Configuration Tables
|
Secondary Circuit Controller |
Features new this issue are in RED textLatest released version is 4e1 |
for Temperature Control of Heating Circuits
|
Configuration Parameters |
|||||
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
C1 |
FRSP |
Frost Protection / Non Occupied Setpoint
|
Deg C |
10 |
2 to 15 |
C2 |
MAXF |
Maximum Flow Setpoint (VTC and VTU) / CT Setpoint (CTU)
|
Deg C |
82 |
5 to 100 |
C3 |
MINF |
Minimum Flow Setpoint
|
Deg C |
30 |
1 to 100 |
C4 |
FLAV |
Flow Temperature for 10°C outside temperature (VTC only)
|
Deg C |
50 |
20 to 100 |
C5 |
SACT |
Sensor Action
|
- |
0 |
0 to 3 |
C6 |
SCAL |
Sensor Calibration
|
Deg C |
0 |
-10 to +10 |
C7 |
SPTY |
Setpoint Type (CTU type only)
|
- |
0 |
0 to 3 |
|
|
Setpoint Type (VTU types only)
|
- |
1 |
0 to 3 |
|
|
Setpoint Type (VTC types only)
|
- |
3 |
0 to 3 |
C8 |
INMD |
Input Mode for input terminals 3 and 4 temp a
|
- |
0 |
0 to 5 |
C9 |
MIND |
Minimum Demand
|
% |
5 |
0 to 100 |
C10 |
MNAV |
Minimum Average Demand
|
% |
0 |
0 to 100 |
C11 |
MNOC |
Minimum number of Occupied Zones
|
- |
0 |
0 to 200 |
C12 |
MNDV |
Minimum demand for driver, affects control of Fan or Pump |
% |
5 |
0 to 100 |
C13 |
LOSS |
Flow Loss added to setpoint and sent to Heat Provider |
Deg C |
10 |
0 to 20 |
C14 |
TRNG |
Maximum trim effect on heating setpoint (VTC only) |
Deg C |
10 |
0 to 20 |
C15 |
CRNG |
Maximum adaptive effect on heating setpoint (VTC only) |
Deg C |
10 |
0 to 20 |
C16 |
SMRT |
Summer outside temperature setpoint to inhibit heating |
Deg C |
20 |
10 to 30 |
C17 |
HPRD |
Heating Driver Stroke/Minimum On Time |
Secs/10 |
18 |
1 to 240 |
C18 |
HDLY |
Heating Interlock Delay
|
Mins |
5 - |
30 to 30 |
C19 |
FPRD |
Not used in this application |
Secs/10 |
12 |
1 to 240 |
C20 |
FRPT |
Frost Protection Mode
|
- |
2 |
0 to 3 |
C21 |
MANL |
Manual Level, set by Doorway or InSite |
% |
0 |
-100 to 100 |
C22 |
CMDE |
Control Mode
|
- |
1 |
0 to 1 |
C23 |
ALRM |
Alarm Mode
|
- |
0 |
0 to 4 |
C24 |
ALST |
Alarm report sense
|
- |
1 |
0 to 1 |
C25 |
HTSC |
Heat Source
|
- |
1 |
0 to 9255 |
C26 |
OCDS |
Occupation Destination |
-
|
0 |
0 to 9255 |
C27 |
HTCT |
Heating Demand sent as CT
|
- |
1 |
0 to 1 |
C28 |
COMP |
Adaption offset for weather compensated setpoint |
Deg C |
0 |
-50 to 50 |
C29 |
XHSC |
Allows demand to be sent to an addtional heat source used primarily
in Natural ventilation applications, leave at 0 to disable.
|
- |
0 |
0 to 225 |
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
I1 (C30) |
EXTI |
External Input (function depends on INMD setting) |
- |
- |
0 to 1 |
I2 (C31) |
OCCD |
Occupied |
- |
- |
0 to 1 |
I3 (C32) |
CLOR |
Cooling Override, when ON this controller has been overriden OFF by the interlocked Cooling controller. See knob ICSC |
- |
- |
0 to 1 |
I4 (C33) |
SHOF |
Summer Heating Inhibit |
- |
- |
0 to 1 |
I5 (C34) |
COOL |
Cooling Mode |
- |
- |
0 to 1 |
I6 (C35) |
RLYA |
Triac A Status (for 3T types only |
- |
- |
0 to 1 |
I7 (C36) |
RLYB |
Triac B Status (for 3T types only |
- |
- |
0 to 1 |
I8 (C37) |
RLYC |
Triac C Status (for 3T types only |
- |
- |
0 to 1 |
W1 (C38) |
AUTO |
Automatic/Manual Status |
- |
- |
0 to 1 |
W2 (C39) |
OVRD |
Override |
- |
- |
0 to 1 |
W3 (C40) |
ILKP |
Interlock Pump (PCO submodule) |
- |
- |
0 to 1 |
W4 (C41) |
ESTF |
Establish Flow (PCO submodule) |
- |
- |
0 to 1 |
W5 (C42) |
HAND |
Manual Hand; use with MANL to set output level |
- |
0 |
0 to 1 |
W6 (C43) |
POT |
Not used in this application |
- |
0 |
0 to 1 |
W7 (C44) |
SERV |
Service Pin Message (to Doorway and InSite, self resetting) |
- |
- |
0 to 1 |
W8 (C45) |
CGST |
Configuration Mode Status |
- |
- |
0 to 1 |
S1* (C50) |
HTMP |
Heated Water Temperature |
Deg C |
- |
- |
S2* (C51) |
DMND |
Control Demand |
% |
- |
-100 to 100 |
S3 (C52) |
REQD |
Controller current setpoint |
Deg C |
- |
- |
S4 (C53) |
ZDMD |
Highest demand from zones |
% |
- |
- |
S5 (C54) |
AVDM |
Average demand from zones |
% |
- |
- |
S6 (C55) |
NOCC |
Number of zones Occupied |
- |
- |
- |
S7 (C56) |
FLOW |
Flow Temperature |
Deg C |
- |
- |
S8 (C57) |
RTRN |
Return Temperature |
Deg C |
- |
- |
K1 (C60) |
MAXF |
Maximum Flow Setpoint (for VTU, VTC and CTU) |
Deg C |
82 |
10 to 100 |
K2 (C61) |
MINF |
Minimum Flow Setpoint (for VTU and VTC only)
|
Deg C |
30 |
5 to 100 |
K3 (C62) |
FLAV |
Flow Temperature Setpoint for 10C outside (for VTC only)
|
Deg C |
50 |
10 to 100 |
K4 (C63) |
FRSP |
Non Occupied (Frost) Setpoint
|
Deg C |
10 |
5 to30 |
K5 (C64) |
ICSC |
Interlocked Cool Source, when set this points to the interlocked cooling
secondary controller and only the heating or the cooling controller can
be active, the controller with the highest demand wins. Used to control
the common meduim of Two Pipe systems
|
- |
- |
0 to 8255 |
|
|
Engineering Parameters; only accessible via Doorway and InSite |
|
|
|
C90 |
NOAL |
No Alarms; all alarms cleared when set to 1 |
- |
- |
0 or 1 |
C91 |
SENF |
Sensor Failed (when set to 1) |
- |
- |
0 or 1 |
C92 |
EXTN |
Volt-Free Contact alarm (when set to 1) |
- |
- |
0 or 1 |
C93 |
CNDF |
Condensation detected (for cooling types only) |
- |
- |
0 or 1 |
C94 |
PMPF |
Pump Failed (when set to 1) |
- |
- |
0 or 1 |
C95 |
STOP |
STOP alarm received (when set to 1) |
- |
- |
0 or 1 |
C180 |
DI A |
Input 3-4 digital status |
- |
- |
0 or 1 |
C181 |
DI B |
Input 5-6 digital status |
- |
- |
0 or 1 |
|
|
* 24 hour plots available for these values by default |
|
|
|
|
|
Plotting interval and plotted variable changeable via Doorway or InSite |
|
|
|