Pump Changeover Controller
PCO3c1

Configuration Tables

Monitoring Parameters

Label Doorway code CT Pump Controller
FL A I1 (C30) Flow signal Pump A
FL B I2 (C31) Flow signal Pump B
EN A I3 (C32) Pump A enable

only applicable on 0001 hardware (with pot)

EN B I4 (C33) Pump B enable

only applicable on 0001 hardware (with pot)

FAIL I5 (C34) One or more pumps failed
PMPA I6 (C35) Pump A status
PMPB I7 (C36) Pump B status
ALRM I8 (C37) relay C Alarm indication
AUTO W1 (C38) Automatic, control mode
OVRD W2 (C39) Override
RSTA W3 (C40) Reset Hours run Pump A
RSTB W4 (C41) Reset Hours run Pump B
HRSA S1 (C50) Hours Run Pump A
HRSB S2 (C51) Hours Run Pump B

Configuration Parameters

ref. Neumonic description default units
C1 ALRM alarm mode

0 do not report alarms

1 report pump failures

2 send STOP alarms

0  
C2 ALST alarm state 0  
C3 FMDE failure mode

1 both pumps remain enabled

2 last pump on remains enabled

3 both pumps disabled

1  
C4 DLAY delay to wait for proof of flow 10 secs
C5 MXHR Maximum hours run before automatic changover to the other pump 24 1 to 200 hours
C6 TYPE driver type

1 Primary Pumps

2 VT Pumps

3 DHW Pumps

4 Heating OSS

5  Heating OCC

6 Heating demand >5%

7  Cooling OSS

8 Cooling OCC

9 Cooling demand >5%

1  
C90 NOAL no alarms 1  
C91 FLFA flow fail A 0  
C92 FLFB flow fail B 0  
C93 STOP STOP alarm 0  
C94 CLRS clear STOP alarm 0