Secondary Circuit Controller
for Temperature Control
of Heating or Cooling Circuits
with 3 x Triac Outputs (3T version)
with 2 x 0-10V DC Outputs (AOP version)
Chiller
Controller
with 3 x Triac Outputs
Multi Channel Controller
with 3 x Triac Outputs
History (Sec.Circ./Chiller) |
History (Multi Channel) |
Engineering Tables
Latest updated version is 4c1
Document last updated 17/12/2001
Engineering Parameters
Doorway / InSite Code | Label | Description | Units | Default Value | Range |
Control parameters | |||||
C70 | UNDH | Under temperature heating | - | - | 1 to 2 |
C71 | OVRH | Over temperature heating | - | - | 1 to 2 |
C72 | DBDH | Deadband heating | - | - | 1 to 2 |
C73 | PGNH | Heating gain | - | - | 0 to 250 |
C74 | GN H | Heating gain | - | - | 0 to 250 |
C75 | UNDC | Under temperature cooling | - | - | 1 to 2 |
C76 | OVRC | Over temperature cooling | - | - | 1 to 2 |
C77 | DBDC | Deadband cooling | - | - | 1 to 2 |
C78 | PGNC | Cooling gain | - | - | 0 to 250 |
C79 | GN C | Cooling gain | - | - | 0 to 250 |
System Parameters | |||||
C80 | XCFG | Exit config mode system message | - | - | 0 to 1 |
C81 | GRP | Own group | - | - | Read only |
C83 | MANL | Manual level | - | 0 | -100 to 100 |
C84 | NCRS | No comms resets | - | 0 | 0 to 255 |
C85 | SWRS | Software resets | - | 0 | 0 to 255 |
C86 | CSTP | Control step | - | 0 | 0 to 99 |
Alarm Parameters | |||||
C90 | NOAL | No alarms | - | - | 0 to 1 |
C91 | SENF | Sensor fail alarm | - | - | 0 to 1 |
C92 | EXTN | External alarm input | - | - | 0 to 1 |
C93 | CNDF | Condensation alarm | - | - | 0 to 1 |
C94 | PMPF | Pump fail alarm | - | - | 0 to 1 |
C95 | STOP | Stop alarm received | - | - | 0 to 1 |
C96 | RPVF | Remote PV fail alarm | - | - | 0 to 1 |
Sources | |||||
C100 | #ACT | Number of registered actuators | - | 0 | Read only |
C101 | HTSC | Remote update of heat source | - | 1 | 0 to 8225 |
C102 | CLSC | Remote update of cool source | - | 0 | 0 to 8225 |
C103 | OCDS | Remote update of Occupation destination | - | 0 | 0 to 8225 |
C104 | #SEN | Number of registered sensors | - | 0 | Read only |
Plots | |||||
C130 | PN A | Config variable number for plot A | 50 | 1 to 255 | |
C131 | PT A |
Plot type A: |
- | 1 | 1 to 4 |
C132 | PN B | Config variable number for plot B | - | 51 | 1 to 255 |
C133 | PT B | Plot type B | - | 1 | 1 to 4 |
Driver Parameters | |||||
C150 | HTYP | Heat type | - | 0 | 0 to 9 |
C151 | HSTG | Heat stages | - | 0 | 0 to 8 |
C152 | CTYP | Cool type | - | 0 | 0 to 9 |
C153 | CSTG | Cool stages | - | 0 | 0 to 8 |
C154 | FTYP | Fan/pump type | - | 0 | 0 to 9 |
C155 | FSTG | Fan/pump stages | - | 0 | 0 to 155 |
C156 | HPRD | Heat period | - | 0 | 1 to 240 |
C157 | HDLY | Heat delay | - | 0 | -600 to 600 |
C158 | CPRD | Cool period | - | 0 | 1 to 240 |
C159 | CDLY | Cool delay | - | 0 | -600 to 600 |
C160 | HDRV | Heat demand to driver and sub modules | % | - | 0 to 100 |
C161 | CDRV | Cool demand to driver and sub modules | % | - | 0 to 100 |
C162 | MXVA | Maximum voltage channel A | Vdc | 10.0 | 0.0 to 10.0 |
C163 | MNVA | MInimum Voltage channel A | Vdc | 0 | 0.0 to 10.0 |
C164 | MXVB | Maximum voltage channel B | Vdc | 10.0 | 0.0 to 10.0 |
C165 | MNVB | MInimum Voltage channel B | Vdc | 0 | 0.0 to 10.0 |
Test Values | |||||
C170 | ACH1 | Analogue Channel 1 | - | - | - |
C171 | ACH2 | Analogue Channel 2 | - | - | - |
C172 | ACH3 | Analogue Channel 3 | - | - | - |