ref |
Description |
default |
range |
|
C1 |
SPFC |
Occupied Setpoint |
20 |
10.0 to 35.0C |
C2 |
SPDB |
Setpoint Deadband |
1.0 |
0.0 to 10.0C |
C3 |
SPTR |
Setpoint Trim |
0 |
-10.0 to 10.0 C |
C4 |
SPTY |
Setpoint
Type, control mode 0 control to SPFC, occupation from Master Zone 1 SPFC supervised from Master Zone 2 Slave Mode. Heat/Cool demands from Zone Controller or another Fan Coil |
1 |
0 to 2 |
C5 |
INMD |
Input Mode
use of terminals 'temp' 0 supply temperature 1 window contact (short = occupied) AND internal occ 2 Time Clock OR internal clock 3 External occupation signal only 4 Alarm input |
0 |
0 to 4 |
C6 |
MAXH |
Maximum Supply Heating setpoint |
30 |
0 to 90C |
C7 |
MINH |
Minimum Supply Heating setpoint |
20 |
0 to 90C |
C8 |
MAXC |
Maximum Supply Cooling setpoint |
18 |
2 to 30C |
C9 |
MINC |
Minimum Supply Heating setpoint |
10 |
2 to 30C |
C10 |
MIND |
Supply minimum demand, used for switching between heating and cooling |
4 |
0.0 to 10.0 |
C11 |
OCCO |
When set controller will only run during the occupied period |
0 |
0 to 1 |
C12 |
HPRD |
heating valve period or minimum on time |
depends on driver type |
1 to 60 secs/10 |
C13 |
HDLY |
Interlock delay negative value delays fan (or pump) after heating starts positive value cause run on of fan after heating shuts down |
0 |
-30.0 to 30.0 minutes |
C14 |
CPRD |
cooling valve period or minimum on time |
depends on driver type |
1 to 60 secs/10 |
C15 |
CDLY |
Interlock delay negative value delays fan (or pump) after cooling starts positive value cause run on of fan after cooling shuts down |
0 |
-30.0 to 30.0 minutes |
C16 |
FPRD |
Fan period, minimum time to change fan speed steps |
12 (2 minutes) |
1 to 60 secs/10 |
C17 |
FRPT |
Frost protect 0 no action 1 open heating valve 50% 2 open heating valve and run pump/fan |
0 |
0 to 2 |
C18 |
MANL |
Manual level , from Doorway |
0 |
-100 to 100 % |
C19 |
HTSC |
Heat source |
1 |
-1 to 100 |
C20 |
CLSC |
Cool source |
0 |
-1 to 100 |
C21 |
HTCT |
setting for constant temperature heating setpoint as demand signal to Boiler ot secondary boiler | 0 | 0 to 100 C |
C22 |
CLCT |
setting fo constant temperature cooling setpoint as demand |
0 |
0 to 20 C |
C23 |
MAXV |
Maximum Box Volume |
100 |
5 to 100% |
C24 |
MINV |
Minimum Box Volume |
25 |
0 to 50 % |
C25 | REHT | Re
Heat
-1 Check availability of Heating and cooling by checking Plenham temperature against setpoint 0 No re heat 1 to 100 Maximum Box volume when in heating |
0 | -1 to 100% |
C26 |
ALRM |
Alarm mode
0 ignore alarms 1 report alarms 2 report alarms, shut down all outputs on alarm 3 report alarms, shut down all outputs on STOP alarm or sensor fail alarm |
1 |
0 to 3 |
C27 |
ALST |
not used |
0 |
0 to 1 |
*AOP versions only
Digital monitoring
6R derivatives (Boiler Board)
ref |
Description |
default |
range |
|
C30 |
INPA |
input A occupation/window contact et al |
0 to 1 |
|
C31 |
INPB |
input B |
0 to 1 |
|
C32 |
RLYA |
relay A |
0 to 1 |
|
C33 |
RLYB |
relay B |
0 to 1 |
|
C34 |
RLYC |
relay C |
0 to 1 |
|
C35 |
RLYD |
relay D (fan A) |
0 to 1 |
|
C36 |
RLYE |
relay E (fan B) |
0 to 1 |
|
C37 |
RLYF |
relay F (fan C) |
0 to 1 |
|
C38 |
AUTO |
Automatic/manual mode |
0 to 1 |
|
C39 |
OVRD |
override |
0 to 1 |
|
C45 |
CGST |
configuration mode |
other boards
ref |
Description |
default |
range |
|
C30 |
INPA |
input A occupation/window contact et al |
0 to 1 |
|
C31 |
OCCD |
occupied |
0 to 1 |
|
C32 |
not used |
0 to 1 |
||
C33 |
not used |
0 to 1 |
||
C34 |
COOL |
cooling mode |
0 to 1 |
|
C35 |
RLYA |
relay A |
0 to 1 |
|
C36 |
RLYB |
relay B |
0 to 1 |
|
C37 |
RLYC |
relay C |
0 to 1 |
|
C38 |
AUTO |
Automatic/manual mode |
0 to 1 |
|
C39 |
OVRD |
override |
0 to 1 |
|
C45 |
CGST |
configuration mode |
ref |
Description |
default |
range |
|
C50 |
BOXV |
box volume |
0 to 100% |
|
C51 |
RTNA |
return air temperature |
5.0 to 35.0 C |
|
C52 |
HCOP |
heat cool output to drivers (cooling negative) |
-100 to 100 % |
|
C53 |
SPSL |
not used |
5.0 to 35.0 C |
|
C54 |
SPRT |
return air setpoint |
5.0 to 35.0 C |
|
C55 |
HDMD |
heat demand from return loop or from Zone Controller |
0 to 100% |
|
C56 |
CDMD |
cool demand from return loop or from Zone Controller |
0 to 100% |
ref |
Description |
default |
range |
|
C60 |
SPOC |
Occupied setpoint |
20.0 |
5.0 to 35.0 C |
C61 |
SPNO |
Non Occupied setpoint |
10.0 |
5.0 to 20.0 C |
C62 |
SPSV |
Supervised setpoint from Master controller |
0 to 35.0 C |
|
C63 |
SPTR |
Setpoint Trim |
0 |
-10.0 to 10.0 C |
C26 |
MXVA* |
Maximum voltage channel A |
10.0 |
0.0 to 10.0 volt |
C27 |
MNVA* |
Minimum voltage channel A |
0.0 |
0.0 to 10.0 volt |
C28 |
MXVB* |
Maximum voltage channel B |
10.0 |
0.0 to 10.0 volt |
C29 |
MNVB* |
Minimum voltage channel B |
0.0 |
0.0 to 10.0 volt |
ref |
Description |
default |
range |
|
C69 |
RTLP |
selects Return Loop parameters |
0 |
0 to 1 |
C70 |
UNDH |
sets very Low muzzy level for heating loop |
3.5 :1.00 |
10 to 200 |
C71 |
OVRH |
sets very High muzzy level for heating loop |
3.5 :1.00 |
10 to 200 |
C72 |
DBBH |
deadband sets limit for OK band for heating loop |
1.5 :0.50 |
10 to 100 |
C73 |
RCGH |
max rate of change heating |
5 to 100 |
|
C74 |
GN H |
gain heating |
20 :50 |
1 to 200 |
C75 |
UNDC |
sets very Low muzzy level for cooling loop |
3.5 :1.00 |
10 to 200 |
C76 |
OVRC |
sets very High muzzy level for cooling loop |
3.5 :1.00 |
10 to 200 |
C77 |
DBBC |
deadband sets limit for OK band for cooling loop |
1.5 :0.50 |
10 to 100 |
C78 |
RCGC |
max rate of change cooling |
5 to 100 |
|
C79 |
GN C |
gain cooling |
20 :50 |
1 to 200 |
ref |
Description |
default |
range |
|
C80 |
XCFG |
forces exit from config mode |
||
C81 |
GRP |
own group number |
ref |
Description |
default |
range |
|
C90 |
NOAL |
no alarm |
||
C91 |
SENF |
sensor fail |
||
C92 |
EXTN |
alarm for external input |
||
C93 |
STOP |
STOP alarm received |
ref |
Description |
default |
range |
|
C100 |
#ACT |
number of Actuators registered to this controller |
||
ref |
Description |
default |
range |
|
C120 |
SLVE |
denotes that this is a Slave Fan Coil |
0 |
0 to 1 |
C121 |
MZON |
zone number of master zone |
0 |
0 to 200 |
ref |
Description |
default |
range |
|
C130 |
PN A |
config variable number for channel A |
51 |
0 to 255 |
C131 |
PT A |
period code for plot A |
1 |
1 to 4 |
C132 |
PN B |
config variable number for channel B |
52 |
0 to 255 |
C133 |
PT B |
period code for plot B |
1 |
1 to 4 |
C134 |
PN C |
config variable number for channel C |
53 |
0 to 255 |
C135 |
PT C |
period code for plot C |
1 |
1 to 4 |
ref |
Description |
default |
range |
|
C150 |
HTYP |
heating driver type |
0 to 5 |
|
C151 |
HSTG |
number of heating stages |
0 to 8 |
|
C152 |
CTYP |
cooling driver type |
0 to 5 |
|
C153 |
CSTG |
number of cooling stages |
0 to 8 |
|
C154 |
FTYP |
fan driver type |
0 to 7 |
|
C155 |
FSTG |
number of fan stages |
0 to 5 |