Secondary Circuit Controller
for Temperature Control of Heating or Cooling Circuits
with 3 x Triac Outputs (3T version)

with 2 x 0-10V DC Outputs (AOP version)

Feature
Notes
Configuration Tables Data Sheet Wiring History

Configuration Tables
(for heating variants only)

Latest released version is 4c2
Document last updated 01/11/2001
Recent features not included on Data sheet are in
RED text

Configuration Parameters

Doorway / InSite Code

Label

Description

Units

Default Value

Range

C1
FRSP
Frost Protection / Non Occupied Setpoint
Deg C
10
2 to 15
C2
MAXF
Maximum Flow Setpoint (VTC and VTU) / CT Setpoint (CTU)
Deg C
82
5 to 100
C3
MINF
Minimum Flow Setpoint
Deg C
30
1 to 100
C4
FLAV
Flow Temperature for 10°C outside temperature (VTC only)
Deg C
50
20 to 100
C5
SACT
Sensor Action
0: Use ‘temp b’ sensor for control and optionally use ‘temp a’ sensor for monitoring or VFC using INMD
1: Use average of valid sensor values (INMD = 0)
2: Use maximum of valid sensor values (INMD = 0)
3: Use minimum of valid sensor values (INMD = 0)
-
0
0 to 3
C6
SCAL
Sensor Calibration
Deg C
0
-10 to +10
C7
SPTY
Setpoint Type (CTU type only)
0: Constant temperature setpoint (value set in MAXF)
-
0
0 to 3
 
 
Setpoint Type (VTU types only)
1: Setpoint varies linearly based on Maximum Demand Signal from Consumers
2: Setpoint varies linearly based on Average Demand Signal from Consumers
-
1
0 to 3
 
 
Setpoint Type (VTC types only)
3: Weather Compensated with Zone demand Compensation
-
3
0 to 3
C8
INMD
Input Mode for input terminals 3 and 4 ‘temp a’
0: Additional temperature input for max, min, ave using SACT
1: External occupation (input linked = Occupied) AND with internal Occupation
2: External occupation (input linked = Occupied) OR with internal Occupation
3: External Occupation signal only
4: Alarm input
5: Pump alarm
-
0
0 to 5
C9
MIND
Minimum Demand
%
5
0 to 100
C10
MNAV
Minimum Average Demand
%
0
0 to 100
C11
MNOC
Minimum number of Occupied Zones
-
0
0 to 200
C12
MNDV
Minimum demand for driver, affects control of Fan or Pump
%
5
0 to 100
C13
LOSS
Flow Loss added to setpoint and sent to Heat Provider
Deg C
10
0 to 20
C14
TRNG
Maximum trim effect on heating setpoint (VTC only)
Deg C
10
0 to 20
C15
CRNG
Maximum adaptive effect on heating setpoint (VTC only)
Deg C
10
0 to 20
C16
SMRT
Summer outside temperature setpoint to inhibit heating
Deg C
20
10 to 30
C17
HPRD
Heating Driver Stroke/Minimum On Time
Secs/10
18
1 to 240
C18
HDLY
Heating Interlock Delay
Negative value opens valve before pump starts
Positive value runs pump on after valve shuts down
Mins
5 -
30 to 30
C19
FPRD
Not used in this application
Secs/10
12
1 to 240
C20
FRPT
Frost Protection Mode
0: No action
1: Open heating valve 50%
2: Open heating valve and run pump
3: Run pump only
-
2
0 to 3
C21
MANL
Manual Level, set by Doorway or InSite
%
0
-100 to 100
C22
CMDE
Control Mode
0: Control loop disabled, demand passed direct to outputs
1: Normal control
-
1
0 to 1
C23
ALRM
Alarm Mode
0: Ignore alarms
1: Report all alarms to Doorway/InSite,
no control action, no flashing Temp indicator
2: Report all alarms, shut down all outputs on local alarm
3: Report all alarms, shut down on STOP alarm or local alarm
4: Report all alarms, shut down on STOP alarm only
-
0
0 to 4
C24
ALST
Alarm report sense
0: Alarm if input = 0, pump running if input = 1
1: Alarm if input = 1, pump running if input = 0
-
1
0 to 1
C25
HTSC
Heat Source
-
1
0 to 8255
C26
OCDS
Occupation Destination
-
0
0 to 8255
C27
HTCT
Heating Demand sent as CT
0: HTSC interconnects to Secondary Circuit, demand sent %
1: HTSC interconnects to Boiler, demand sent as CT temp
-
1
0 to 1
C28
COMP
Adaption offset for weather compensated setpoint
Deg C
0
-50 to 50

 

Monitoring Parameters

Doorway / InSite Code

Label

Description

Units

Default Value

Range

I1 (C30)
EXTI
External Input (function depends on INMD setting)
-
-
0 to 1
I2 (C31)
OCCD
Occupied
-
-
0 to 1
I4 (C33)
SHOF
Summer Heating Inhibit
-
-
0 to 1
I5 (C34)
COOL
Cooling Mode
-
-
0 to 1
I6 (C35)
RLYA
Triac A Status (for 3T types only
-
-
0 to 1
I7 (C36)
RLYB
Triac B Status (for 3T types only
-
-
0 to 1
I8 (C37)
RLYC
Triac C Status (for 3T types only
-
-
0 to 1
W1 (C38)
AUTO
Automatic/Manual Status
-
-
0 to 1
W2 (C39)
OVRD
Override
-
-
0 to 1
W3 (C40)
ILKP
Interlock Pump (PCO submodule)
-
-
0 to 1
W4 (C41)
ESTF
Establish Flow (PCO submodule)
-
-
0 to 1
W5 (C42)
HAND
Manual Hand; use with MANL to set output level
-
0
0 to 1
W6 (C43)
POT
Not used in this application
-
0
0 to 1
W7 (C44)
SERV
Service Pin Message (to Doorway and InSite, self resetting)
-
-
0 to 1
W8 (C45)
CGST
Configuration Mode Status
-
-
0 to 1
S1* (C50)
HTMP
Heated Water Temperature
Deg C
-
-
S2* (C51)
DMND
Control Demand
%
-
-100 to 100
S3 (C52)
REQD
Controller current setpoint
Deg C
-
-
S4 (C53)
ZDMD
Highest demand from zones
%
-
-
S5 (C54)
AVDM
Average demand from zones
%
-
-
S6 (C55)
NOCC
Number of zones Occupied
-
-
-
S7 (C56)
FLOW
Flow Temperature
Deg C
-
-
S8 (C57)
RTRN
Return Temperature
Deg C
-
-
K1 (C60)
MAXF
Maximum Flow Setpoint (for VTU, VTC and CTU)
Deg C
82
10 to 100
K2 (C61)
MINF
Minimum Flow Setpoint (for VTU and VTC only)
Deg C
30
5 to 100
K3 (C62)
FLAV
Flow Temperature Setpoint for 10C outside (for VTC only)
Deg C
50
10 to 100
K4 (C63)
FRSP
Non Occupied (Frost) Setpoint
Deg C
10
5 to30
K5 (C64)
MXVA
Maximum Voltage output a (for AOP types only)
Vdc
10
0 to 10
K6 (C65)
MNVA
Minimum Voltage output a (for AOP types only)
Vdc
0
0 to 10
K7 (C66)
MXVB
Maximum Voltage output b (for AOP types only)
Vdc
10
0 to 10
K8 (C67)
MNVB
Minimum Voltage output b (for AOP types only)
Vdc
0
0 to 10
 
 
Engineering Parameters; only accessible via Doorway and InSite
 
 
 
C90
NOAL
No Alarms; all alarms cleared when set to 1
-
-
0 or 1
C91
SENF
Sensor Failed (when set to 1)
-
-
0 or 1
C92
EXTN
Volt-Free Contact alarm (when set to 1)
-
-
0 or 1
C93
CNDF
Condensation detected (for cooling types only)
-
-
0 or 1
C94
PMPF
Pump Failed (when set to 1)
-
-
0 or 1
C95
STOP
STOP alarm received (when set to 1)
-
-
0 or 1
C180
DI A
Input 3-4 digital status
-
-
0 or 1
C181
DI B
Input 5-6 digital status
-
-
0 or 1
 
 
* 24 hour plots available for these values by default
 
 
 
 
 
Plotting interval and plotted variable changeable via Doorway or InSite
 
 
 