Secondary Circuit Controller
for Temperature Control of Heating or Cooling Circuits
with 3 x Triac Outputs (3T version)

with 2 x 0-10V DC Outputs (AOP version)
Chiller Controller
with 3 x Triac Outputs
Multi Channel Controller
with 3 x Triac Outputs

History
(Sec.Circ./Chiller)
History
(Multi Channel)

Engineering Tables

Latest updated version is 4c1
Document last updated 17/12/2001

Engineering Parameters

Doorway / InSite Code Label Description Units Default Value Range
    Control parameters      
C70 UNDH Under temperature heating - - 1 to 2
C71 OVRH Over temperature heating - - 1 to 2
C72 DBDH Deadband heating - - 1 to 2
C73 PGNH Heating gain - - 0 to 250
C74 GN H Heating gain - - 0 to 250
C75 UNDC Under temperature cooling - - 1 to 2
C76 OVRC Over temperature cooling - - 1 to 2
C77 DBDC Deadband cooling - - 1 to 2
C78 PGNC Cooling gain - - 0 to 250
C79 GN C Cooling gain - - 0 to 250
    System Parameters      
C80 XCFG Exit config mode system message - - 0 to 1
C81 GRP Own group - - Read only
C83 MANL Manual level - 0 -100 to 100
C84 NCRS No comms resets - 0 0 to 255
C85 SWRS Software resets - 0 0 to 255
C86 CSTP Control step - 0 0 to 99
    Alarm Parameters      
C90 NOAL No alarms - - 0 to 1
C91 SENF Sensor fail alarm - - 0 to 1
C92 EXTN External alarm input - - 0 to 1
C93 CNDF Condensation alarm - - 0 to 1
C94 PMPF Pump fail alarm - - 0 to 1
C95 STOP Stop alarm received - - 0 to 1
C96 RPVF Remote PV fail alarm - - 0 to 1
    Sources      
C100 #ACT Number of registered actuators - 0 Read only
C101 HTSC Remote update of heat source - 1 0 to 8225
C102 CLSC Remote update of cool source - 0 0 to 8225
C103 OCDS Remote update of Occupation destination - 0 0 to 8225
C104 #SEN Number of registered sensors - 0 Read only
    Plots      
C130 PN A Config variable number for plot A   50 1 to 255
C131 PT A

Plot type A:
1: every 15 minutes
2: once per day
3: every minute
4: every hour

- 1 1 to 4
C132 PN B Config variable number for plot B - 51 1 to 255
C133 PT B Plot type B - 1 1 to 4
    Driver Parameters      
C150 HTYP Heat type - 0 0 to 9
C151 HSTG Heat stages - 0 0 to 8
C152 CTYP Cool type - 0 0 to 9
C153 CSTG Cool stages - 0 0 to 8
C154 FTYP Fan/pump type - 0 0 to 9
C155 FSTG Fan/pump stages - 0 0 to 155
C156 HPRD Heat period - 0 1 to 240
C157 HDLY Heat delay - 0 -600 to 600
C158 CPRD Cool period - 0 1 to 240
C159 CDLY Cool delay - 0 -600 to 600
C160 HDRV Heat demand to driver and sub modules % - 0 to 100
C161 CDRV Cool demand to driver and sub modules % - 0 to 100
C162 MXVA Maximum voltage channel A Vdc 10.0 0.0 to 10.0
C163 MNVA MInimum Voltage channel A Vdc 0 0.0 to 10.0
C164 MXVB Maximum voltage channel B Vdc 10.0 0.0 to 10.0
C165 MNVB MInimum Voltage channel B Vdc 0 0.0 to 10.0
    Test Values      
C170 ACH1 Analogue Channel 1 - - -
C171 ACH2 Analogue Channel 2 - - -
C172 ACH3 Analogue Channel 3 - - -

 

 