| Configuration Parameters - Submodule - Window Controller |
Configuration Parameters
| ref | Description | default | range | |
| C1 | MNFA | Minimum Fresh Air | 10 | 0 to 100% |
| C2 | NOWS |
Minimum Wind Speed for Wind Direction Indication to be valid |
1.0 | 0.0 to 25.0 m/sec |
| C3 | MXWS | Maximum Wind Speed (Window Shut) | 0 | 0 to 25.0 m/sec |
| C4 | MNWS | Minimum Wind Speed (Window open) | 0 | 0 to 15.0 m/sec |
| C5 | WNWD | Window Direction | 0 | 0 to 360 degrees |
| C6 | WNWS | Window Span, the deviation in Wind Direction from dead down wind when the Window will be forced shut. | 0 | 0 to 360 degrees |
| C7 | INMD |
Input Mode use of terminals 'input a'
|
0 | 0 to 5 |
| C8 | MIND |
minimum demand, used for defining Occupancy switching for the Fan/Pump. 0 will run pump/fan throughout Occupancy >0 will require minimum demand level before pump/fan will run |
4 | 0.0 to 10.0 |
| C9 | OCCO | When set controller will only run during the occupied period | 0 | 0 to 1 |
| C10 | HPRD | heating valve period or minimum on time | depends on driver type | 1 to 60 secs/10 |
| C11 | HDLY | Interlock delay
negative value delays fan (or pump) after heating starts positive value cause run on of fan after heating shuts down |
0 | -30.0 to 30.0 minutes |
| C12 | CPRD | cooling valve period or minimum on time | depends on driver type | 1 to 60 secs/10 |
| C13 | CDLY | Interlock delay
negative value delays fan (or pump) after cooling starts positive value cause run on of fan after cooling shuts down |
0 | -30.0 to 30.0 minutes |
| C14 | FPRD | Fan period, minimum time to change fan speed steps (6R + 7R version only) | 12 (2 minutes) | 1 to 60 secs/10 |
| C15 | CALC | Calculation Mode
0 Multiply the Factors 1 use Loweset Factor |
0 | 0 to 1 |
| C16 | MANL | Manual level , from Doorway | 0 | -100 to 100 % |
| C17 | CMDE |
Control Mode 0 driver only inputs used for monitoring or alarm 1 closed loop control, input b primary sensor 2 on/off control, heating or cooling demand will be 100% when controller is 'occupied'. Sensor inputs used for monitoring or alarm functions |
0 | -100 to 100 % |
| C18 | ALRM | alarm mode
0 ignore alarms 1 report alarms 2 report alarms, shut down all outputs on local alarm 3 report alarms, shut down all outputs on STOP alarm or local alarm 4 report alarms, shut down all outputs on STOP alarm only |
0 | 0 to 4 |
| C19 | ALST | sets alarm state | 0 | 0 to 1 |
| C20 | MXVA* | Maximum voltage channel A | 10.0 | 0.0 to 10.0 volt |
| C21 | MNVA* | Minimum voltage channel A | 0.0 | 0.0 to 10.0 volt |
| C22 | MXVB* | Maximum voltage channel B | 10.0 | 0.0 to 10.0 volt |
| C23 | MNVB* | Minimum voltage channel B | 0.0 | 0.0 to 10.0 volt |
* AOP versions only
Monitoring Parameters
Input Monitoring (3R, 2T1R, 3T and AOP variants)
| ref | Description | default | range | |
| I1 (C30) | FRST | not used in this version | 0 to 1 | |
| I2 (C31) | OCCD | occupied | 0 to 1 | |
| I3 (C32) | WMUP | not used in this version | 0 to 1 | |
| I4 (C33) | EXIP | external input | 0 to 1 | |
| I5 (C34) | COOL | cooling mode | 0 to 1 | |
| I6 (C35) | RLYA | relay A status | 0 to 1 | |
| I7 (C36) | RLYB | relay B status | 0 to 1 | |
| I8 (C37) | RLYC | relay C status | 0 to 1 | |
| W1 (C38) | AUTO | Automatic/manual mode | 0 to 1 | |
| W2 (C39) | OVRD | override | 0 to 1 | |
| W5 (C42) | HAND | Manual HAND override from Doorway | 0 to 1 | |
| W6 (C43) | POT | selects whether the board mounted potentiometer option is fitted or not | 0 to 1 | |
| W7 (C44) | SERV | send service pin (registration) message | 0 to 1 |
Sensors
| ref | Description | default | range | |
| S1 (C50) | TEMP | measured temperature | 5 to 90 C | |
| S2 (C51) | HCOP | heat cool output to drivers (cooling negative) | -100 to 100 % | |
| S3 (C52) | REQD | current setpoint | 5 to 90 C | |
| S4 (C53) | HDMD | heat demand from loop or from Zone Controller | 0 to 100% | |
| S5 (C54) | CDMD | cool demand from loop or from Zone Controller | 0 to 100% | |
| S6 (C55) | FDMD | fan demand | 0 to 100% | |
| S7 (C56) | OSFR | Outside Temperature Override Factor | 0 to 100% | |
| S8 (C57) | WSFR | Wind Speed Override Factor | 0 to 100% | |
| S9 (C58) | WDFR | Wind Direction Override Factor | 0 to 100% | |
| S10 (C59) | FACT | Overall Override Factor | 0 to 100% |
Knobs
| ref | Description | default | range | |
| K1 (C60) | MXWS | Maximum Wind Speed, speed at which Window is Overriden shut | 0 | 0 to 25.0 m/sec |
| K2 (C61) | MNWS | Minimum Wind Speed, speed at which window is still allowed to be 100% open | 0 | 0 to 25.0 m/sec |
| K3 (C62) | Reserved for supervised setpoint from master controller | |||
| K4 (C63) | WNWD | Window Direction, compass bearing looking directly out of the window | 0 | 0 to 360 degrees |
| K5 (C64) | DDEV | Wind Direction deviation, deviation from dead down wind where window must be shut | 0 | 0 to 160 degrees |
| K6 (C65) | NOWS | No Wind, below this Wind Speed the Wind Direction is ignored | 1.0 | 0.0 to 25.0 m/sec |
| K7 (C66) | MNFA | Minimum Fresh Air setting for the Window opening | 10 | 0 to 100% |
| K8 (C67) | OUTT | Outside Temperature Top limit, at which the window can be fully open | 0 | 0.0 to 25.0 degC |
| K9 (C68) | OUTB | Outside Temperature Bottom limit, at or below which the window will be shut | 0 | 0.0 to 25.0 degC |
| ref | Description | range | |
| C180 | DI A | State of Digital input A | 0 or 1 |
| C181 | DI B | State of Digital input B | 0 or 1 |