Air Handing Unit Controller |
|
Latest released version is 4c2Document last updated 03/11/2003 |
AHU / DIN / RET / .../ .../... |
Main FeaturesControls Supply & Extract Fans, Heating and Cooling Batteries
|
![]() |
Note if a Preheater module is registered to the AHU the AHU will automatically change to the interlocks appropriate to the Pre Heater
FANF |
Fan Failure (which would need a fan running status signal wired to the appropriate input) |
FLTF |
Filter Blocked (which would need a differential pressure switch installed
across the filter). |
ALRM = 0 |
Ignore alarms (inputs could be used for monitoring status of any volt-free contact) |
ALRM = 1 |
Report alarms FANF and FLTF, no control action |
ALRM = 2 |
Report alarms, shut down all outputs on receipt of STOP alarm |
ALRM = 3 |
Report alarms, shut down all outputs on STOP alarm or FANF alarm |
FANF |
Alarm if generated from a Fan Changeover Module registered to the AHU (if this feature is not required, the Changeover Modules ALRM parameter may be set to generate no alarms) |
FREZ |
Danger of Freezing, which is generated when the Supply Air Temperature drops below a limit set on parameter CUTS (default 4 degC). If this value is set to zero, this feature is disabled |
SPLF |
Supply Temperature Failed which is generated when the Supply Sensor reading is invalid (not used if SPTY set to 6 or 7, Return-only control) |
OUTF |
Outside Temperature Fail, which is generated when the AHU Controller is not receiving a valid Outside Temperature (either locally connected or via the network from another module).This alarm does not cause the AHU to shut down |
Input 13-14 |
VFC input or potentiometer |
INMD = 1 |
Disabling AHU from an External Contact |
INMD = 2 |
Enabling AHU from an External Contact |
|
Enabling AHU from an External Contact |
INMD = 1, 2 or 3 |
External Setpoint Trim Potentiometer |
INMD = 1 |
Setpoint Trim with external Disable Contact |
INMD = 2 or 3 |
Setpoint Trim with external Enable Contact |
Submodule Type |
Max |
Preheater Submodule |
1 |
Humidity Submodule |
1 |
T+Rh Networked Sensors |
3 |
Submodule Type |
Max |
Damper Submodule |
1 |
or |
|
Heat recovery Submodule |
1 |
Submodule Type |
Max |
Fan Changeover Submodules |
2 |
or |
|
Static Pressure Submodule |
2 |
Submodule Type |
Cascade Submodule |
or |
Actuator Submodule |
or |
Dessicant Wheel Controller |
Option |
Heater Battery |
Cooling Battery |
/ WW / |
Raise / Lower Valve |
Raise / Lower Valve |
/ WE / |
Raise / Lower Valve |
2 Stage Electric |
/ EW / |
2 Stage Electric |
Raise / Lower Valve |
/ EE / |
2 Stage Electric |
2 Stage Electric |
Option |
Housekeeping |
/ SH / |
With System Housekeeping |
/ NH / |
With No System Housekeeping |
Option |
Variant |
/ 001 |
Standard |