Feature
Notes

Configuration Tables

Data Sheet

Wiring

History

Feature Notes

Datasheet

 

Air Handing Unit Controller
FRE version for Constant Supply Temperature Control
(SPTY 3&4)

Latest released version is 4c2

Document last updated 03/11/2003
Recent features not included on Data sheet are in
RED text

AHU / DIN / FRE / .../.../...

Main Features

Controls Supply & Extract Fans, Heating and Cooling Batteries

More complex Air Handling Units controlled by adding modules

AHU may feed single or multiple zones

Constant Supply, fixed or user adjustable setpoint

Demand signals fed to Main Plant automatically

Summary Features

User Features

Supply Air Temperature Setpoint may be adjusted using a Zone Controller.
Occupation Times for the spaces served by the AHU are set on Zone Controllers. The AHU will run if any of the Zones are in their Occupation period

Engineering Features

Automatic “Plug-and-Play” engineering using SeaChange Pushbutton Registration.
Demand Signals for Heating and Cooling are automatically fed back to main plant so that Boilers and Chillers only run when needed.
Control of more complex AHUs (e.g. with Preheater, Heat recovery, Multiple Heating or Cooling Stages etc.) is achieved by adding further modules. Interlocks are used by additional modules automatically.
Configuration Parameters may be set using a Zone Controller or SeaChange Doorway.

General Control Description

The AHU Controller will control supply (off-coil) temperature to a fixed setpoint, providing that it is receiving an Occupancy signal from at least one of the Zone Controllers that are registered to it, or the controller is being driven from an external timeclock (see later).
The Setpoint may alternatively be made adjustable by the user, using a Zone Controller (see Registration, later).
A return air temperature sensor may be fitted, either for monitoring purposes, or because it is needed for Night Cooling (see later) or by another module (e.g. Mixing Damper Controller or Heat Recovery Controller).
A deadband may be set which will prevent cycling between heating and cooling and reduce energy usage.
Heating and cooling batteries may be “wet” i.e. coils fed with LPHW and Chilled water, controlled by raise/lower type valves, or they may be staged electric batteries, switched by external contactors.
Supply and Extract Fans are interlocked with the batteries to ensure correct operation. It is possible to select whether the supply or extract starts first, to ensure positive or negative pressurisation of the building.

Description of Features

Temperature Control

The AHU Controller will control supply (off-coil) temperature to a fixed setpoint set using Configuration parameter SPAH, or an adjustable setpoint, using a Zone Controller (see Registration, later). A deadband may be set (using the DBND parameter) which will prevent cycling between heating and cooling and reduce energy usage.
Heating and cooling batteries may be “wet” ie. coils fed with LPHW and Chilled water, controlled by raise/lower type valves, or they may be staged electric batteries, switched by external contactors. The correct product variant should be selected to suit the combination of wet or electric batteries.

SPTY 3 : Supply Temperature control, Occupancy from one or more Zones

This mode allows the AHU to supply fixed temperature air when any of the registered Zones are occupied. The Zones provide this information using an additional network variable thus allowing the Heat/Cool demands from each zone to be passed to the relevant main plant for the primary Space temperature control. The AHU is put into config and the zones are registered to it, the Zone will confirm the connection by displaying OCDS (occupancy destination) 51 (for AHU1)

The Supply air setpoint is set on Knob 1 (or config C1) and is the midpoint setpoint. The deadband between heating and cooling setpoints is set on config C2 SPDB.

SPTY 4 : Supply Temperature control, Occupancy from one or more Zones, setpoint supervised by a Zone Controller

This mode operates as for the above mode SPTY 3 with the additional feature that the supply setpoint can be made to track the setpoint of a particular Zone Controller. To achieve this the zones are registered to the AHU as above, then the designated Zone is put into config and the AHU registration button pressed to make the Setpoint supervision link, the Zone will report SAHU 1 etc.
The AHU setpoint can be 'modified' with the SPTR setpoint trim config variable, this will be useful if the AHU air needs to be say 1 degree too low so that the zone makes up the correct space temperature with say perimeter heating, or where one Zone is used to set all the AHU's in the building and they need to be individually trimmed to compensate for local conditions.

Simultaneous Heating and Cooling

Normally, simultaneous use of the heating and cooling batteries is automatically prevented. However, under certain circumstances it may be necessary: either when Dehumidifying the Supply Air (see Humidity Control) or because staged cooling is being used.
With staged (DX) cooling, large step changes to the supply air temperature may be experienced when the stage is switched on and off. If this is not permissible, and a modulating heater battery is provided, this can be enabled at the same time as the staged cooling battery. Although this is not energy efficient, it may be the only way to achieve stable control of temperature using the mechanical plant provided.
To enable simultaneous heating and cooling, set parameter HCOK to 1. (Note: do not adjust this parameter when using dehumidifying control).

Occupancy Control

If using one of the Control modes based on Occupancy, it is possible to prevent the AHU from starting for Optimum Start or Fabric Protection, this would be appropriate for Fresh Air plants which only need to run when the building is occupied. A config variable OCCO (Occupation only) when set to 1 provides this feature. Otherwise the AHU will start for all Occupancy states other than non Occupied. The associated Zone Controller must be version ZON3b or later.

Occupation Destination

The config variable OCDS has been added which allows the Occupancy state of one AHU to be passed to another AHU or indeed to any SeaChange module wich supports receipt of the Occupancy status (DHW for example). This might be used when a number of tempered Air plants needs to run if any zone in the building is occupied. The Occupaction status of the Zones can be collated by one AHU as normal then it's occupancy state can be passed to the next and so on. Simply set the OCDS parameter to point to the required device (AHU number plus 50) and ensure that the receiving AHU is operating in SPTY 0, 3 or 6.

Humidity Control

If the AHU Controller is equipped with a Cooling battery and is appropriately constructed (with condensate trays, baffles etc.), it is possible to De-Humidify the Supply Air by applying full cooling. If the dew point of the incoming air is higher than the off-coil temperature, condensation will occur, thus de-humidifying the air. The Heater Battery can now be used to reheat the air to the required temperature; this will mean allowing Heating and Cooling Batteries to run simultaneously (which is normally prohibited). Setting a non-zero value for RHSP (see below) automatically allows simultaneous heating and cooling.
Parameters RHSP and RHDB set the Return (or Space) Humidity setpoint and deadband respectively; setting RHSP to a non-zero value enables Dehumidification control. If the Return Air Humidity rises above: (setpoint + 1/2 of the deadband) the supply air cooling setpoint will be depressed to drive the cooling coil fully open. It will stay in this mode until the Return Air Humidity falls to: (setpoint - 1/2 of the deadband) when normal temperature control will resume.
The Supply heating loop remains active and this will endeavour to maintain the required supply temperature.
Note when operating in De-Hum mode the HCOK must be set to zero, the heating and cooling operation is handled by the De-Hum control logic.
A Networked Temp + Rh sensor must be fitted in the Return Air (or in the space) and registered as a Submodule to the AHU Controller (see Registration, later). Supply and Outside T+Rh sensors can also be registered to the AHU Controller for monitoring purposes.
Humidification of the Supply Air using a Humidifier may be controlled by a Humidity Controller Submodule. Also, a different regime of Hum / DeHum control can be used to give tighter control of Rh; see Humidity Controller Data Sheet for further details.
If  Close Humidity control is being used then the AHU De-Hum features are not used and RHSP must be set to zero to disable them. In this case the Hum and De-Hum are controlled by the Humidity controller and the Cooling coil override will take place automatically when the Humidity controller is setup.

Dessicant AHU control modules

The AHU can be used as the base controller for controlling Dessicant Cooled AHU's, The following special control modules can be registered to the AHU to create a Dessicant AHU solution. The special control modules take in the Heat demand% and Cool Demand% from the AHU, and rescale it to produce either a direct output to the driver stages or a setpoint to an interposing control loop.
Please contact smartkontrols for further information on the control modules below, or follow the links in History/Issue Notes.
Thermal Wheel/Evaporative Cooler controller registered as Mixing Damper/Heat Recovery [A1M1]
Dessicant Wheel/ReGen heater controller registered as Actuator, register first [A1C1]
Motor Speed controller, fan speed as function of Outside temperature, registered as Actuator [A1C2]
Supply Air Evaporative Cooler, Humidity controller with CMDE=0, registers as HUM [A1H1]

Mixing Damper control

A Damper controller can be setup to use the mixing dampers as the first stage of heating and cooling control. This allows modulation of the dampers without the need for a mixed air temperature sensor. The AHU needs to have a Return Air temperature values, either hard wired or networked and an Outside temperature value in order to determine the sense of operation of the dampers (heating or cooling).
If the damper is used as part of the heating/cooling sequence a configuration parameter in the Damper controller DMPC is set to the percentage of heat and cool demand which will be utilised by the damper controller. In this case the AHU driver re-scaling needs to be set up so that the AHU heating and cooling outputs do not start until the damper sequence is completed. So if DMPC (DeMand PerCent) in the Damper controller is set to 25%, then the minimum driver rescale parameters for heat and cool (HRMN,CRMN) should also be set to 25%.

Fan Control

Supply and Extract fans may be switched (via a contactor) directly from the outputs on the controller. Alternatively, the fan outputs may be used to open isolation dampers (if fitted) and limit switches on the dampers used to start the fan; this ensures that fresh air and exhaust dampers are fully open before the fans start, so as to avoid damage to the damper blades.
The parameter SFRT may be used to determine which fan starts first; some buildings (e.g.. clean rooms) need to be positively pressurised, in which case the supply fan should start first. Other buildings (e.g.. hospitals) require the opposite; the parameter should be set accordingly.
The fan is also subject to an automatic start delay, which is determined according to the address of the controller. This ensures that, where a building has multiple AHUs, all of the fans do not start at once, thus causing a high peak electrical load. AHUs will start with 10 second intervals between them. This provides a 10 second delay between AHU units on the same subnet. The maximum delay is 100 seconds.

Frost Protection

If the Heating and Cooling Batteries are “wet”, the Controller will open both batteries to 50% in the event that the Outside Temperature falls below the Frost Protection Setpoint SPFR during non-occupation.This will ensure that both the coil and its bypass have water circulating through them. Control of the water temperature and pumps is handled either by the Boiler Controller, or by an existing control system.

Interlocks

The fans are interlocked with heating and cooling batteries automatically, to prevent damage to the batteries from frost or overheating. The nature of the interlock varies according to the type of battery:
Note if a Preheater module is registered to the AHU the AHU will automatically change to the interlocks appropriate to the Pre Heater

Wet Heating Interlocks

The fans will start after the heater battery has been opened, to avoid drawing cold air through the unit before the heater battery is operational, and thus causing damage or tripping the frost thermostat (if fitted).
If the Controller is receiving valid signals for both Outside Temperature and Boiler Flow Temperature, the fan will not start until:
a) Outside Temp >5 oC and Boiler Flow Temp>10 oC,
Or,
b) Flow Temp> (20-Outside Temp) x 2 AND a delay of 5 minutes has elapsed since the valve achieved 50% open
If either the Boiler Flow Temperature or Outside Temperature are not available (because of a system fault, or because the Boilers are not under SeaChange control), then the fan will not start until a delay of 10 minutes has elapsed since the valve achieved 50% open.
The controller will indicate that it is in Frost Start Up mode by flashing the temperature led amber, this state can be monitored remotely by monitoring C181 SILK.

Overriding Frost Start Up Interlocks

While commissioning it is sometimes useful to bypass the start up delay, this can be done by changing the state of switch W3 RSET when the AHU is in Frost Start Up mode. Ensure you have adequate hot water flow to the heater batteries. Frost damage can not be blamed on the control system if you have overriden the built in protection.

Supply Temperature Cut Off

In addition to the frost protection mentioned earlier and the delays associated with starting under cold conditions when the heater battery is raise lower i.e. assumed to be water heated, a further protection is that if the supply air temperature falls below the setting of CUTS (default 4) then the AHU fans will be stopped. If the AHU is not water heated, e.g. direct gas fired then this parameter should be set to zero to disable this feature. Beware of setting CUTS too high because this may lead to the AHU not being able to start when the outside temperature is very low, also do not set it too low (less than 2) beacuse it is usually only a point measurement and some areas of the heater battery may be at a significantly lower temperature.

Electric Heating and Cooling Interlocks

The batteries will not be enabled until the supply fan is running, and the fan will continue to run after the battery has shut down, for a period determined by the fan minimum run time parameter MINR.

Alarm Handling

The AHU Controller has 2 status inputs for volt-free contacts. The Controller may be set to ignore these inputs as alarm conditions and use them purely for monitoring, report them to a SeaChange Doorway Supervisor (either locally connected to the system, or via an autodialling modem), or to both report alarms and shut down the AHU. The ALRM parameter is used to select the desired Alarm Mode, whilst ALST is used to set the sense (ie. whether a closing or opening contact generates an alarm) of the Fan Fail and Filter Blocked inputs.
The AHU Controller will generate 2 different alarms from these 2 inputs;
FANF
Fan Failure (which would need a “fan running” status signal wired to the appropriate input)
FLTF
Filter Blocked (which would need a differential pressure switch installed across the filter).
FLTF will not shut down the AHU
Note that if only one of the two inputs is used, the other input may need a shorting link wired across it in order to prevent the generation of spurious alarms.
A delay or Grace time can be introduced on the Fan Fail alarm to allow time for interlocked inlet dampers to fully open. This value is set in seconds on parameter ADLY.
The AHU Controller can also be set to respond to the STOP System Stop Alarm which is generated by a Boiler Controller; this can be used to shut down the entire control system, or parts of it, if a particularly critical event occurs (e.g.. Pressurisation Unit failure).
The setting of ALRM is as follows:
ALRM = 0
Ignore alarms (inputs could be used for monitoring status of any volt-free contact)
ALRM = 1
Report alarms FANF and FLTF, no control action
ALRM = 2
Report alarms, shut down all outputs on receipt of STOP alarm
ALRM = 3
Report alarms, shut down all outputs on STOP alarm or FANF alarm

Alarm Interlocks

Some protection interlocks (which are active at all times unless specifically disabled) cause the AHU to shut down, and will generate an alarm. Once shut down,the AHU will attempt to restart after a delay set on parameter RTRY (retry), or if the Override button is pressed.
FANF
Alarm if generated from a Fan Changeover Module registered to the AHU (if this feature is not required, the Changeover Module’s ALRM parameter may be set to generate no alarms)
FREZ
Danger of Freezing, which is generated when the Supply Air Temperature drops below a limit set on parameter CUTS (default 4 degC). If this value is set to zero, this feature is disabled
SPLF
Supply Temperature Failed which is generated when the Supply Sensor reading is invalid (not used if SPTY set to 6 or 7, Return-only control)
OUTF
Outside Temperature Fail, which is generated when the AHU Controller is not receiving a valid Outside Temperature (either locally connected or via the network from another module).This alarm does not cause the AHU to shut down

Local Indication of Alarms

The AHU Controller will flash its temperature lamp red if any Alarm or Alarm Interlock is current. When the Alarm clears, the flashing will stop.

Night Cooling

It may be possible to use the Air Handling Unit to provide free cooling of the space during non-occupied hours by running the fans only (ie. with the cooling battery disabled). This requires that a sensor is wired to the Return Air Temperature terminals; the sensor may need to be located in the space, as it must give a representative reading of space temperature when fans are not running.
Normally, the setpoint for Night Cooling would be set to be within the normal deadband (using parameter NTCL).
Night Cooling will then commence (using the preheater if necessary), if:
The Return Sensor reading is valid, and above the Night Cooling Setpoint
AND the Outside Temperature is above 5 deg C,
AND the outside Temperature is at least 1 deg C below the Night Cooling Setpoint
AND it is at least 1 hour since the last Night Cooling cycle terminated
Once the purge starts it will run for at least the minimum run time of the AHU or until the Return Air temperature is below or equals the night cool setpoint. The purge routine will not recommence for at least an hour.

Multiple Space Sensors

The AHU capabilities have been extended to allow multiple AHU's to feed one large space where making individual return air measurements is impossible. Multiple space temperature measurements are made using networked sensors, or Zone controllers, these values are processed by a Monitoring Module (3a2) to produce an average value which can be used as the return air temperature on the AHU.
The AHU controller can be used with the Monitor Module to enable it to control to the average, maximum, or minimum of up to 10 networked Temperature or temperature and RH sensors. In this situation a Zone controller can be used as a networked temperature sensor. The sensors are registered to the Monitor Module in the normal manner, then the Monitor Module is registered to the AHU. The AHU will consider the Monitor Module to be a Return Air (RHR) temperature and RH sensor. The values of Monitor sensor 6 (temp) and Monitor sensor 7(RH) are presented to the AHU as Return Air Temperature and RH. The monitor module can be set to deliver average (default) maximum or minimum.

Networked Sensors

The AHU will accept TRH sensors for Return, Supply and Outside temperature and RH values. Register the sensors to the AHU in the normal manner. A hard wired sensor overrides the networked value.

Operation from an external volt-free contact and trim potentiometer

It may not possible to use a Zone Controller (or a number of Zone Controllers) as the only devices to set Occupancy times for the space, and hence determine running times for the AHU. It is possible to use an external signal to run the AHU Controller, for instance a timed signal from an existing control system, or a simple timeclock. Alternatively, it is possible to disable the AHU using an external signal. The INMD parameter is used to set the desired mode, and then a volt-free contact from the timeclock device may be wired to the “Spare a” input (note that contact must be “made” for AHU to run).
Three different modes are available; the external contact may be used in conjunction with a Zone Controller (or a number of Zone Controllers), either:
a) as an “OR” function (INMD = 2) when the Zones Occupancy or the external contact will cause the AHU to run or,
b) as an “AND” function (INMD = 1) when both the Zones Occupancy and the external signal need to be present - this can be used as a disabling input, e.g. a window contact.
Alternatively, the external contact can be used as the sole means of enabling the AHU (INMD = 3).
Input 13-14
VFC input or potentiometer
INMD = 1
Disabling AHU from an External Contact
e.g. Window contact
INMD = 2
Enabling AHU from an External Contact
e.g. Occupancy extension switch
(for Zones or VFC enable)

INMD = 3
Enabling AHU from an External Contact
e.g. External timeswitch
(for VFC enable only)
INMD = 1, 2 or 3
 
External Setpoint Trim Potentiometer
SeaChange SEN/PTR/ROM/002
Pot gives +/- 5 DegC setpoint adjustment
INMD = 1
Setpoint Trim with external Disable Contact
SeaChange SEN/PTR/ROM/004
INMD = 2 or 3
Setpoint Trim with external Enable Contact
SeaChange SEN/PTR/ROM/004

Setpoint Trim using an external potentiometer

If a 10Kohm potentometer and a 1Kohm resistor (use SeaChange SEN/PTR/ROM/004) are wired in series with the external contact, the pot will apply a +/- 5 degC trim adjustment to the current setpoint when in Occupancy.

Driver Re-scaling

It is now possible to re-scale the input to the driver on the AHU. This allows the full range of the driver output to be achieved over a selected range of the control loop output. The selected range is set up using config variables HRMX, HRMN for the heating driver and CRMX, CRMN for the cooling driver. An example will clarify it's use.
If HRMN is 0, and HRMX is 50, the internal heating driver will operate from 0 to 100% as the control output varies from 0 to 50%.  Actuator Controllers issue 3d1 or later and the Dessicant control modules have input re-scaling, so in this example an actuator would be able to take up the control output for the range 50% to 100% by setting it's re-scale parameters to HRMN 50, HRMX 100. This allows a diverse range of heating and cooling resources to be applied in a co-ordinated manner.

Submodules

AHU Controllers may have a number of Submodules which extend its control capabilities; these can be as follows:
Submodule Type
Max
Preheater Submodule
for Preheater (frost) battery control
1
Humidity Submodule
to control Humidifier.
1
T+Rh Networked Sensors
to sense Return (or Space), Supply and Outside Temp + Humidity
3
and
Submodule Type
Max
Damper Submodule
to control mixing dampers for heat recovery
1
or
 
Heat recovery Submodule
to control heat wheel, runaround coil etc.
1
and
Submodule Type
Max
Fan Changeover Submodules
for Auto Changeover of Supply and Extract fans.
2
or
 
Static Pressure Submodule
to control fan speed in a VAV plant.
2
and any two from
Submodule Type
Cascade Submodule
additional stages of heating or cooling (5 stages max total of each)
or
Actuator Submodule
driven by AHU demand signals; can use AOP version for 0 -10V DC valves.
or
Dessicant Wheel Controller
refer to SeaChange for details.

Registration

Registration is the simple process by which logical connections are made between Controllers in a SeaChange system; it is done at time of commissioning and involves pressing buttons on the Controllers in a specific sequence. For further details of the registration process, see our publication “Engineering Guide”.

Registration of the AHU Controller

The AHU Controller must first be registered with the Controller in the system which is performing System Housekeeping Functions, unless it is performing the Housekeeping Functions for the system itself (see later section). This part of the registration process will allocate a system address to the Controller. Press the register button; the status lamp should flash according to the address that has been allocated. For further details of the registration process, see our publication “Engineering Guide”.
If the AHU has “wet” heating or cooling batteries, it must then be registered with its heating or cooling source, ie. the Controller that is providing hot or chilled water to the batteries (e.g. a Boiler Controller).This will automatically set the HTSC and CLSC parameters in the AHU Controller to “point” to the source of heating and/or cooling. Demand signals will then automatically be sent to the heat/cooling sources when the AHU coils require heating and cooling. The heat or cooling source Controller is put into Configuration Mode, and the AHU Controller is registered to it. For further details of the registration process, see our publication “Engineering Guide”.

Registration of Submodules

The AHU Controller may have one, or a number of Submodules associated with it for controlling Preheaters, Mixing Dampers and so on. These Submodules must be registered to the AHU Controller so that it works in co-ordination with the Submodules, and all necessary demand signals, interlocks etc. are passed between them.
The AHU Controller is put into Configuration Mode, and the Submodules are registered to it. This process will allocate an address to each Submodules; the status lamp on each one should flash to indicate the address that the AHU Controller has allocated to it.

Registration of Zone Controllers - Occupancy Demand Linking

One, or many Zone Controllers can be used to determine the operating times of the AHU Controller. This is done by registering the Zone Controllers to the AHU Controller. This part of the process will automatically set the Occupancy Destination OCDS parameter in the Zone Controllers to “point” to the AHU Controller. The OCDS parameter will be set to (50 + n), where n is the AHU address (so the Zone controller will have its HTSC and CLSC parameters set to 51 for AHU1, 52 for AHU2 etc). Thus when any of these Zone Controllers enter their Occupied state, the AHU will run (the AHU may be made to run during the Optimum Start period and Fabric Protection mode as well by setting the OCCO parameter). The AHU Controller is put into Configuration Mode, and the Zone Controllers are registered to it. For further details of the registration process, see our publication “Engineering Guide”.

Registration of Zone Controller - Setpoint Supervision

If a Zone Controller is to be used to adjust the setpoint of the AHU Controller (it need not be one of the Zone Controllers controlling the operating times of the AHU), then the AHU Controller must be registered to that Zone Controller. The SLVM parameter in the Zone Controller must be set to 2 or 3 to enable remote supervision of a setpoint.and the AHU config parameter SPTY must be changed from 3 to 4 to enable receipt of the setpoint. The Zone Controller is put into Configuration Mode, and the AHU Controller is registered to it. For further details of the registration process, see our publication “Engineering Guide”. This will then set up a setpoint slave connection between the Zone Controller and the AHU Controller (confirmed by SAHU appearing on the Zone Controller’s display). The setpoint of the Zone Controller will now automatically be used by the AHU Controller. If it is desired that the Supply Air setpoint is set higher or lower than the Zone Controller’s setpoint, the SPTR parameter may be used; this value will be added (or subtracted, if negative) to the Zone Controller’s setpoint and the result used as the Supply Air setpoint.


Accessing Configuration and Monitoring Parameters

Configuration Parameters are used to adjust settings from their factory defaults; Monitoring Parameters are used to monitor internal readings (such as temperature readings) during the Commissioning process.
The Parameters may be viewed, and in the case of Configuration Parameters, adjusted by one of two methods; Either by using a Zone Controller connected to the network, or by using the SeaChange Doorway Supervisor.

Using the Zone Controller:

a) The Zone Controller must be connected to the network and registered (see Commissioning Guide for further details).
b) Put the Zone Controller into Configuration Mode by depressing Select and Override buttons for 10 seconds, until the CNFG legend appears on the display.
c) Press Select button on the target device (in this case, the Boiler Controller).
d) Hold down Select button on the Zone Controller, and rotate the rotary knob:
clockwise to view Monitoring Parameters
anticlock to view Configuration Parameters
e) When desired Configuration Parameter appears, release Select, hold down Override and turn knob to adjust the parameter (some Monitoring Parameters cannot be adjusted).

Using SeaChange Doorway:

Data Points may be added to a Doorway page to access/adjust any Configuration or Monitoring Parameter. Graphs of certain Parameters are also available. The code used to access an AHU Controller is An,where n is the AHU number. The code for each parameter is shown in the adjacent tables.
Further details of how to set up Doorway pages may be found in the SeaChange Doorway Manual, or in the online help facility supplied with SeaChange Doorway.
The PC running SeaChange Doorway can be connected locally via a Serial Adaptor Module, or remotely using standard High-Speed Modems; all Parameters can thus be monitored and adjusted remotely.

System Housekeeping Functions

A SeaChange system needs certain system-wide functions to be provided by a single Controller, to ensure synchronisation, and to avoid conflicts. These functions are known as System Housekeeping Functions; examples of these are the management of time-of-day information, Outside Temperature and address allocation during registration. A full description of these functions may be found in the Boiler Controller Data Sheet. These functions may be provided by a Boiler Controller (if one is present) or by an Air Handling Unit Controller; either way, it is important that only one controller in each SeaChange system has System Housekeeping capability.
Refer to “Products and Order Codes” below to select the Controller, either to have System Housekeeping Functions, or not

Manual Override

Manual override allows the AHU to be forced ON or OFF independant of the Automatic Control requirement. This is particularly useful for proving plant and wiring during commissioning and to drive plant for maintenance purposes.
The override function allows the AHU to be driven into one of three states;
a) AHU running continuously under temperature control, controlling to its normal Occupied setpoint.
b) AHU running continuously with 100% heating; the temperature is NOT controlled in this mode.
c) AHU running continuously with 100% cooling; the temperature is NOT controlled in this mode.
When in Override mode, the module retains all its inherant time delays and safety functions. So for example, Sequence outputs will increase to bring in all the stages with the time delays between stages that have been set in the modules configuration parameters.
To put module into Override state:
  1. Press and hold the Override Button until the Green status LED flashes rapidly.
    Temperature indicator LED - green
    Unit goes into Occupied state, so AHU runs and controls to Occupied setpoint
  2. Press and release the Override Button.
    Temperature indicator LED - red
    Heating output turns on to 100%
    If Raise/Lower type output, valve will open fully
    Iif staged heating, all stages will be brought on under normal sequence timing control. Additional stages controlled by Cascade Modules or analogue valve controlled by Actuator Controller will also be driven 100%
  3. Press and release the Override Button.
    Temperature indicator LED - yellow
    Heating outputs close down under normal stroke or sequence timing
    Cooling output channel turns ON to 100%
    Cooling Valves or Staged outputs brought on as for Heating outputs
  4. Press and release Override Button
    Status LED stops flashing
    Module resumes Automatic Control
As the Override Mode does not time out, care should be exercised to ensure that the module is returned to Automatic mode.
Override mode can also be set and reset via Doorway where AUTO and OVRD are used to set the Automatic and Override modes.

Manual Hand Mode

The AHU can be forced to any fixed demand level between full Heating and full Cooling by setting a manual level on configuration variable C28 MANL (100 to -100%) and setting switch W5 HAND to 1. This function is controlled automatically by InSite override features.

Setting Stroke Times for Raise/Lower outputs and Minimum-on time for Staged outputs

To position a valve accurately using a Raise/Lower driver type relies on the AHU Controller having an accurate knowledge of the Stroke Time of the actuator. Similarly, for Staged (Sequenced) outputs, it is sometimes important to set Minimum-on time for each stage (to prevent excessive cycling of a DX Cooling battery, for example).
These times may be set for the Heating and Cooling outputs by using the parameters HPRD (for the heating output and CPRD (for the cooling output).

Options and Product Codes

Air Handling Unit Controller for Constant Supply Temperature Control

AHU / DIN / FRE / [battery types] / [housekeeping] / [variant]

Battery types

Option
Heater Battery
Cooling Battery
/ WW /
Raise / Lower Valve
Raise / Lower Valve
/ WE /
Raise / Lower Valve
2 Stage Electric
/ EW /
2 Stage Electric
Raise / Lower Valve
/ EE /
2 Stage Electric
2 Stage Electric

Housekeeping options

Option
Housekeeping
/ SH /
With System Housekeeping
/ NH /
With No System Housekeeping

Variant

Option
Variant
/ 001
Standard

 

 

smartkontrols Ltd
8 Horsted Square
Bell Lane Business Park
Uckfield East Sussex
TN22 1QG
phone 01825 769812
fax 01825 769813
e-mail sales@smartkontrols.co.uk
http:// www.smartkontrols.co.uk