Actuator Controller Network Variables ACTx4c1

Name
SNVT type
in/
out
normal connection
nciNetConfig SNVT_config_src in when set TRUE disables inbuilt binding
nciLocation SNVT_str_asc in node label string.. application updates it when address changed
nviConfigPara single byte parameter number in used to read config parameter, node replies with data in SeaChange data structure
nviConfigData SeaChange data structure in writes new config parameter data
nviHeatTrim SNVT_lev_cont in heat demand from Zone Controller
nviCoolTrim SNVT_lev_cont in cool demand from Zone Controller
nviFanSpeed SNVT_lev_cont in fan speed demand from Zone Controller
nviClock SNVT_date_time in connected to nvoClock on Boiler controller
nviDayofWeek SNVT_date_day in connected to nvoDayofWeek on Boiler controller
nviBlrOutTemp SNVT_temp in connected to nvoOutsideTemp on Boiler Controller
nviBoilerTemp SNVT_temp in connected to nvoBoilerTemp on Boiler Controller
nviInstallZone SNVT_lev_cont in used to display installed zone number
nviOutsideTemp SNVT_temp_p in Outside temperature connected to optional networked sensor
nviOutsideRH SNVT_lev_cont in Outside RH connected to optional networked sensor
nvoMeasuredTemp SNVT_temp_p * out current measured temperature
nvoEffectSetPt SNVT_temp_p out current setpoint
nvoHeatOutput SNVT_lev_percent * out Heating Demand
nvoCoolOutput SNVT_lev_percent * out Cooling Demand
nviHeatDemand SNVT_lev_percent in Heating Demand
nviCoolDemand SNVT_lev_percent in Cooling Demand
nviOccSetpoint SNVT_temp_p in Occupied setpoint, changes EEPROM value so update rate needs to be carefully considered
nvoOccSetpoint SNVT_temp_p out current Occupied setpoint
nvoCurrentOp SNVT_lev_percent out current output level or valve position
nviPlotRequest SeaChange plot request in proprietory data structure
nciSndHrtBt SNVT_time_sec in heartbeat setting for update time of SNVT values marked with a *