 (C45) CGST Configuration Mode Status - - 0 to 1
S1* (C50) CTMP Chilled Water Temperature Deg C - -
S2* (C51) DMND Control Demand % - -100 to 100
S3 (C52) REQD Controller current setpoint Deg C - -
S4 (C53) ZDMD Highest demand from zones % - -
S5 (C54) AVDM Average demand from zones % - -
S6 (C55) NOCC Number of zones Occupied - - -
S7 (C56) FLOW Flow Temperature Deg C - -
S8 (C57) RTRN Return Temperature Deg C - -
K1 (C60) MAXF Maximum Flow Setpoint (for VTU and CTU) Deg C 16 10 to 100
K2 (C61) MINF Minimum Flow Setpoint (for VTU only)
Deg C 11 5 to 100
K3 (C62) IHSC Interlocked Heat Source, when set this points to the interlocked heating secondary controller and only the heating or the cooling controller can be active, the controller with the highest demand wins. Used to control the common meduim of Two Pipe systems.
- - 0 to 8255
    Engineering Parameters; only accessible via Doorway and InSite      
C90 NOAL No Alarms; all alarms cleared when set to 1 - - 0 or 1
C91 SENF Sensor Failed (when set to 1) - - 0 or 1
C92 EXTN Volt-Free Contact alarm (when set to 1) - - 0 or 1
C93 CNDF Condensation detected (when set to 1) - - 0 or 1
C94 PMPF Pump Failed (when set to 1) - - 0 or 1
C95 STOP STOP alarm received (when set to 1) - - 0 or 1
C180 DI A Input 3-4 digital status - - 0 or 1
C181 DI B Input 5-6 digital status - - 0 or 1
    * 24 hour plots available for these values by default      