Configuration Parameters -  VAV Controller

Types:VAV/DIN/AOP/xxx

Software Release: FCUV4c1

Configuration Parameters


ref
 
Description

default

range

C1

SPFC

Occupied Setpoint

20

10.0 to 35.0C

C2

SPDB

Setpoint Deadband

1.0

0.0 to 10.0C

C3

SPTR

Setpoint Trim

0

-10.0 to 10.0 C

C4

SPTY
Setpoint Type, control mode
0 control to SPFC, occupation from Master Zone
1 SPFC supervised from Master Zone
2 Slave Mode. Heat/Cool demands from Zone Controller or another Fan Coil

1

0 to 2

C5

INMD
Input Mode use of terminals 'temp'
0 supply temperature
1 window contact (short = occupied) AND internal occ
2 Time Clock OR internal clock
3 External occupation signal only
4 Alarm input

0

0 to 4

C6

MAXH

Maximum Supply Heating setpoint

30

0 to 90C

C7

MINH

Minimum Supply Heating setpoint

20

0 to 90C

C8

MAXC

Maximum Supply Cooling setpoint

18

2 to 30C

C9

MINC

Minimum Supply Heating setpoint

10

2 to 30C

C10

MIND

Supply minimum demand, used for switching between heating and cooling

4

0.0 to 10.0

C11

OCCO

When set controller will only run during the occupied period

0

0 to 1

C12

HPRD
for future use -leave as default
depends on driver type

1 to 60 secs/10

C13

HDLY
for future use -leave as default 0
-30.0 to 30.0 minutes

C14

CPRD
for future use -leave as default depends on driver type

1 to 60 secs/10

C15

CDLY
for future use -leave as default 0
-30.0 to 30.0 minutes

C16

FPRD
for future use -leave as default
12 (2 minutes)

1 to 60 secs/10

C17

FRPT

Frost protect
0 no action
1 open heating valve 50%
2 not used in this application

0

0 to 2

C18

MANL

Manual level , from Doorway

0

-100 to 100 %

C19

HTSC

Heat source; points to source of Heating energy (the AHU Controller if no reheat, the source of LPHW if wet reheat battery, set to zero if electric reheat).

1

-1 to 100

C20

CLSC

Cool source; points to source of Cooling energy (the AHU Controller)

0

-1 to 100

C21

MAXV

Maximum Box Volume

100

5 to 100%

C22

MINV

Minimum Box Volume (during Occupancy - box closes during non-Occupancy)

25

0 to 50 %
C23 REHT Re Heat;

-1: Check availability of Heating and cooling by checking Plenum temperature against setpoint

0: No re heat

1 to 100:  sets Maximum Box volume when in heating

0 -1 to 100%

C24

ALRM
Alarm mode 
0 ignore alarms
1 report alarms
2 report alarms, shut down all outputs on alarm
3 report alarms, shut down all outputs on STOP alarm or sensor fail alarm

1

0 to 3

C25

ALST

not used

0

0 to 1

Monitoring Parameters

Input Monitoring


ref
 
Description

default

range

C30

EXTI

input A occupation/window contact function determined by setting of INMD
 
0 to 1

C31

OCCD

occupied
 
0 to 1

C32
 
not used
 
0 to 1

C33
 
not used
 
0 to 1

C34

COOL

cooling mode
 
0 to 1

C35

RLYA

not used
 
0 to 1

C36

RLYB

not used
 
0 to 1

C37

RLYC

not used
 
0 to 1

C38

AUTO

Automatic/manual mode
 
0 to 1

C39

OVRD

override
 
0 to 1

C42

HAND
Manual Hand Mode 0
0 to 1

C43
POT Potentiometer fitted to board 0
0 to 1
C44 SERV operation of Registration button from Doorway self resets 0 to 1

C45

CGST

configuration mode
   

Sensors


ref
 
Description

default

range

C50

BOXV

current box volume (if volume feedback signal used)
 
0 to 100%

C51

RTNA

return air temperature
 
5.0 to 35.0 C

C52

HCOP

heat cool output to drivers (cooling negative)
 
-100 to 100 %

C53

SPSL

not used
 
5.0 to 35.0 C

C54

SPRT

return air setpoint
 
5.0 to 35.0 C

C55

HDMD

heat demand from return loop or from Zone Controller
 
0 to 100%

C56

CDMD

cool demand from return loop or from Zone Controller
 
0 to 100%

Knobs

 


ref
 
Description

default

range

C60

SPOC

Occupied setpoint

20.0

5.0 to 35.0 C

C61

SPNO

Non Occupied setpoint

10.0

5.0 to 20.0 C

C62

SPSV

Supervised setpoint from Master controller
 
0 to 35.0 C

C63

SPTR

Setpoint Trim

0

-10.0 to 10.0 C

C26

MXVA*

Maximum voltage channel A

10.0

0.0 to 10.0 volt

C27

MNVA*

Minimum voltage channel A

0.0

0.0 to 10.0 volt

C28

MXVB*

Maximum voltage channel B

10.0

0.0 to 10.0 volt

C29

MNVB*

Minimum voltage channel B

0.0

0.0 to 10.0 volt