| Configuration Parameters - VAV Controller | 
Configuration Parameters
ref  | 
    Description  | 
    default  | 
    range  | 
  |
C1  | 
    SPFC  | 
    Occupied Setpoint  | 
    20  | 
    10.0 to 35.0C  | 
  
C2  | 
    SPDB  | 
    Setpoint Deadband  | 
    1.0  | 
    0.0 to 10.0C  | 
  
C3  | 
    SPTR  | 
    Setpoint Trim  | 
    0  | 
    -10.0 to 10.0 C  | 
  
C4  | 
    SPTY  | 
    Setpoint Type, control mode 0 control to SPFC, occupation from Master Zone 1 SPFC supervised from Master Zone 2 Slave Mode. Heat/Cool demands from Zone Controller or another Fan Coil  | 
    1  | 
    0 to 2  | 
  
C5  | 
    INMD  | 
    Input Mode use of terminals 'temp' 0 supply temperature 1 window contact (short = occupied) AND internal occ 2 Time Clock OR internal clock 3 External occupation signal only 4 Alarm input  | 
    0  | 
    0 to 4  | 
  
C6  | 
    MAXH  | 
    Maximum Supply Heating setpoint  | 
    30  | 
    0 to 90C  | 
  
C7  | 
    MINH  | 
    Minimum Supply Heating setpoint  | 
    20  | 
    0 to 90C  | 
  
C8  | 
    MAXC  | 
    Maximum Supply Cooling setpoint  | 
    18  | 
    2 to 30C  | 
  
C9  | 
    MINC  | 
    Minimum Supply Heating setpoint  | 
    10  | 
    2 to 30C  | 
  
C10  | 
    MIND  | 
    Supply minimum demand, used for switching between heating and cooling  | 
    4  | 
    0.0 to 10.0  | 
  
C11  | 
    OCCO  | 
    When set controller will only run during the occupied period  | 
    0  | 
    0 to 1  | 
  
C12  | 
    HPRD  | 
    for future use -leave as default | 
    depends on driver type | 
    1 to 60 secs/10  | 
  
C13  | 
    HDLY  | 
    for future use -leave as default | 0 | -30.0 to 30.0 minutes  | 
  
C14  | 
    CPRD  | 
    for future use -leave as default | depends on driver type | 
    1 to 60 secs/10  | 
  
C15  | 
    CDLY  | 
    for future use -leave as default | 0 | -30.0 to 30.0 minutes  | 
  
C16  | 
    FPRD  | 
    for future use -leave as default | 12 (2 minutes)  | 
    1 to 60 secs/10  | 
  
C17  | 
    FRPT  | 
    Frost protect 0 no action 1 open heating valve 50% 2 not used in this application  | 
    0  | 
    0 to 2  | 
  
C18  | 
    MANL  | 
    Manual level , from Doorway  | 
    0  | 
    -100 to 100 %  | 
  
C19  | 
    HTSC  | 
    Heat source; points to source of Heating energy (the AHU Controller if no reheat, the source of LPHW if wet reheat battery, set to zero if electric reheat).  | 
    1  | 
    -1 to 100  | 
  
C20  | 
    CLSC  | 
    Cool source; points to source of Cooling energy (the AHU Controller)  | 
    0  | 
    -1 to 100  | 
  
C21  | 
    MAXV  | 
    Maximum Box Volume  | 
    100  | 
    5 to 100%  | 
  
C22  | 
    MINV  | 
    Minimum Box Volume (during Occupancy - box closes during non-Occupancy)  | 
    25  | 
    0 to 50 %  | 
  
| C23 | REHT | Re Heat; -1: Check availability of Heating and cooling by checking Plenum temperature against setpoint 0: No re heat 1 to 100: sets Maximum Box volume when in heating  | 
    0 | -1 to 100% | 
C24  | 
    ALRM  | 
    Alarm mode   0 ignore alarms 1 report alarms 2 report alarms, shut down all outputs on alarm 3 report alarms, shut down all outputs on STOP alarm or sensor fail alarm  | 
    1  | 
    0 to 3  | 
  
C25  | 
    ALST  | 
    not used  | 
    0  | 
    0 to 1  | 
  
Monitoring Parameters
Input Monitoring
|   ref  | 
      Description  | 
      default  | 
      range  | 
  |
|   C30  | 
      EXTI  | 
      input A occupation/window contact function determined by setting of INMD  | 
      0 to 1  | 
  |
|   C31  | 
      OCCD  | 
      occupied  | 
      0 to 1  | 
  |
|   C32  | 
      not used  | 
      0 to 1  | 
  ||
|   C33  | 
      not used  | 
      0 to 1  | 
  ||
|   C34  | 
      COOL  | 
      cooling mode  | 
      0 to 1  | 
  |
|   C35  | 
      RLYA  | 
      not used  | 
      0 to 1  | 
  |
|   C36  | 
      RLYB  | 
      not used  | 
      0 to 1  | 
  |
|   C37  | 
      RLYC  | 
      not used  | 
      0 to 1  | 
  |
|   C38  | 
      AUTO  | 
      Automatic/manual mode  | 
      0 to 1  | 
  |
|   C39  | 
      OVRD  | 
      override  | 
      0 to 1  | 
  |
C42  | 
    HAND  | 
    Manual Hand Mode | 0 | 0 to 1  | 
  
C43  | 
    POT | Potentiometer fitted to board | 0 | 0 to 1  | 
  
| C44 | SERV | operation of Registration button from Doorway self resets | 0 to 1 | |
|   C45  | 
      CGST  | 
      configuration mode  | 
    
Sensors
ref  | 
    Description  | 
    default  | 
    range  | 
  |
C50  | 
    BOXV  | 
    current box volume (if volume feedback signal used)  | 
    0 to 100%  | 
  |
C51  | 
    RTNA  | 
    return air temperature  | 
    5.0 to 35.0 C  | 
  |
C52  | 
    HCOP  | 
    heat cool output to drivers (cooling negative)  | 
    -100 to 100 %  | 
  |
C53  | 
    SPSL  | 
    not used  | 
    5.0 to 35.0 C  | 
  |
C54  | 
    SPRT  | 
    return air setpoint  | 
    5.0 to 35.0 C  | 
  |
C55  | 
    HDMD  | 
    heat demand from return loop or from Zone Controller  | 
    0 to 100%  | 
  |
C56  | 
    CDMD  | 
    cool demand from return loop or from Zone Controller  | 
    0 to 100%  | 
  
ref  | 
    Description  | 
    default  | 
    range  | 
  |
C60  | 
    SPOC  | 
    Occupied setpoint  | 
    20.0  | 
    5.0 to 35.0 C  | 
  
C61  | 
    SPNO  | 
    Non Occupied setpoint  | 
    10.0  | 
    5.0 to 20.0 C  | 
  
C62  | 
    SPSV  | 
    Supervised setpoint from Master controller  | 
    0 to 35.0 C  | 
  |
C63  | 
    SPTR  | 
    Setpoint Trim  | 
    0  | 
    -10.0 to 10.0 C  | 
  
C26  | 
    MXVA*  | 
    Maximum voltage channel A  | 
    10.0  | 
    0.0 to 10.0 volt  | 
  
C27  | 
    MNVA*  | 
    Minimum voltage channel A  | 
    0.0  | 
    0.0 to 10.0 volt  | 
  
C28  | 
    MXVB*  | 
    Maximum voltage channel B  | 
    10.0  | 
    0.0 to 10.0 volt  | 
  
C29  | 
    MNVB*  | 
    Minimum voltage channel B  | 
    0.0  | 
    0.0 to 10.0 volt  |