Actuator Submodule for Natural Ventilation Window Control
with 3 x Triac Outputs (3T version)
with 3 x Analogue Outputs (AOP version)
Feature Notes |
Configuration Tables | Data Sheet Not yet Released |
Wiring | History |
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
C1 |
MNFA |
Minimum Fresh Air |
% |
10 |
0 to 100 |
C2 |
NOWS |
Minimum Wind Speed for Wind Direction Indication to be valid |
m/sec |
1 |
0 to 25 |
C3 |
MXWS |
Maximum Wind Speed (Window Shut) |
m/sec |
0 |
0 to 25 |
C4 |
MNWS |
Minimum Wind Speed (Window open) |
m/sec |
0 |
0 to 15 |
C5 |
WNWD |
Window Direction |
Degrees |
0 |
0 to 360 |
C6 |
DDEV |
Wind Direction Deviation, the deviation in Wind Direction from dead down wind when the Window will be forced shut. |
Degrees |
0 |
0 to 360 |
C7 |
INMD |
Input Mode use of terminals 'input a' : |
- |
0 |
0 to 5 |
C8 |
MIND |
Minimum demand, used for defining Occupancy switching
for the Fan/Pump: |
- |
4 |
0 to 10 |
C9 |
OCCO |
When set controller will only run during the occupied period |
- |
0 |
0 to 1 |
C10 |
HPRD |
Heating valve period or minimum on time |
secs/10 |
Depends on type |
1 to 60 |
C11 |
HDLY |
Interlock delay: |
mins |
0 |
-30 to 30 |
C12 |
CPRD |
Cooling valve period or minimum on time |
secs/10 |
Depends on type |
1 to 60 |
C13 |
CDLY |
Interlock delay: |
mins |
0 |
-30 to 30 |
C14 |
FPRD |
Fan period, minimum time to change fan speed steps (6R + 7R version only) |
secs/10 |
12 |
1 to 60 |
C15 |
CALC |
Calculation Mode: |
- |
0 |
0 to 1 |
C16 |
MANL |
Manual level , from Doorway |
% |
0 |
-100 to 100 |
C17 |
CMDE |
Control Mode: |
- |
0 |
0 to 2 |
C18 |
ALRM |
Alarm mode: |
- |
0 |
0 to 4 |
C19 |
ALST |
Sets alarm state |
- |
0 |
0 to 1 |
C20 |
MXVA |
Maximum Voltage output a (for AOP types only) |
V |
10 |
0 to 10 |
C21 |
MNVA |
Minimum Voltage output a (for AOP types only) |
V |
0 |
0 to 10 |
C22 |
MXVB |
Maximum Voltage output b (for AOP types only) |
V |
10 |
0 to 10 |
C23 |
MNVB |
Minimum Voltage output b (for AOP types only) |
V |
0 |
0 to 10 |
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
I1 (C30) |
FRST |
Frost Protection Mode (SPNO violated) |
- |
- |
0 to 1 |
I2 (C31) |
OCCD |
Occupied |
- |
- |
0 to 1 |
I3 (C32) |
WMUP |
Not used in this version |
- |
- |
0 to 1 |
I4 (C33) |
EXIP |
External Input State |
- |
- |
0 to 1 |
I5 (C34) |
COOL |
Cooling mode |
- |
- |
0 to 1 |
I6 (C35) |
RLYA |
Triac A Status (3T versions only) |
- |
- |
0 to 1 |
I7 (C36) |
RLYB |
Triac B Status (3T versions only) |
- |
- |
0 to 1 |
I8 (C37) |
RLYC |
Triac C Status (3T versions only) |
- |
- |
0 to 1 |
W1 (C38) |
AUTO |
Automatic/Manual Status |
- |
- |
0 to 1 |
W2 (C39) |
OVRD |
Override |
- |
- |
0 to 1 |
W5 (C42) |
HAND |
Manual Hand; use with MANL to set output level |
- |
0 |
0 to 1 |
W6 (C43) |
POT |
Selects whether the board mounted potentiometer option is fitted or not |
- |
0 |
0 to 1 |
W7 (C44) |
SERV |
Service Pin Msg (to Doorway +InSite, self resetting) |
- |
- |
0 to 1 |
S1* (C50) |
TEMP |
Measured temperature |
Deg C |
- |
0 to 95 |
S2* (C51) |
HCOP |
Heat cool output to drivers (cooling negative) |
% |
- |
-100 to 100 |
S3 (C52) |
REQD |
Current setpoint |
Deg C |
- |
5 to 90 |
S4 (C53) |
HDMD |
Heat demand from loop or from Zone Controller |
% |
- |
0 to 100 |
S5 (C54) |
CDMD |
Cool demand from loop or from Zone Controller |
% |
- |
0 to 100 |
S6 (C55) |
FDMD |
Fan demand |
% |
- |
0 to 100 |
S7 (C56) |
OSFR |
Outside Temperature Override Factor |
% |
- |
0 to 100 |
S8 (C57) |
WSFR |
Wind Speed Override Factor |
% |
- |
0 to 100 |
S9 (C58) |
WDFR |
Wind Direction Override Factor |
% |
- |
0 to 100 |
S10 (C59) |
FACT |
Overall Override Factor |
% |
- |
0 to 100 |
K1 (C60) |
MXWS |
Maximum Wind Speed, speed at which Window is Overriden shut |
m/sec |
0 |
0 to 25 |
K2 (C61) |
MNWS |
Minimum Wind Speed, speed at which window is still allowed to be 100% open |
m/sec |
0 |
0 to 25 |
K3 (C62) |
Reserved for supervised setpoint from master controller |
- |
- |
- |
|
K4 (C63) |
WNWD |
Window Direction, compass bearing looking directly out of the window |
Degrees |
0 |
0 to 360 |
K5 (C64) |
DDEV |
Wind Direction deviation, deviation from dead down wind where window must be shut |
Degrees |
0 |
0 to 160 |
K6 (C65) |
NOWS |
No Wind, below this Wind Speed the Wind Direction is ignored |
m/sec |
1 |
0 to 25 |
K7 (C66) |
MNFA |
Minimum Fresh Air setting for the Window opening |
% |
10 |
0 to 100 |
K8 (C67) |
OUTT |
Outside Temperature Top limit, at which the window can be fully open |
Deg C |
0 |
0 to 25 |
K9 (C68) |
OUTB |
Outside Temperature Bottom limit, at or below which the window will be shut |
Deg C |
0 |
0 to 25 |
Engineering Parameters; only accessible via Doorway and InSite |
|||||
C180 |
DI A |
Input 3-4 digital status |
- |
- |
0 or 1 |
C181 |
DI B |
Input 5-6 digital status |
- |
- |
0 or 1 |
* 24 hour plots available for these values by default |
|||||
Plotting interval and plotted variable changeable via Doorway or InSite |