Configuration Tables
|
Multi Channel Controller
|
software release 4e1 |
MCC / DIN / 3T |
Configuration Parameters |
|||||
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
C1 |
FRSP |
Frost protection/ Non Occupied setpoint |
Deg C |
10 |
2 to 15 |
C2 |
MAXF |
Maximum Flow setpoint (used with HTCT to set CT setpoint in BLR) |
Deg C |
70 |
5 to 100 |
C3 |
MINF |
Minimum Flow setpoint (used with HTCT to set CT setpoint in BLR) |
Deg C |
30 |
1 to 100 |
C4 |
SACT |
Sensor action:
|
- |
0 |
0 to 3 |
C5 |
SCAL |
Sensor calibration |
Deg C |
0 |
-10 to 10 |
C6 |
SPTY |
Setpoint Type (used with HTCT to set CT setpoint in BLR):
|
- |
0 |
0 to 2 |
C7 |
INMD |
Input Mode use of terminals 3-4 'temp a'
|
- |
0 |
0 to 5 |
C8 |
MIND |
Minimum Demand:
|
% |
5 |
0 to 100 |
C9 |
MNDV |
Minimum demand for driver, affects control of Fan or Pump |
% |
0 |
0 to 100 |
C10 |
LOSS |
Flow Loss:
|
Deg C |
10 |
0 to 20 |
C11 |
PRDA |
Minimum on time channel A |
Secs/10 |
Depends on type |
1 to 240 |
C12 |
DLYA |
Interlock delay channel A;
|
Mins |
0 |
-60 to 60 |
C13 |
PRDB |
Minimum on time channel B |
Secs/10 |
Depends on type |
1 to 240 |
C14 |
DLYB |
Interlock delay channel B;
|
Mins |
0 |
-60 to 60 |
C15 |
PRDC |
Minimum on time channel C |
Secs/10 |
Depends on type |
1 to 240 |
C16 |
IVOP |
Invert outputs when set provided driver is set to sequence or time proportioning |
- |
0 |
0 to 1 |
C17 |
FRPT |
Frost protect mode:
|
- |
0 |
0 to 3 |
C18 |
MANL |
Manual level |
- |
0 |
0 to 1 |
C19 |
CMDE |
Control Mode, when set to 0 disables control loop, sensors can be used for monitoring. Demands passed direct to outputs. |
- |
0 |
0 to 1 |
C20 |
ALRM |
Alarm mode:
|
- |
0 |
0 to 4 |
C21 |
ALST |
Alarm State sets the state which is considered to be the Alarm state
for the External Alarm input:
|
- |
0 |
0 to 1 |
C22 |
HTSC |
Heat Source; points Energy Demand to source of Heating energy |
- |
1 |
0 to 9255 |
C23 |
OCDS |
Occupation Destination:
|
- |
0 |
0 to 9255 |
C24 |
HTCT |
Heating Demand Selector:
|
- |
1 |
0 to 1 |
Monitoring Parameters |
|||||
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
I1 (C30) |
EXTI |
External input (function depends on input mode) |
- |
- |
0 to 1 |
I2 (C31) |
OCC |
Occupied |
- |
- |
0 to 1 |
I6 (C35) |
RLYA |
Triac A Status |
- |
- |
0 to 1 |
I7 (C36) |
RLYB |
Triac B Status |
- |
- |
0 to 1 |
I8 (C37) |
RLYC |
Triac C Status |
- |
- |
0 to 1 |
W1 (C38) |
AUTO |
Automatic/Manual Status |
- |
- |
0 to 1 |
W2 (C39) |
OVRD |
Override |
- |
- |
0 to 1 |
W3 (C40) |
ILKP |
Interlock Pump |
- |
- |
0 to 1 |
W5 (C42) |
HAND |
Manual Hand; use with MANL to set output level |
- |
0 |
0 to 1 |
W6 (C41) |
POT |
Enable use of optional potentiometer (special order hardware) |
- |
- |
0 to 1 |
W7 (C44) |
SERV |
Service Pin Msg (to Doorway +InSite, self resetting) |
- |
- |
0 to 1 |
W8 (C45) |
CGST |
Configuration Mode Status |
- |
- |
0 to 1 |
S1* (C50) |
HTMP |
Heating temperature (resultant of processing by SACT) (for monitoring only) |
Deg C |
- |
- |
S2* (C51) |
DMND |
Control Demand |
% |
- |
- |
S3 (C52) |
REQD |
Current Setpoint |
Deg C |
- |
- |
S4 (C53) |
DMDA |
Demand received for channel A (see knob 3) |
% |
- |
- |
S5 (C54) |
DMDB |
Demand received for channel B (see knob 4) |
% |
- |
- |
S6 (C55) |
DMDC |
Demand received for channel C (see knob 5) |
% |
- |
- |
S7 (C56) |
FLOW |
Temperature (terminals 5-6) |
Deg C |
- |
- |
S8 (C57) |
RTRN |
Temperature (terminals 3-4) |
Deg C |
- |
- |
K1 (C60) |
MAXF |
Maximum Flow setpoint (used with HTCT to set CT setpoint in BLR) |
Deg C |
- |
- |
K2 (C61) |
MINF |
Minimum Flow setpoint (used with HTCT to set CT setpoint in BLR) |
Deg C |
- |
- |
K3 (C62) |
ZONA |
Number of Zone Controller whose demand is to be used for channel A |
- |
- |
- |
K4 (C63) |
ZONB |
Number of Zone Controller whose demand is to be used for channel B |
- |
- |
- |
K5 (C64) |
ZONC |
Number of Zone Controller whose demand is to be used for channel C |
- |
- |
- |
|
Engineering Parameters; only accessible via Doorway and InSite |
|
|||
C90 |
NOAL |
No alarms ; all alarms cleared when set to 1 |
- |
- |
0 or 1 |
C91 |
SENF |
Sensor fail alarm (when set to 1) |
- |
- |
0 or 1 |
C92 |
EXTN |
External alarm input (when set to 1) |
- |
- |
0 or 1 |
C93 |
CNDF |
Condensation alarm (when set to 1) |
- |
- |
0 or 1 |
C94 |
PMPF |
Pump fail alarm (when set to 1) |
- |
- |
0 or 1 |
C95 |
STOP |
Stop alarm received (when set to 1) |
- |
- |
0 or 1 |
C180 |
DI A |
Input 3-4 digital status |
- |
- |
0 or 1 |
C181 |
DI B |
Input 5-6 digital status |
- |
- |
0 or 1 |
|
* 24 hour plots available for these values by default |
|
|||