Configuration Parameters -  Submodule - Window Controller

Types:WNW/DIN/3R/xxx, WNW/DIN/3T/xxx, WNW/DIN/AOP/xxx

Software Release: ACTAW4c2,

Configuration Parameters

ref   Description default range
C1 MNFA Minimum Fresh Air 10 0 to 100%
C2 NOWS

Minimum Wind Speed for Wind Direction Indication to be valid

1.0 0.0 to 25.0 m/sec
C3 MXWS Maximum Wind Speed (Window Shut) 0 0 to 25.0 m/sec
C4 MNWS Minimum Wind Speed (Window open) 0 0 to 15.0 m/sec
C5 WNWD Window Direction 0 0 to 360 degrees
C6 WNWS Window Span, the deviation in Wind Direction from dead down wind when the Window will be forced shut. 0 0 to 360 degrees
C7 INMD

Input Mode use of terminals 'input a'

  • 0 additional temperature input for max,min,average use SACT
  • 1 external input (short = occupied) AND internal occ
  • 2 external input OR internal occ
  • 3 external input signal only
  • 4 Alarm input
  • 5 Alarm if input does not match Pump/Fan State
Note modes 2 & 3 are only suitable for use with Actuator in Control Mode 2, small plant driver mode.
0 0 to 5
C8 MIND

minimum demand, used for defining Occupancy switching for the Fan/Pump.

0 will run pump/fan throughout Occupancy

>0 will require minimum demand level before pump/fan will run

4 0.0 to 10.0
C9 OCCO When set controller will only run during the occupied period 0 0 to 1
C10 HPRD heating valve period or minimum on time depends on driver type 1 to 60 secs/10
C11 HDLY Interlock delay

negative value delays fan (or pump) after heating starts

positive value cause run on of fan after heating shuts down

0 -30.0 to 30.0 minutes
C12 CPRD cooling valve period or minimum on time depends on driver type 1 to 60 secs/10
C13 CDLY Interlock delay

negative value delays fan (or pump) after cooling starts

positive value cause run on of fan after cooling shuts down

0 -30.0 to 30.0 minutes
C14 FPRD Fan period, minimum time to change fan speed steps (6R + 7R version only) 12 (2 minutes) 1 to 60 secs/10
C15 CALC Calculation Mode

0 Multiply the Factors

1 use Loweset Factor

0 0 to 1
C16 MANL Manual level , from Doorway 0 -100 to 100 %
C17 CMDE

Control Mode

0 driver only inputs used for monitoring or alarm

1 closed loop control, input b primary sensor

2 on/off control, heating or cooling demand will be 100% when controller is 'occupied'. Sensor inputs used for monitoring or alarm functions

0 -100 to 100 %
C18 ALRM alarm mode

0 ignore alarms

1 report alarms

2 report alarms, shut down all outputs on local alarm

3 report alarms, shut down all outputs on STOP alarm or local alarm

4 report alarms, shut down all outputs on STOP alarm only

0 0 to 4
C19 ALST sets alarm state 0 0 to 1
C20 MXVA* Maximum voltage channel A 10.0 0.0 to 10.0 volt
C21 MNVA* Minimum voltage channel A 0.0 0.0 to 10.0 volt
C22 MXVB* Maximum voltage channel B 10.0 0.0 to 10.0 volt
C23 MNVB* Minimum voltage channel B 0.0 0.0 to 10.0 volt

* AOP versions only

Monitoring Parameters

Input Monitoring (3R, 2T1R, 3T and AOP variants)

ref   Description default range
I1 (C30) FRST not used in this version   0 to 1
I2 (C31) OCCD occupied   0 to 1
I3 (C32) WMUP not used in this version   0 to 1
I4 (C33)  EXIP external input   0 to 1
I5 (C34) COOL cooling mode   0 to 1
I6 (C35) RLYA relay A status   0 to 1
I7 (C36) RLYB relay B status   0 to 1
I8 (C37) RLYC relay C status   0 to 1
W1 (C38) AUTO Automatic/manual mode   0 to 1
W2 (C39) OVRD override   0 to 1
W5 (C42) HAND Manual HAND override from Doorway   0 to 1
W6 (C43) POT selects whether the board mounted potentiometer option is fitted or not   0 to 1
W7 (C44) SERV send service pin (registration) message   0 to 1

 

 

Sensors

ref   Description default range
S1 (C50) TEMP measured temperature   5 to 90 C
S2 (C51) HCOP heat cool output to drivers (cooling negative)   -100 to 100 %
S3 (C52) REQD current setpoint   5 to 90 C
S4 (C53) HDMD heat demand from loop or from Zone Controller   0 to 100%
S5 (C54) CDMD cool demand from loop or from Zone Controller   0 to 100%
S6 (C55) FDMD fan demand   0 to 100%
S7 (C56) OSFR Outside Temperature Override Factor   0 to 100%
S8 (C57) WSFR Wind Speed Override Factor   0 to 100%
S9 (C58) WDFR Wind Direction Override Factor 0 to 100%
S10 (C59) FACT Overall Override Factor 0 to 100%

Knobs

ref   Description default range
K1 (C60) MXWS Maximum Wind Speed, speed at which Window is Overriden shut 0 0 to 25.0 m/sec
K2 (C61) MNWS Minimum Wind Speed, speed at which window is still allowed to be 100% open 0 0 to 25.0 m/sec
K3 (C62)   Reserved for supervised setpoint from master controller    
K4 (C63) WNWD Window Direction, compass bearing looking directly out of the window 0 0 to 360 degrees
K5 (C64) DDEV Wind Direction deviation, deviation from dead down wind where window must be shut 0 0 to 160 degrees
K6 (C65) NOWS No Wind, below this Wind Speed the Wind Direction is ignored 1.0 0.0 to 25.0 m/sec
K7 (C66) MNFA Minimum Fresh Air setting for the Window opening 10 0 to 100%
K8 (C67) OUTT Outside Temperature Top limit, at which the window can be fully open 0 0.0 to 25.0 degC
K9 (C68) OUTB Outside Temperature Bottom limit, at or below which the window will be shut 0 0.0 to 25.0 degC

Digital Input Monitoring

ref   Description range
C180 DI A State of Digital input A 0 or 1
C181 DI B State of Digital input B 0 or 1