VAV Configuration variables 4b5


ref

Description

default

range

C1

SPFC

Occupied Setpoint

20

10.0 to 35.0C

C2

SPDB

Setpoint Deadband

1.0

0.0 to 10.0C

C3

SPTR

Setpoint Trim

0

-10.0 to 10.0 C

C4

SPTY
Setpoint Type, control mode
0 control to SPFC, occupation from Master Zone
1 SPFC supervised from Master Zone
2 Slave Mode. Heat/Cool demands from Zone Controller or another Fan Coil

1

0 to 2

C5

INMD
Input Mode use of terminals 'temp'
0 supply temperature
1 window contact (short = occupied) AND internal occ
2 Time Clock OR internal clock
3 External occupation signal only
4 Alarm input

0

0 to 4

C6

MAXH

Maximum Supply Heating setpoint

30

0 to 90C

C7

MINH

Minimum Supply Heating setpoint

20

0 to 90C

C8

MAXC

Maximum Supply Cooling setpoint

18

2 to 30C

C9

MINC

Minimum Supply Heating setpoint

10

2 to 30C

C10

MIND

Supply minimum demand, used for switching between heating and cooling

4

0.0 to 10.0

C11

OCCO

When set controller will only run during the occupied period

0

0 to 1

C12

HPRD

heating valve period or minimum on time

depends on driver type

1 to 60 secs/10

C13

HDLY

Interlock delay
negative value delays fan (or pump) after heating starts
positive value cause run on of fan after heating shuts down

0

-30.0 to 30.0 minutes

C14

CPRD

cooling valve period or minimum on time

depends on driver type

1 to 60 secs/10

C15

CDLY

Interlock delay
negative value delays fan (or pump) after cooling starts
positive value cause run on of fan after cooling shuts down

0

-30.0 to 30.0 minutes

C16

FPRD

Fan period, minimum time to change fan speed steps

12 (2 minutes)

1 to 60 secs/10

C17

FRPT

Frost protect
0 no action
1 open heating valve 50%
2 open heating valve and run pump/fan

0

0 to 2

C18

MANL

Manual level , from Doorway

0

-100 to 100 %

C19

HTSC

Heat source

1

-1 to 100

C20

CLSC

Cool source

0

-1 to 100

C21

HTCT
setting for constant temperature heating setpoint as demand signal to Boiler ot secondary boiler 0 0 to 100 C

C22

CLCT

setting fo constant temperature cooling setpoint as demand

0

0 to 20 C

C23

MAXV

Maximum Box Volume

100

5 to 100%

C24

MINV

Minimum Box Volume

25

0 to 50 %
C25 REHT Re Heat

-1 Check availability of Heating and cooling by checking Plenham temperature against setpoint

0 No re heat

1 to 100 Maximum Box volume when in heating

0 -1 to 100%

C26

ALRM
Alarm mode 
0 ignore alarms
1 report alarms
2 report alarms, shut down all outputs on alarm
3 report alarms, shut down all outputs on STOP alarm or sensor fail alarm

1

0 to 3

C27

ALST

not used

0

0 to 1


*AOP versions only

Digital monitoring
6R derivatives (Boiler Board)

ref
 
Description
default
range
C30
INPA
input A  occupation/window contact et al
 
0 to 1
C31
INPB
input B
 
0 to 1
C32
RLYA
relay A
 
0 to 1
C33
RLYB
relay B
 
0 to 1
C34
RLYC
relay C
 
0 to 1
C35
RLYD
relay D (fan A)
 
0 to 1
C36
RLYE
relay E (fan B)
 
0 to 1
C37
RLYF
relay F (fan C)
 
0 to 1
C38
AUTO
Automatic/manual mode
 
0 to 1
C39
OVRD
override
 
0 to 1
C45
CGST
configuration mode
   


other boards

ref
 
Description
default
range
C30
INPA
input A  occupation/window contact et al
 
0 to 1
C31
OCCD
occupied
 
0 to 1
C32
 
not used
 
0 to 1
C33
 
not used
 
0 to 1
C34
COOL
cooling mode
 
0 to 1
C35
RLYA
relay A
 
0 to 1
C36
RLYB
relay B
 
0 to 1
C37
RLYC
relay C
 
0 to 1
C38
AUTO
Automatic/manual mode
 
0 to 1
C39
OVRD
override
 
0 to 1
C45
CGST
configuration mode
   


sensors

ref
 
Description
default
range
C50

BOXV

box volume

0 to 100%
C51

RTNA

return air temperature

5.0 to 35.0 C
C52

HCOP

heat cool output to drivers (cooling negative)

-100 to 100 %
C53

SPSL

not used

5.0 to 35.0 C
C54

SPRT

return air setpoint

5.0 to 35.0 C
C55

HDMD

heat demand from return loop or from Zone Controller

0 to 100%
C56

CDMD

cool demand from return loop or from Zone Controller

0 to 100%


knobs

ref
 
Description
default
range

C60

SPOC

Occupied setpoint

20.0

5.0 to 35.0 C

C61

SPNO

Non Occupied setpoint

10.0

5.0 to 20.0 C

C62

SPSV

Supervised setpoint from Master controller

0 to 35.0 C

C63

SPTR

Setpoint Trim

0

-10.0 to 10.0 C

C26

MXVA*

Maximum voltage channel A

10.0

0.0 to 10.0 volt

C27

MNVA*

Minimum voltage channel A

0.0

0.0 to 10.0 volt

C28

MXVB*

Maximum voltage channel B

10.0

0.0 to 10.0 volt

C29

MNVB*

Minimum voltage channel B

0.0

0.0 to 10.0 volt


loop parameters

ref
 
Description
default
range
C69
RTLP
selects Return Loop parameters
0
0 to 1
C70
UNDH
sets very Low muzzy level for heating loop
3.5 :1.00
10 to 200
C71
OVRH
sets very High muzzy level for heating loop
3.5 :1.00
10 to 200
C72
DBBH
deadband sets limit for OK band for heating loop
1.5 :0.50
10 to 100
C73
RCGH
max rate of change heating
 
5 to 100
C74
GN H
gain heating
20 :50
1 to 200
C75
UNDC
sets very Low muzzy level for cooling loop
3.5 :1.00
10 to 200
C76
OVRC
sets very High muzzy level for cooling loop
3.5 :1.00
10 to 200
C77
DBBC
deadband sets limit for OK band for cooling loop
1.5 :0.50
10 to 100
C78
RCGC
max rate of change cooling
 
5 to 100
C79
GN C
gain cooling
20 :50
1 to 200


System

ref
 
Description
default
range
C80
XCFG 
forces exit from config mode
   
C81
 GRP
own group number
   


Alarms

ref
 
Description
default
range
C90
NOAL 
no alarm
   
C91
SENF
sensor fail
   
C92
EXTN
alarm for external input
   
C93
STOP
STOP alarm received
   




Registration table

ref
 
Description
default
range
C100
#ACT
number of Actuators registered to this controller
   
         


Documentation

ref
 
Description
default
range
C120
SLVE
denotes that this is a Slave Fan Coil
0
0 to 1
C121
MZON
zone number of master zone
0
0 to 200


Plot configuration

ref
 
Description
default
range
C130
PN A
 config variable number for channel A 
51
0 to 255
C131
PT A
period code for plot A
1
1 to 4
C132
PN B
 config variable number for channel B 
52
0 to 255
C133
PT B
period code for plot B
1
1 to 4
C134
PN C
 config variable number for channel C 
53
0 to 255
C135
PT C
period code for plot C
1
1 to 4


Driver Parameter

ref
 
Description
default
range
C150
HTYP
heating driver type
 
0 to 5
C151 
HSTG
number of heating stages
 
0 to 8
C152
CTYP
cooling driver type
 
0 to 5
C153 
CSTG
number of cooling stages
 
0 to 8
C154
FTYP
fan driver type
 
0 to 7
C155 
FSTG
number of fan stages
 
0 to 5