Air Handing Unit Controller
FRE version for Constant Supply Temperature Control (SPTY
3&4)
RET version for Constant Return Temperature Control (SPTY 0&1, 6&7)
SUP version for Variable Supply Temperature Control (SPTY 2&5)
History
Latest released version is 4c3 (SH version)
Document last updated 03/11/2003
Software Release Document for: AHU/DIN/.../.../SH
PROM file header: AHUSM
Software Version | Release Date | Hardware Version | Notes |
4c3 |
03/11/03 |
0004/0001 C |
Corrections
|
4c2 | 28/04/2003 |
0004/0001 C |
Corrections
|
4c1 |
20/03/03 | 0004/0001 C |
New this issue-Start up interlock can now be monitored and overriden
|
4b7 |
17/09/01 | 0004/0001 C | increase maximum allowable return setpoint to 45 degC |
4b6 | 03/07/00 | 0004/0001 C | correct operation with alarm mode 2 or 3, STOP alarms operation only in alarm mode 3 |
4b5 | 06/12/99 | 0004/0001 C |
correct response to OCDS demand in SPTY 6 correct updating of MZON for InSite |
4b4 | 19/08/99 | 0004/0001 C |
correct reporting of supply setpoint when in local de-hum mode increase the range of setpoint adjustment from configuration varibles correct allocation of addresses to 'clone' sub modules |
4b3 | 08/06/99 | 0004/0001 C |
correct registration of HSC, CSC, ALM, SLT registration of subsequent modules could cause re-allocation of addresses correct operation of 'RETRY' after an AHU fail |
4b2 | 22/04/99 | 0004/0001 C | add transfer of Zone Temperature to Return Air temperature when registering
a zone in SPTY 2
allow registration of Slave AHU in all modes which control the Supply Air and therefore have a valid supply setpoint SPTY 0-4 inclusive |
4b1 | 16/04/99 | 0004/0001 C | add production test code
add support for Monitor Module as remote sensor processing |
4a1 | 26/01/99 | 0004/0001 C | add dual domain support
add decoding of De-Hum demand from Humidity controller |
3c6 | 20/10/98 | 0004/0001 C | correct retention of OCDS links when AHU is re-registered |
3d5 | 08/09/98 | 0004/0001 C | correct sending demand signals to heat/cool sources |
3d4 |
15/07/98 |
0004/0001 C | revise registration of Dessicant control modules
add support for OCDS correct registration of ZSL modules (again?) add registration of Alarm Monitor modules revise numbers of modules which can be registered to SM version |
3d3 | 23/06/98 | 0004/0001 C | add support for both 'old format' and 'new format' alarm messages, allows
the correct receipt of STOP alarms from pre 3c Boilers and Floor Controllers.
correct the decoding of alarm monitoring requests from Doorway |
3d2
code not issued use 3d3 |
04/06/98 | 0004/0001 C | correct registration of ZSL modules |
3d1
code not issued use 3d3 |
0004/0001 C | development issue, includes code for De Hum
reduce slope of gain change with error size to allow higher small signal gain and better overall stability |
|
3c9 | 23/04/98 | 0004/0001C | correct registration of ZSL controllers |
3c8 | 08/04/98 | 0004/0001C | correct registration of AHC cascade sub modules, error introduced in 3c7 code |
3c7 | 09/02/98 | 0004/0001C | all mods to 3c7 from standard AHU incorporated
SPC added to registration tables registration code changed to table driven version control routine tables modified to reduce response for large errors (control_array_2) |
3c4 | 16/01/98 | 0004/0001C | correct operation of mode SPTY 7 |
3c3 | 15/01/98 | 0004/0001C | correct range of SPTY, disable set_driver_loops when in manual mode |
3c2 | 22/12/97 | 0004/0001C | correct timing of run on |
3c1 | 16/12/97 | 0004/0001C | new supply setpoint operation add remote trim capability add manual facility |
3b5 | 04/11/97 | C | correct negative TrimSpaceSPincrease valid temperature range for valid PV check 2 to 100 |
3b4 | 16/11/97 | C | correct negative TrimSpaceSP |
3b3 | 18/11/97 | C | correct error in 'tempered air control' modify default loop constants |
3b2 | 13/11/97 | C | correct error in 'tempered air control' modify default loop constants |
3b1 | 13/11/97 | C | first 3b issue of SM version to Uckfield |
3ai | 24/10/97 | C |
Latest released version is 4c2 (NH version)
Document last updated 03/11/2003
Software Release Document for: AHU/DIN/.../.../NH
PROM file header: AHU
Software Version | Release Date | Hardware Version | Notes |
4c2 |
28/04/2003 |
0004/0001 C |
Corrections
|
4c1 |
20/03/03 | 0004/0001 C |
New this issue-Start up interlock can now be monitored and overriden
|
4b7 | 17/09/01 | 0004/0001C | increase maximum allowable return setpoint to 45 degC |
4b6 | 03/07/00 | 0004/0001 C | correct operation with alarm mode 2 or 3, STOP alarms operation only in alarm mode 3 |
4b5 | 06/12/99 | 0004/0001 C |
correct response to OCDS demand in SPTY 6 correct updating of MZON for InSite |
4b4 | 19/08/99 | 0004/0001 C |
correct reporting of supply setpoint when in local de-hum mode increase the range of setpoint adjustment from configuration varibles correct allocation of addresses to 'clone' sub modules |
4b3 | not issued | ||
4b2 | 22/04/99 | 0004/0001 C | add transfer of Zone Temperature to Return Air temperature when registering
a zone in SPTY 2
allow registration of Slave AHU in all modes which control the Supply Air and therefore have a valid supply setpoint SPTY 0-4 inclusive |
4b1 | 16/04/99 | 0004/0001 C | add production test code
add support for Monitor Module as remote sensor processing |
4a2 | 09/02/99 | 0004/0001 C | correct sending of supply setpoint to AHU slaves
correct operation of valve stroking |
4a1 | 26/01/99 | 0004/0001 C | add dual domain support
add decoding of De-Hum demand from Humidity controller |
3d7 | 09/12/98 | 0004/0001 C | correct manual setup of drivers using select button |
3d6 | 20/10/98 | 0004/0001 C | correct retention of OCDS links when AHU is re-registered |
3d5 | 08/09/98 | 0004/0001 C | correct sending demand signals to heat/cool sources |
3d4 | 15/07/98 | 0004/0001 C | revise registration of Dessicant control modules
add support for OCDS correct registration of ZSL modules (again?) add registration of Alarm Monitor modules revise numbers of modules which can be registered to SM version |
3d3 | 23/06/98 | 0004/0001 C | add support for both 'old format' and 'new format' alarm messages, allows
the correct receipt of STOP alarms from pre 3c Boilers and Floor Controllers.
correct the decoding of alarm monitoring requests from Doorway |
3d2 | 04/06/98 | 0004/0001 C | correct registration of ZSL modules |
3d1 | 0004/0001 C | development issue, includes code for De Hum
reduce slope of gain change with error size to allow higher small signal gain and better overall stability |
|
3c9 | 23/04/98 | 0004/0001 C | correct registration of ZSL controllers to AHU |
3c8 | 08/04/98 | 0004/0001 C | correct registration of AHC cascade sub modules, error introduced in 3c7 code |
3c7 | 09/02/98 | 0004/0001 C | add SPC to type for registration change to table based registration routines change to CONTROL_ARRAY_2 |
3c6 | 03/02/98 | 0004/0001 C | add FCU to slave types so heat/cool sources are set up in FCU |
3c5 | 27/01/98 | 0004/0001 C | cooling flag not being set correctly in modes sp_type 6&7
in manual cooling starting before heating closed down
frost protection didn't work in all modes degF mods made to config code |
3c4 | 16/01/98 | 0004/0001 C | correct operation of mode SPTY 7 |
3c3 | 15/01/98 | 0004/0001 C | correct range of SPTY |
3c2 | 22/12/97 | 0004/0001 C | correct timing of run on |
3c1 | 16/12/97 | 0004/0001 C | new supply setpoint operation add remote trim capability add manual facility |
3b5 | 04/11/97 | 0004/0001 C | increase valid temperature range for valid PV check 2 to 100 |
3b4 | 26/11/97 | 0004/0001 C | correct negative TrimSpaceSP |
3b3 | 18/11/97 | 0004/0001 C | reduce supply gain to 20 clear remote_fan_fail etc if no FCO's fitted |
3b2 | 13/11/97 | 0004/0001 C | correct error in 'tempered air control' modify default loop constants |
3b1 | 22/10/97 | 0004/0001 C | revised registration to go with Floor Controller |
3ai | 15/10/97 | 0004/0001 C | correct operation of 'error led' add retry delay, clears AHU_fail after set delay |
3ah |
09/10/97 | 0004/0001 C | correct SPTY 2 mode, don't use minimum demand to decide on heating/cooling set 'cooling' flag to get correct Doorway values add support for FCO using ahp_op for confirmation of fan state add support AHU_fail (Fan Fail) cleared with switch3 or override |
3ag |
09/09/97 |
0004/0001 C | correct install routine, setup nvs every time correct operation with PreHeater controller, re-vamp PreHeater interlocks |
3ag |
09/09/97 |
0004/0001 C | correct install routine, setup nvs every time correct operation with PreHeater controller, re-vamp PreHeater interlocks |
3af |
09/09/97 |
0004/0001 C | correct operation of STOP alarm |
3ae |
09/09/97 |
0004/0001 C | disable setting of warm_up and Cool_down, new boolean variables introduced but not yet being set needs changes to Zone Controller |