Configuration Parameters -  Secondary Circuit Controller - Heating Type

Types:VTC/DIN/3T/1xx, VTU/DIN/3T/1xx, CTU/DIN/3T/1xx

Software Release: HSCVT4c1

Configuration Parameters

ref. Neumonic description default range
C1 FRSP Frost protection/ Non Occupied setpoint 10 2 to 15C
C2 MAXF maximum Flow setpoint (CT setpoint for CTU) 70 5 to 100C
C3 MINF minimum Flow setpoint 30 1 to 100C
C4 FLAV Flow temperature for 10C outside temperature (used on VTC only) 50 20 to 100C
C5 SACT sensor action

0 either

1 average

2 maximum

3 minimum

0 0 to 3
C6 SCAL sensor calibration 0.0 -10.0 to 10.0 C
C7 SPTY Setpoint Type:
for CTU:        
0: Constant temperature setpoint (value set in MAXF)
for VTU:
1: Setpoint varies linearly based on Maximum Demand Signal from Consumers
2: Setpoint varies linearly based on Average Demand Signal from Consumers
for VTC:
3: Weather Compensated with Zone demand Compensation
1 0 to 3
C8 INMD

Input Mode use of terminals 'temp a'

  • 0 additional temperature input for max,min,average using SACT
  • 1 External occupation (short = occupied) AND internal occ
  • 2 External occupation OR internal occ
  • 3 External occupation signal only
  • 4 Alarm input
  • 5 Pump Alarm
0 0 to 5
C9 MIND Minimum Demand:
When highest demand from all registered zones is less than this value,controller uses non occupied FRST setpoint
0: controller runs to Occupied setpoint for Occupation period
5 0 to 100%
C10 MNAV minimum value for average demand 0 0 to 100%
C11 MNOC minimum number of occupied zones 0 0 to 200
C12 MNDV minimum demand for driver, affects control of Fan or Pump 0 0 to 100%
C13 LOSS Flow Loss:
amount added to the Controller’s setpoint and sent as a CT setpoint to Heat Provider; offsets distrbution heat losses
10 0 to 20C
C14 TRNG Maximum Trim effect on heating setpoint (immediate effect) - VTC Only 10 0 to 20C
C15 CRNG Maximum adaptive effect on heating setpoint (learning effect) - VTC only 10 0 to 20C
C16 SMRT Summer Temp, outside temperature inhibits heating above this setting 25 10 to 30C
C17 HPRD stroke time or minimum on time of valve depends on driver type 1 to 240secs/10
C18 HDLY Interlock delay;
0:     Pump starts as valve opens; no delay
Negative value:  Valve opens before Pump starts
Positive Value: Pump runs on after valve shuts down
0 -60.0 to 60.0 minutes
C19 FPRD not used in this application; set to 12 12 1 to 240secs/10
C20 FRPT frost protect mode

0 none

1 valve only

2 valve and pump

3 pump only

0 0 to 3
C21 MANL manual level 0 -100 to 100 %
C22 CMDE Control Mode, when set to 0 disables control loop, sensors can be used for monitoring. Demands passed direct to outputs. 1 0 to 1
C23 ALRM Alarm mode

0 ignore alarms

1 report alarms

2 report alarms, shut down all outputs on local alarm

3 report alarms, shut down all outputs on STOP alarm or local alarm

4 report alarms, shut down all outputs on STOP alarm only

0 0 to 4
C24 ALST

Alarm State sets the state which is considered to be the Alarm state for the External Alarm input:

0 open circuit

1 short circuit

0 0 to 1
C25 HTSC Heat Source; points Energy Demand to source of Heating energy 1 0 to 8255
C26 OCDS Occupation Destination:
points Occupancy Demand at another controller
0 0 to 8255
C27 HTCT Heating Demand Selector:

Set to1 if HTSC is pointing Energy Demand at a Boiler Controller - demand sent as a CT setpoint

Set to 0 if HTSC is pointing to another Secondary Circuit Controller - demand sent as a % signal

1 0 to 1
C28 COMP adaption offset for weather compensated setpoint 0 -50 to 50C

Monitoring Parameters

Label Doorway code Description
EXTI I1 (C30) External input (function depends on input mode)
OCC I2 (C31) Occupied
SHOF I4 (C33) Summer Heating Inhibit (heating version only)
RLYA I6 (C35) relay A
RLYB I7 (C36) relay B
RLYC I8 (C37) relay C
  SWITCHES  
AUTO W1 (C38) Automatic, control mode
OVRD W2 (C39) Override
ILKP W3 (C40) Interlock Pump (PCO sub module)
ESTF W4 (C41) Establish Flow (PCO sub module)
HAND W5 (C42) Manual HAND override from Doorway
POT W6 (C43) enable use of optional potentiometer (special order hardware)
SERV W7 (C44) remote operation of registration (service) button
CGST W8 (C45) config mode
SENSORS  
HTMP S1 (C50) Heating temperature for control (resultant of processing by SACT)
DMND S2 (C51) Control output
REQD S3 (C52) Current setpoint
ZDMD S4 (C53) Highest demand from the zones
AVDM S5 (C54) Average demand from the zones
NOCC S6 (C55) Number of zones occupied
FLOW S7 (C56) Flow temperature
RTRN S8 (C57) Return Temperature
  KNOBS  
MAXF K1 (C60) Maximum Flow setpoint (used in VTU and CTU)
MINF K2 (C61) Minimum Flow setpoint (used in VTU only)
FLAV K3 (C62) Flow temperature setpoint for 10C outside temperature (used in VTC)
FRSP K4 (C63) Non Occupied (Frost) setpoint

Digital Input Monitoring

ref   Description range
C180 DI A State of Digital input A 0 or 1
C181 DI B State of Digital input B 0 or 1
C182 DI C* State of Digital input C 0 or 1
C183 DI D* State of Digital input D 0 or 1
C184 DI E* State of Digital input E 0 or 1
C185 DI F* State of Digital input F 0 or 1

*xxx-DIN-6R versions only