ref  | 
    Description  | 
    default  | 
    range  | 
  |
C1  | 
    SPFC  | 
    Occupied Setpoint  | 
    20  | 
    10.0 to 35.0C  | 
  
C2  | 
    SPDB  | 
    Setpoint Deadband  | 
    1.0  | 
    0.0 to 10.0C  | 
  
C3  | 
    SPTR  | 
    Setpoint Trim  | 
    0  | 
    -10.0 to 10.0 C  | 
  
C4  | 
    SPTY  | 
    Setpoint 
      Type, control mode 0 control to SPFC, occupation from Master Zone 1 SPFC supervised from Master Zone 2 Slave Mode. Heat/Cool demands from Zone Controller or another Fan Coil  | 
    1  | 
    0 to 2  | 
  
C5  | 
    INMD  | 
    Input Mode 
      use of terminals 'temp' 0 supply temperature 1 window contact (short = occupied) AND internal occ 2 Time Clock OR internal clock 3 External occupation signal only 4 Alarm input  | 
    0  | 
    0 to 4  | 
  
C6  | 
    MAXH  | 
    Maximum Supply Heating setpoint  | 
    30  | 
    0 to 90C  | 
  
C7  | 
    MINH  | 
    Minimum Supply Heating setpoint  | 
    20  | 
    0 to 90C  | 
  
C8  | 
    MAXC  | 
    Maximum Supply Cooling setpoint  | 
    18  | 
    2 to 30C  | 
  
C9  | 
    MINC  | 
    Minimum Supply Heating setpoint  | 
    10  | 
    2 to 30C  | 
  
C10  | 
    MIND  | 
    Supply minimum demand, used for switching between heating and cooling  | 
    4  | 
    0.0 to 10.0  | 
  
C11  | 
    OCCO  | 
    When set controller will only run during the occupied period  | 
    0  | 
    0 to 1  | 
  
C12  | 
    HPRD  | 
    heating valve period or minimum on time  | 
    depends on driver type  | 
    1 to 60 secs/10  | 
  
C13  | 
    HDLY  | 
    Interlock delay negative value delays fan (or pump) after heating starts positive value cause run on of fan after heating shuts down  | 
    0  | 
    -30.0 to 30.0 minutes  | 
  
C14  | 
    CPRD  | 
    cooling valve period or minimum on time  | 
    depends on driver type  | 
    1 to 60 secs/10  | 
  
C15  | 
    CDLY  | 
    Interlock delay negative value delays fan (or pump) after cooling starts positive value cause run on of fan after cooling shuts down  | 
    0  | 
    -30.0 to 30.0 minutes  | 
  
C16  | 
    FPRD  | 
    Fan period, minimum time to change fan speed steps  | 
    12 (2 minutes)  | 
    1 to 60 secs/10  | 
  
C17  | 
    FRPT  | 
    Frost protect 0 no action 1 open heating valve 50% 2 open heating valve and run pump/fan  | 
    0  | 
    0 to 2  | 
  
C18  | 
    MANL  | 
    Manual level , from Doorway  | 
    0  | 
    -100 to 100 %  | 
  
C19  | 
    HTSC  | 
    Heat source  | 
    1  | 
    -1 to 100  | 
  
C20  | 
    CLSC  | 
    Cool source  | 
    0  | 
    -1 to 100  | 
  
C21  | 
    HTCT  | 
    setting for constant temperature heating setpoint as demand signal to Boiler ot secondary boiler | 0 | 0 to 100 C | 
C22  | 
    CLCT  | 
    setting fo constant temperature cooling setpoint as demand  | 
    0  | 
    0 to 20 C  | 
  
C23  | 
    MAXV  | 
    Maximum Box Volume  | 
    100  | 
    5 to 100%  | 
  
C24  | 
    MINV  | 
    Minimum Box Volume  | 
    25  | 
    0 to 50 %  | 
  
| C25 | REHT | Re 
      Heat 
       -1 Check availability of Heating and cooling by checking Plenham temperature against setpoint 0 No re heat 1 to 100 Maximum Box volume when in heating  | 
    0 | -1 to 100% | 
C26  | 
    ALRM  | 
    Alarm mode  
       0 ignore alarms 1 report alarms 2 report alarms, shut down all outputs on alarm 3 report alarms, shut down all outputs on STOP alarm or sensor fail alarm  | 
    1  | 
    0 to 3  | 
  
C27  | 
    ALST  | 
    not used  | 
    0  | 
    0 to 1  | 
  
*AOP versions only
Digital monitoring
6R derivatives (Boiler Board)
ref  | 
    Description  | 
    default  | 
    range  | 
  |
C30  | 
    INPA  | 
    input A occupation/window contact et al  | 
    0 to 1  | 
  |
C31  | 
    INPB  | 
    input B  | 
    0 to 1  | 
  |
C32  | 
    RLYA  | 
    relay A  | 
    0 to 1  | 
  |
C33  | 
    RLYB  | 
    relay B  | 
    0 to 1  | 
  |
C34  | 
    RLYC  | 
    relay C  | 
    0 to 1  | 
  |
C35  | 
    RLYD  | 
    relay D (fan A)  | 
    0 to 1  | 
  |
C36  | 
    RLYE  | 
    relay E (fan B)  | 
    0 to 1  | 
  |
C37  | 
    RLYF  | 
    relay F (fan C)  | 
    0 to 1  | 
  |
C38  | 
    AUTO  | 
    Automatic/manual mode  | 
    0 to 1  | 
  |
C39  | 
    OVRD  | 
    override  | 
    0 to 1  | 
  |
C45  | 
    CGST  | 
    configuration mode  | 
    
other boards
ref  | 
    Description  | 
    default  | 
    range  | 
  |
C30  | 
    INPA  | 
    input A occupation/window contact et al  | 
    0 to 1  | 
  |
C31  | 
    OCCD  | 
    occupied  | 
    0 to 1  | 
  |
C32  | 
    not used  | 
    0 to 1  | 
  ||
C33  | 
    not used  | 
    0 to 1  | 
  ||
C34  | 
    COOL  | 
    cooling mode  | 
    0 to 1  | 
  |
C35  | 
    RLYA  | 
    relay A  | 
    0 to 1  | 
  |
C36  | 
    RLYB  | 
    relay B  | 
    0 to 1  | 
  |
C37  | 
    RLYC  | 
    relay C  | 
    0 to 1  | 
  |
C38  | 
    AUTO  | 
    Automatic/manual mode  | 
    0 to 1  | 
  |
C39  | 
    OVRD  | 
    override  | 
    0 to 1  | 
  |
C45  | 
    CGST  | 
    configuration mode  | 
    
 
      ref  | 
     
      Description  | 
     
      default  | 
     
      range  | 
  |
 
      C50  | 
      BOXV  | 
      box volume  | 
      0 to 100%  | 
  |
 
      C51  | 
      RTNA  | 
      return air temperature  | 
      5.0 to 35.0 C  | 
  |
 
      C52  | 
      HCOP  | 
      heat cool output to drivers (cooling negative)  | 
      -100 to 100 %  | 
  |
 
      C53  | 
      SPSL  | 
      not used  | 
      5.0 to 35.0 C  | 
  |
 
      C54  | 
      SPRT  | 
      return air setpoint  | 
      5.0 to 35.0 C  | 
  |
 
      C55  | 
      HDMD  | 
      heat demand from return loop or from Zone Controller  | 
      0 to 100%  | 
  |
 
      C56  | 
      CDMD  | 
      cool demand from return loop or from Zone Controller  | 
      0 to 100%  | 
  
 
      ref  | 
     
      Description  | 
     
      default  | 
     
      range  | 
  |
C60  | 
    SPOC  | 
    Occupied setpoint  | 
    20.0  | 
    5.0 to 35.0 C  | 
  
C61  | 
    SPNO  | 
    Non Occupied setpoint  | 
    10.0  | 
    5.0 to 20.0 C  | 
  
C62  | 
    SPSV  | 
    Supervised setpoint from Master controller  | 
    0 to 35.0 C  | 
  |
C63  | 
    SPTR  | 
    Setpoint Trim  | 
    0  | 
    -10.0 to 10.0 C  | 
  
C26  | 
    MXVA*  | 
    Maximum voltage channel A  | 
    10.0  | 
    0.0 to 10.0 volt  | 
  
C27  | 
    MNVA*  | 
    Minimum voltage channel A  | 
    0.0  | 
    0.0 to 10.0 volt  | 
  
C28  | 
    MXVB*  | 
    Maximum voltage channel B  | 
    10.0  | 
    0.0 to 10.0 volt  | 
  
C29  | 
    MNVB*  | 
    Minimum voltage channel B  | 
    0.0  | 
    0.0 to 10.0 volt  | 
  
ref  | 
    Description  | 
    default  | 
    range  | 
  |
C69  | 
    RTLP  | 
    selects Return Loop parameters  | 
    0  | 
    0 to 1  | 
  
C70  | 
    UNDH  | 
    sets very Low muzzy level for heating loop  | 
    3.5 :1.00  | 
    10 to 200  | 
  
C71  | 
    OVRH  | 
    sets very High muzzy level for heating loop  | 
    3.5 :1.00  | 
    10 to 200  | 
  
C72  | 
    DBBH  | 
    deadband sets limit for OK band for heating loop  | 
    1.5 :0.50  | 
    10 to 100  | 
  
C73  | 
    RCGH  | 
    max rate of change heating  | 
    5 to 100  | 
  |
C74  | 
    GN H  | 
    gain heating  | 
    20 :50  | 
    1 to 200  | 
  
C75  | 
    UNDC  | 
    sets very Low muzzy level for cooling loop  | 
    3.5 :1.00  | 
    10 to 200  | 
  
C76  | 
    OVRC  | 
    sets very High muzzy level for cooling loop  | 
    3.5 :1.00  | 
    10 to 200  | 
  
C77  | 
    DBBC  | 
    deadband sets limit for OK band for cooling loop  | 
    1.5 :0.50  | 
    10 to 100  | 
  
C78  | 
    RCGC  | 
    max rate of change cooling  | 
    5 to 100  | 
  |
C79  | 
    GN C  | 
    gain cooling  | 
    20 :50  | 
    1 to 200  | 
  
ref  | 
    Description  | 
    default  | 
    range  | 
  |
C80  | 
    XCFG  | 
    forces exit from config mode  | 
    ||
C81  | 
    GRP  | 
    own group number  | 
    
ref  | 
    Description  | 
    default  | 
    range  | 
  |
C90  | 
    NOAL  | 
    no alarm  | 
    ||
C91  | 
    SENF  | 
    sensor fail  | 
    ||
C92  | 
    EXTN  | 
    alarm for external input  | 
    ||
C93  | 
    STOP  | 
    STOP alarm received  | 
    
ref  | 
    Description  | 
    default  | 
    range  | 
  |
C100  | 
    #ACT  | 
    number of Actuators registered to this controller  | 
    ||
ref  | 
    Description  | 
    default  | 
    range  | 
  |
C120  | 
    SLVE  | 
    denotes that this is a Slave Fan Coil  | 
    0  | 
    0 to 1  | 
  
C121  | 
    MZON  | 
    zone number of master zone  | 
    0  | 
    0 to 200  | 
  
ref  | 
    Description  | 
    default  | 
    range  | 
  |
C130  | 
    PN A  | 
    config variable number for channel A  | 
    51  | 
    0 to 255  | 
  
C131  | 
    PT A  | 
    period code for plot A  | 
    1  | 
    1 to 4  | 
  
C132  | 
    PN B  | 
    config variable number for channel B  | 
    52  | 
    0 to 255  | 
  
C133  | 
    PT B  | 
    period code for plot B  | 
    1  | 
    1 to 4  | 
  
C134  | 
    PN C  | 
    config variable number for channel C  | 
    53  | 
    0 to 255  | 
  
C135  | 
    PT C  | 
    period code for plot C  | 
    1  | 
    1 to 4  | 
  
ref  | 
    Description  | 
    default  | 
    range  | 
  |
C150  | 
    HTYP  | 
    heating driver type  | 
    0 to 5  | 
  |
C151  | 
    HSTG  | 
    number of heating stages  | 
    0 to 8  | 
  |
C152  | 
    CTYP  | 
    cooling driver type  | 
    0 to 5  | 
  |
C153  | 
    CSTG  | 
    number of cooling stages  | 
    0 to 8  | 
  |
C154  | 
    FTYP  | 
    fan driver type  | 
    0 to 7  | 
  |
C155  | 
    FSTG  | 
    number of fan stages  | 
    0 to 5  |