Pump Changover Module PC1b
22nd October                  Software release notes

  1. Add third relay energises if both pumps have been tried and no 'flow confirmation' signal has been received.
  2. Add Sensor 1 & 2 Hours run for each pump, cumulative values is updated at 01:00 each day to non volatile memory. Hours run resets at 9999 hours.
  3. Add Plots 1 & 2, once per day reading of hours run, displayed as 15 minute increments.
  4. Add switch 3 & 4 , set to ON resets hours run on appropriate pump. Automatically reset to OFF.
  5. Add config variable FMDE failure mode which controls the relay action when both pumps have failed to produce a 'flow confirmation' signal.
  1. Add Override pressed cancels failure mode, this is needed because if FMDE is set to 3, when flow switch is repaired pumps will not restart automatically since both are off and therefore there is no flow.
    1. Inputs, Switches, Sensors & Knobs made available as config style communication request.






Label

Doorway code

DHW Controller

FL A

I1  (C30)

Flow signal Pump A

FL B

I2  (C31)

Flow signal Pump B

EN A

I3  (C32)

Pump A enable
only applicable on 0001 hardware (with pot)


EN B

I4  (C33)

Pump B enable
only applicable on 0001 hardware (with pot)


FAIL

I5  (C34)

One or more pumps failed

PMPA

I6  (C35)

Pump A status

PMPB

I7  (C36)

Pump B status

ALRM

I8  (C37)

relay C Alarm indication

AUTO

W1  (C38)

Automatic, control mode

OVRD

W2  (C39)

Override   

RSTA

W3  (C40)

Reset Hours run Pump A

RSTB

W4  (C41)

Reset Hours run Pump B

HRSA

S1  (C50)

Hours Run Pump A

HRSB

S2  (C51)

Hours Run Pump B