Configuration Tables

Secondary Circuit Controller

Features new this issue are in RED text
Latest released version is 4e1

for Temperature Control of Heating Circuits
with 3 x Triac Outputs (3T version)

with 2 x 0-10V DC Outputs (AOP version)

 

Configuration Parameters

Doorway / InSite Code

Label

Description

Units

Default Value

Range

C1
FRSP
Frost Protection / Non Occupied Setpoint
Deg C
10
2 to 15
C2
MAXF
Maximum Flow Setpoint (VTC and VTU) / CT Setpoint (CTU)
Deg C
82
5 to 100
C3
MINF
Minimum Flow Setpoint
Deg C
30
1 to 100
C4
FLAV
Flow Temperature for 10°C outside temperature (VTC only)
Deg C
50
20 to 100
C5
SACT
Sensor Action
0: Use ‘temp b’ sensor for control and optionally use ‘temp a’ sensor for monitoring or VFC using INMD
1: Use average of valid sensor values (INMD = 0)
2: Use maximum of valid sensor values (INMD = 0)
3: Use minimum of valid sensor values (INMD = 0)
-
0
0 to 3
C6
SCAL
Sensor Calibration
Deg C
0
-10 to +10
C7
SPTY
Setpoint Type (CTU type only)
0: Constant temperature setpoint (value set in MAXF)
-
0
0 to 3
 
 
Setpoint Type (VTU types only)
1: Setpoint varies linearly based on Maximum Demand Signal from Consumers
2: Setpoint varies linearly based on Average Demand Signal from Consumers
-
1
0 to 3
 
 
Setpoint Type (VTC types only)
3: Weather Compensated with Zone demand Compensation
-
3
0 to 3
C8
INMD
Input Mode for input terminals 3 and 4 ‘temp a’
0: Additional temperature input for max, min, ave using SACT
1: External occupation (input linked = Occupied) AND with internal Occupation
2: External occupation (input linked = Occupied) OR with internal Occupation
3: External Occupation signal only
4: Alarm input
5: Pump alarm
-
0
0 to 5
C9
MIND
Minimum Demand
%
5
0 to 100
C10
MNAV
Minimum Average Demand
%
0
0 to 100
C11
MNOC
Minimum number of Occupied Zones
-
0
0 to 200
C12
MNDV
Minimum demand for driver, affects control of Fan or Pump
%
5
0 to 100
C13
LOSS
Flow Loss added to setpoint and sent to Heat Provider
Deg C
10
0 to 20
C14
TRNG
Maximum trim effect on heating setpoint (VTC only)
Deg C
10
0 to 20
C15
CRNG
Maximum adaptive effect on heating setpoint (VTC only)
Deg C
10
0 to 20
C16
SMRT
Summer outside temperature setpoint to inhibit heating
Deg C
20
10 to 30
C17
HPRD
Heating Driver Stroke/Minimum On Time
Secs/10
18
1 to 240
C18
HDLY
Heating Interlock Delay
Negative value opens valve before pump starts
Positive value runs pump on after valve shuts down
Mins
5 -
30 to 30
C19
FPRD
Not used in this application
Secs/10
12
1 to 240
C20
FRPT
Frost Protection Mode
0: No action
1: Open heating valve 50%
2: Open heating valve and run pump
3: Run pump only
-
2
0 to 3
C21
MANL
Manual Level, set by Doorway or InSite
%
0
-100 to 100
C22
CMDE
Control Mode
0: Control loop disabled, demand passed direct to outputs
1: Normal control
-
1
0 to 1
C23
ALRM
Alarm Mode
0: Ignore alarms
1: Report all alarms to Doorway/InSite,
no control action, no flashing Temp indicator
2: Report all alarms, shut down all outputs on local alarm
3: Report all alarms, shut down on STOP alarm or local alarm
4: Report all alarms, shut down on STOP alarm only
-
0
0 to 4
C24
ALST
Alarm report sense
0: Alarm if input = 0, pump running if input = 1
1: Alarm if input = 1, pump running if input = 0
-
1
0 to 1
C25
HTSC
Heat Source
-
1
0 to 9255
C26
OCDS
Occupation Destination
-
0
0 to 9255
C27
HTCT
Heating Demand sent as CT
0: HTSC interconnects to Secondary Circuit, demand sent %
1: HTSC interconnects to Boiler, demand sent as CT temp
-
1
0 to 1
C28
COMP
Adaption offset for weather compensated setpoint
Deg C
0
-50 to 50
C29
XHSC
Allows demand to be sent to an addtional heat source used primarily in Natural ventilation applications, leave at 0 to disable.
heat source number 1-25 send control demand
heat source +100 send Max Zone Demand
heat source +200 send Average incoming Demand
-
0
0 to 225

Monitoring Parameters

Doorway / InSite Code

Label

Description

Units

Default Value

Range

I1 (C30)
EXTI
External Input (function depends on INMD setting)
-
-
0 to 1
I2 (C31)
OCCD
Occupied
-
-
0 to 1
I3 (C32)
CLOR
Cooling Override, when ON this controller has been overriden OFF by the interlocked Cooling controller. See knob ICSC
-
-
0 to 1
I4 (C33)
SHOF
Summer Heating Inhibit
-
-
0 to 1
I5 (C34)
COOL
Cooling Mode
-
-
0 to 1
I6 (C35)
RLYA
Triac A Status (for 3T types only
-
-
0 to 1
I7 (C36)
RLYB
Triac B Status (for 3T types only
-
-
0 to 1
I8 (C37)
RLYC
Triac C Status (for 3T types only
-
-
0 to 1
W1 (C38)
AUTO
Automatic/Manual Status
-
-
0 to 1
W2 (C39)
OVRD
Override
-
-
0 to 1
W3 (C40)
ILKP
Interlock Pump (PCO submodule)
-
-
0 to 1
W4 (C41)
ESTF
Establish Flow (PCO submodule)
-
-
0 to 1
W5 (C42)
HAND
Manual Hand; use with MANL to set output level
-
0
0 to 1
W6 (C43)
POT
Not used in this application
-
0
0 to 1
W7 (C44)
SERV
Service Pin Message (to Doorway and InSite, self resetting)
-
-
0 to 1
W8 (C45)
CGST
Configuration Mode Status
-
-
0 to 1
S1* (C50)
HTMP
Heated Water Temperature
Deg C
-
-
S2* (C51)
DMND
Control Demand
%
-
-100 to 100
S3 (C52)
REQD
Controller current setpoint
Deg C
-
-
S4 (C53)
ZDMD
Highest demand from zones
%
-
-
S5 (C54)
AVDM
Average demand from zones
%
-
-
S6 (C55)
NOCC
Number of zones Occupied
-
-
-
S7 (C56)
FLOW
Flow Temperature
Deg C
-
-
S8 (C57)
RTRN
Return Temperature
Deg C
-
-
K1 (C60)
MAXF
Maximum Flow Setpoint (for VTU, VTC and CTU)
Deg C
82
10 to 100
K2 (C61)
MINF
Minimum Flow Setpoint (for VTU and VTC only)
Deg C
30
5 to 100
K3 (C62)
FLAV
Flow Temperature Setpoint for 10C outside (for VTC only)
Deg C
50
10 to 100
K4 (C63)
FRSP
Non Occupied (Frost) Setpoint
Deg C
10
5 to30
K5 (C64)
ICSC
Interlocked Cool Source, when set this points to the interlocked cooling secondary controller and only the heating or the cooling controller can be active, the controller with the highest demand wins. Used to control the common meduim of Two Pipe systems
-
-
0 to 8255
 
 
Engineering Parameters; only accessible via Doorway and InSite
 
 
 
C90
NOAL
No Alarms; all alarms cleared when set to 1
-
-
0 or 1
C91
SENF
Sensor Failed (when set to 1)
-
-
0 or 1
C92
EXTN
Volt-Free Contact alarm (when set to 1)
-
-
0 or 1
C93
CNDF
Condensation detected (for cooling types only)
-
-
0 or 1
C94
PMPF
Pump Failed (when set to 1)
-
-
0 or 1
C95
STOP
STOP alarm received (when set to 1)
-
-
0 or 1
C180
DI A
Input 3-4 digital status
-
-
0 or 1
C181
DI B
Input 5-6 digital status
-
-
0 or 1
 
 
* 24 hour plots available for these values by default
 
 
 
 
 
Plotting interval and plotted variable changeable via Doorway or InSite
 
 
 