Configuration Tables HSCVT4b1

Monitoring Parameters

Label Doorway code Description
FRST I1 (C30) Frost Protect
OCC I2 (C31) Occupied
COOL I5 (C34) Control in cooling mode
RLYA I6 (C35) relay A
RLYB I7 (C36) relay B
RLYC I8 (C37) relay C
AUTO W1 (C38) Automatic, control mode
OVRD W2 (C39) Override
CGST W8 (C45) config mode
  SENSORS  
HTMP S1 (C50) Heating temperature for control
DMND S2 (C51) Control output
REQD S3 (C52) Current setpoint
ZDMD S4 (C53) Highest demand from the zones
AVDM S5 (C54) Average demand from the zones
NOCC S6 (C55) Number of zones occupied
FLOW S7 (C56) Flow temperature
RTRN S8 (C57) Return Temperature
MAXF K1 (C60) Maximum Flow setpoint
MINF K2 (C61) Minimum Flow setpoint
FLAV K3 (C62) Flow temperature setpoint for 10C outside temperature
FRSP K4 (C63) Non Occupied (Frost) setpoint

Configuration Parameters

ref. Neumonic description default range
C1 FRSP Non Occupied setpoint 10 2 to 15C
C2 MAXF maximum Flow setpoint 70 5 to 100C
C3 MINF minimum Flow setpoint 30 1 to 100C
C4 FLAV Flow temperature for 10C outside temperature 50 20 to 100C
C5 SACT sensor action

0 either

1 average

2 maximum

3 minimum

4 external occupancy input

0 0 to 4
C6 SCAL sensor calibration 0.0 0 to 10 C
C7 SPTY setpoint type

0 CT control Flow fixed at Flow Max

1 scheduled between FlowMin and FlowMax with respect to Maximum heating demand from the zones

2 scheduled between Flow Min and Flow Max with respect to average heating demand from the zones

3 weather compensated

1 0 to 3
C8 MIND minimum demand 5 0 to 100%
C9 MNAV minimum value for average demand 0 0 to 100%
C10 MNOC minimum number of occupied zones 0 0 to 200
C11 MNDV driver minimum demand 5 0 to 100%
C12 LOSS CT setpoint to boiler is this amount above own setpoint 10 0 to 20C
C13 TRNG range of Trim applied to weather compensated setpoint by maximum zone demands 10 0 to 20C
C14 CRNG range of weather compensation adaption 10 0 to 20C
C15 SMRT summer inhibit temperature 25 10 to 30C
C16 HPRD stroke time or minimum on time depends on driver type 1 to 240secs/10
C17 HDLY heat interlock delay 0 -60.0 to 60.0 minutes
C18 FPRD minimum time to change fan speed 6 1 to 240secs/10
C19 FRPT frost protect mode

0 none

1 valve only

2 valve and pump

0 0 to 3
C20 MANL manual level 0 0 to 100 %
C21 CMDE control mode

0 driver only, disable control loops

1 control loops active

1 0 to 1
C22 ALRM alarm mode 0 0 to 4
C23 ALST alarm state 0 0 to 1
C24 HTSC heat source 1 0 to 8255
C25 OCDS occupation destination 0 0 to 8255
C26 HTCT demand sent as CT setpoint 1 0 to 1
C27 COMP adaption offset for weather compensated setpoint 0 -50 to 50C