Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
C1 |
SPAH |
Occupied Setpoint |
Deg C |
20 |
10 - 45
|
C2 |
SPDB |
Setpoint Deadband |
Deg C |
1 |
0 to 10 |
C3 |
SPTR |
Setpoint Trim; is added to the Occupied Setpoint (C1) to produce the
working setpoint, used when setpoint is slaved from a Zone Controller
|
Deg C |
0 |
-10 to 10 |
C4 |
SPTY |
Setpoint Type; used to select mode of control :
FRE Type:-
3: Constant Supply Temp; setpoint = C1 / K1 .
4: Constant Supply Temp; setpoint slaved from a Zone Controller
RET Type:-
0: Constant Return Temp using Cascade (aka Reset) control; setpoint =
C1/K1
1: Constant Return Temp using Cascade (aka Reset) control; setpoint slaved
from a Zone Controller
6: Constant Return Temp only (no Cascade/Reset control); setpoint = C1/K1
7: Constant Return Temp only (no Cascade/Reset control); setpoint slaved
from a Zone Controller
SUP Type:-
2: Variable Supply Temp based on heat/cool demands from one or more Zones/Terminal
Units
5: Variable Supply Temp; supply setpoint slaved from another AHU |
- |
Depends on type |
0 to 7 |
C5 |
SPFR |
Frost Protection Setpoint; opens valves to 50% if OAT< SPFR |
Deg C |
10 |
0 to 20 |
C6 |
INMD |
Input Mode; decides influence of external Volt Free Contact
0: Normal operation, external signal ignored
1: Occupied is External AND normal occupation
(window contact or contact used to stop AHU)
2: Occupied is External OR normal occupation
(Occupancy extension switch for outside normal hours)
3: Occupation controlled by external signal only |
- |
0 |
0 to 3 |
C7 |
MAXS |
Maximum supply air setpoint |
Deg C |
30 |
2 to 70 |
C8 |
MINS |
Minimum supply air setpoint |
Deg C |
10 |
0 to 30 |
C9 |
CUTS |
Supply Air safety cutoff;
0: This feature inactive; AHU will not shut down
>0: If Supply Air falls below this value, AHU will shut down |
Deg C |
4 |
0 to 20 |
C10 |
NTCL |
Night Cooldown Setpoint; if Return Air sensor fitted, can be used
to pre-cool the building using free cooling at night:
0: Night Cooling disabled
>0: value used as Night Cooldown Setpoint |
Deg C |
0 |
0 to 25 |
C11 |
MIND |
Minimum Demand necessary to run the AHU; (SUP version only)
0: AHU will run if any Zone is in Occupation or Warm-Up
(used for plants that are supplying Fresh Air)
>0: AHU will only run if max Zone demand is higher than MIND
(used for plants not supplying Fresh Air)
Not used, set to 0 in this application (FRE and RET versions only) |
% |
0 |
0 to 10 |
C12 |
MRUN |
Minimum Run Time for AHU |
Mins |
5 |
0 to 20 |
C13 |
HPRD |
Heating Valve Stroke Time (for Wet Coils) or Minimum-On Time for
Electric Heater |
Secs/10 |
18 |
2 to 60 |
C14 |
CPRD |
Cooling Valve Stroke Time (for Wet Coils) or Minimum-On Time for Electric
Cooling stage |
Secs/10 |
18 |
2 to 60 |
C15 |
SFRT |
Supply First; used to ensure positive pressurisation of building:
0 : Extract Fan starts before Supply Fan
1 : Supply Fan starts before Extract Fan |
- |
1 |
0 to 1 |
C16 |
OCCO |
Occupancy Only; (FRE and RET versions only)
0 : AHU Runs in Warm-Up, Occupation and Fabric Protection
1: AHU Runs in Occupation only
Not used, set to 1in this application (SUP version only) |
- |
1 |
0 to 1 |
C17 |
RTRY |
Retry Delay after fan failure has shut down AHU (before AHU restarts) |
Hours |
0 |
0 to 24 |
C18 |
HTSC |
Heat Source; defines source of heat for Heater Battery:
0: for Electric Battery or non-SeaChange Boiler plant
1-20: to indicate source of heat (Boiler, Secondary Circuit
Controller etc.), set automatically during registration |
- |
1 |
0 to 20 |
C19 |
CLSC |
Cool Source;
0: for Electric Battery or non-SeaChange cooling plant,
1-20: to indicate source of cooling (Chiller etc.) |
- |
0 |
0 to 20 |
C20 |
OCDS |
Occupancy Destination; Occupancy demand signal pointer
points to other AHUs or
other controllers:
0: feature is inactive
51-100 : will send Occupancy Status to AHU 1 - 50
(for AHU 1, set to 51, AHU2, set to 52 etc.)
101-200: will send Occupancy Status to Zones 1-100
(for Zone 1, set to 101, Zone 2, set to 102 etc.) |
- |
0 |
0 to 255 |
C21 |
MXCT |
Maximum CT demand to Heat Source |
Deg C |
70 |
20 to 100 |
C22 |
MNCT |
Minimum CT demand to Heat Source |
Deg C |
50 |
20 to 100 |
C23 |
HTSG |
Number of Heating Stages (not used if wet heating battery) |
- |
2 |
1 to 5 |
C24 |
CSTG |
Number of Cooling Stages (not used if wet cooling battery) |
- |
2 |
1 to 5 |
C25 |
HCOK |
Heat/Cool OK;
1: allows heating and cooling to run simultaneously for closer
control when using staged DX battery with modulating
heating coil (not to be set when using DeHum control)
0: simultaneous heating and cooling not allowed (unless
DeHum control is enabled using RHSP) |
- |
0 |
0 to 1 |
C26 |
ALRM |
Alarm Mode:
0: Ignore Alarms
1: Report Alarms to supervisor
(Fan Failure, Filter Blocked, Danger of Freezing, Outside Temperature
sensor fault)
2: Report Alarms, shut down all outputs on STOP Alarm
3: as 2) above, and shut down TP or Staged outputs on Fan Failure |
- |
0 |
0 to 3 |
C27 |
ALST |
Alarm State: State of inputs for Fan Failure/Filter Blocked:
0: Contact Opening generates alarm
1: Contact Closure generates alarm |
- |
0 |
0 to 1 |
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
I1 (C30) |
INPA |
Input A (fan fail) input status (Contact Closure = 1) |
- |
- |
0 to 1 |
I2 (C31) |
INPB |
Input B (filter blocked) input status (Contact Closure = 1) |
- |
- |
0 to 1 |
I3 (C32) |
RLYA |
Heating relay 1 status |
- |
- |
0 to 1 |
I4 (C33) |
RLYB |
Heating relay 2 status |
- |
- |
0 to 1 |
I5 (C34) |
RLYC |
Cooling relay 1 status |
- |
- |
0 to 1 |
I6 (C35) |
RLYD |
Cooling relay 2 status |
- |
- |
0 to 1 |
I7 (C36) |
SFAN |
Supply Fan status |
- |
- |
0 to 1 |
I8 (C37) |
EFAN |
Extract Fan Status |
- |
- |
0 to 1 |
W1 (C38) |
AUTO |
Automatic/Manual Status |
- |
- |
0 to 1 |
W2 (C39) |
OVRD |
Override |
- |
- |
0 to 1 |
W3 (C40) |
RSET |
Reset AHU after Fan failure shutdown (auto resetting after use) |
- |
- |
0 to 1 |
W7 (C44) |
SERV |
Remote initiation of service pin message (SeaChange diagnostic use) |
- |
- |
0 to 1 |
W8 (C45) |
CGST |
Configuration mode status |
- |
- |
0 to 1 |
|
|
W1 and W2 used together with Doorway Auto/Manual dialog box |
|
|
|
S1* (C50) |
SPLA |
Supply Air Temperature |
Deg C |
- |
0 to 35 |
S2* (C51) |
RTNA |
Return Air Temperature |
Deg C |
- |
0 to 35 |
S3* (C52) |
HCOP |
Heat / Cool output to Batteries |
% |
- |
-100 to 100 |
S4 (C53) |
INCL |
Inter-coil temperature (not used in this application) |
Deg C |
- |
0 to 50 |
S5 (C54) |
OUTS |
Outside Temperature (locally wired or via network) |
Deg C |
- |
-30 to 35 |
S6 (C55) |
SPSL |
Current Supply temperature Setpoint |
Deg C |
- |
5 to 30 |
S7 (C56) |
SPRT |
Current Return Temperature Setpoint |
Deg C |
- |
5 to 30 |
S8 (C57) |
SPLH |
Supply Air Humidity |
% |
- |
0 to100 |
S9 (C58) |
RTNH |
Return Air Humidity |
% |
- |
0 to100 |
S10.(C59) |
OUTH |
Outside Air Humidity |
% |
- |
0 to100 |
K1 (C60) |
SPOC |
Occupied Setpoint |
Deg C |
20 |
2 to 45
|
K2 (C61) |
SPFR |
Frost Protection Setpoint |
Deg C |
0 |
2 to 35
|
K3 (C62) |
SPSV |
Supervised Setpoint from Zone Controller (overrides C60) |
Deg C |
0 |
0 - 50 |
K4 (C63) |
SPTR |
Setpoint Trim; added to C62 to form current setpoint |
Deg C |
0 |
-10 to 10 |
K5 (C64) |
RHSP |
RH Setpoint for Return Air Humidity;
0: Disables Dehumidification
10 - 100: forms setpoint for Dehum control |
% |
0 |
10 to 100 |
K6 (C65) |
RHDB |
RH deadband for Dehumidification |
% |
5 |
2 to 50 |
|
|
Engineering Parameters; only accessible via Doorway and InSite |
|
|
|
C90 |
NOAL |
No Alarms; all alarms cleared when set to 1 |
- |
- |
0 to 1 |
C91 |
FANF |
Fan Failure Alarm current (when set to 1) |
- |
- |
0 to 1 |
C92 |
FLTF |
Filter Blocked Alarm current (when set to 1) |
- |
- |
0 to 1 |
C93 |
FREZ |
Danger of Freezing Alarm current (when set to 1) |
- |
- |
0 to 1 |
C94 |
OUTF |
No Outside Temperature Available Alarm current (when set to 1) |
- |
- |
0 to 1 |
C95 |
SUPF |
Supply Sensor Failed (when set to 1) |
- |
- |
0 to 1 |
C96 |
STOP |
Controller shut down due to System Stop Alarm received (when set to
1) |
- |
- |
0 to 1 |
|
|
These parameters are factory set; refer to SeaChange for special applications
before changing these settings |
|
|
|
C154 |
HRMN |
Heating Driver input rescale minimum |
% |
0 |
0 to 100 |
C155 |
HRMX |
Heating Driver input rescale maximum |
% |
100 |
0 to 100 |
C156 |
CRMN |
Cooling Driver input rescale minimum |
% |
0 |
0 to 100 |
C157 |
CRMX |
Cooling Driver input rescale maximum |
% |
100 |
0 to 100 |
|
|
* 24 hour plots available for these values by default |
|
|
|
|
|