Configuration Tables
|
Secondary Circuit Controller |
Features new this issue are in RED textLatest released version is 4e1 |
for Temperature Control of Cooling Circuits
|
Configuration Parameters |
|||||
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
C1 |
NOSP |
Non Occupied Setpoint
|
Deg C |
40 |
10 to 50 |
C2 |
MAXF |
Maximum Flow Setpoint
|
Deg C |
16 |
5 to 100 |
C3 |
MINF |
Minimum Flow Setpoint
|
Deg C |
11 |
1 to 100 |
C4 |
SACT |
Sensor Action
|
- |
0 |
0 to 3 |
C5 |
SCAL |
Sensor Calibration
|
Deg C |
0 |
-10 to +10 |
C6 |
SPTY |
Setpoint Type (CTU type only)
|
- |
0 |
0 to 2 |
|
|
Setpoint Type (VTU types only)
|
- |
1 |
0 to 2 |
C7 |
INMD |
Input Mode for input terminals 3 and 4 temp a
|
- |
0 |
0 to 5 |
C8 |
MIND |
Minimum Demand
|
% |
5 |
0 to 100 |
C9 |
MNAV |
Minimum Average Demand
|
% |
0 |
0 to 100 |
C10 |
MNOC |
Minimum number of Occupied Zones
|
- |
0 |
0 to 200 |
C11 |
MNDV |
Minimum demand for driver, affects control of Fan or Pump |
% |
5 |
0 to 100 |
C12 |
GAIN |
Flow Gain added to setpoint and sent to Cooling Provider |
Deg C |
2 |
0 to 20 |
C13 |
CPRD |
Cooling Driver Stroke/Minimum On Time |
Secs/10 |
18 |
1 to 240 |
C14 |
CDLY |
Cooling Interlock Delay
|
Mins |
5 - |
30 to 30 |
C15 |
FPRD |
Not used in this application |
Secs/10 |
12 |
1 to 240 |
C16 |
FRPT |
Frost Protection Mode
|
- |
2 |
0 to 3 |
C17 |
MANL |
Manual Level, set by Doorway or InSite |
% |
0 |
-100 to 100 |
C18 |
CMDE |
Control Mode
|
- |
1 |
0 to 1 |
C19 |
ALRM |
Alarm Mode
|
- |
0 |
0 to 4 |
C20 |
ALST |
Alarm report sense
|
- |
1 |
0 to 1 |
C21 |
CLSC |
Cool Source |
- |
0 |
0 to 9255 |
C22 |
OCDS |
Occupation Destination |
- |
0 |
0 to 9255 |
C23 |
CLCT |
Cooling Demand sent as CT
|
- |
1 |
0 to 1 |
C24 |
XCSC |
Allows demand to be sent to an addtional cool source used primarily
in Natural ventilation applications, leave at 0 to disable.
|
- |
0 |
0 to 225 |
Monitoring Parameters |
|||||
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
I1 (C30) |
EXTI |
External Input (function depends on INMD setting) |
- |
- |
0 to 1 |
I2 (C31) |
OCCD |
Occupied |
- |
- |
0 to 1 |
I3 (C32) |
HTOR |
Heating Override, when ON this controller has been overriden OFF by the interlocked Heating controller. See knob IHSC |
- |
- |
0 to 1 |
I4 (C33) |
COND |
Condensation Alarm |
- |
- |
0 to 1 |
I5 (C34) |
COOL |
Cooling Mode |
- |
- |
0 to 1 |
I6 (C35) |
RLYA |
Triac A Status (for 3T types only |
- |
- |
0 to 1 |
I7 (C36) |
RLYB |
Triac B Status (for 3T types only |
- |
- |
0 to 1 |
I8 (C37) |
RLYC |
Triac C Status (for 3T types only |
- |
- |
0 to 1 |
W1 (C38) |
AUTO |
Automatic/Manual Status |
- |
- |
0 to 1 |
W2 (C39) |
OVRD |
Override |
- |
- |
0 to 1 |
W3 (C40) |
ILKP |
Interlock Pump (PCO submodule) |
- |
- |
0 to 1 |
W4 (C41) |
ESTF |
Establish Flow (PCO submodule) |
- |
- |
0 to 1 |
W5 (C42) |
HAND |
Manual Hand; use with MANL to set output level |
- |
0 |
0 to 1 |
W6 (C43) |
POT |
Not used in this application |
- |
0 |
0 to 1 |
W7 (C44) |
SERV |
Service Pin Message (to Doorway and InSite, self resetting) |
- |
- |
0 to 1 |
W8 (C45) |
CGST |
Configuration Mode Status |
- |
- |
0 to 1 |
S1* (C50) |
CTMP |
Chilled Water Temperature |
Deg C |
- |
- |
S2* (C51) |
DMND |
Control Demand |
% |
- |
-100 to 100 |
S3 (C52) |
REQD |
Controller current setpoint |
Deg C |
- |
- |
S4 (C53) |
ZDMD |
Highest demand from zones |
% |
- |
- |
S5 (C54) |
AVDM |
Average demand from zones |
% |
- |
- |
S6 (C55) |
NOCC |
Number of zones Occupied |
- |
- |
- |
S7 (C56) |
FLOW |
Flow Temperature |
Deg C |
- |
- |
S8 (C57) |
RTRN |
Return Temperature |
Deg C |
- |
- |
K1 (C60) |
MAXF |
Maximum Flow Setpoint (for VTU and CTU) |
Deg C |
16 |
10 to 100 |
K2 (C61) |
MINF |
Minimum Flow Setpoint (for VTU only)
|
Deg C |
11 |
5 to 100 |
K3 (C62) |
IHSC |
Interlocked Heat Source, when set this points to the interlocked heating
secondary controller and only the heating or the cooling controller can
be active, the controller with the highest demand wins. Used to control
the common meduim of Two Pipe systems.
|
- |
- |
0 to 8255 |
|
|
Engineering Parameters; only accessible via Doorway and InSite |
|
|
|
C90 |
NOAL |
No Alarms; all alarms cleared when set to 1 |
- |
- |
0 or 1 |
C91 |
SENF |
Sensor Failed (when set to 1) |
- |
- |
0 or 1 |
C92 |
EXTN |
Volt-Free Contact alarm (when set to 1) |
- |
- |
0 or 1 |
C93 |
CNDF |
Condensation detected (when set to 1) |
- |
- |
0 or 1 |
C94 |
PMPF |
Pump Failed (when set to 1) |
- |
- |
0 or 1 |
C95 |
STOP |
STOP alarm received (when set to 1) |
- |
- |
0 or 1 |
C180 |
DI A |
Input 3-4 digital status |
- |
- |
0 or 1 |
C181 |
DI B |
Input 5-6 digital status |
- |
- |
0 or 1 |
|
|
* 24 hour plots available for these values by default |
|
|
|
|
|
Plotting interval and plotted variable changeable via Doorway or InSite |
|
|
|