Actuator Submodule for Natural Ventilation Window Control
with 3 x Triac Outputs (3T version)
with 3 x Analogue Outputs (AOP version)

Feature
Notes
Configuration Tables Data Sheet
Not yet Released
Wiring History

Configuration Tables

Latest released version is 4c2 (beta)
Document last updated 24/01/2002
Recent features not included on Data sheet are in
RED text

Configuration Parameters

Doorway / InSite Code

Label

Description

Units

Default Value

Range

C1
MNFA
Minimum Fresh Air
%
10
0 to 100
C2
NOWS
Minimum Wind Speed for Wind Direction Indication to be valid
m/sec
1
0 to 25
C3
MXWS
Maximum Wind Speed (Window Shut)
m/sec
0
0 to 25
C4
MNWS
Minimum Wind Speed (Window open)
m/sec
0
0 to 15
C5
WNWD
Window Direction
Degrees
0
0 to 360
C6
DDEV
Wind Direction Deviation, the deviation in Wind Direction from dead down wind when the Window will be forced shut.
Degrees
0
0 to 360
C7
INMD
Input Mode use of terminals 'input a' :
0: additional temperature input for max,min,average use SACT
1: external input (short = occupied) AND internal occ
2: external input OR internal occ
3: external input signal only
4: Alarm input
5: Alarm if input does not match Pump/Fan State
Note modes 2 & 3 are only suitable for use with Actuator in Control Mode 2, small plant driver mode.
-
0
0 to 5
C8
MIND
Minimum demand, used for defining Occupancy switching for the Fan/Pump:
0: will run pump/fan throughout Occupancy
>0: will require minimum demand level before pump/fan will run
-
4
0 to 10
C9
OCCO
When set controller will only run during the occupied period
-
0
0 to 1
C10
HPRD
Heating valve period or minimum on time
secs/10
Depends on type
1 to 60
C11
HDLY
Interlock delay:
negative value delays fan (or pump) after heating starts
positive value cause run on of fan after heating shuts down
mins
0
-30 to 30
C12
CPRD
Cooling valve period or minimum on time
secs/10
Depends on type
1 to 60
C13
CDLY
Interlock delay:
negative value delays fan (or pump) after cooling starts
positive value cause run on of fan after cooling shuts down
mins
0
-30 to 30
C14
FPRD
Fan period, minimum time to change fan speed steps (6R + 7R version only)
secs/10
12
1 to 60
C15
CALC
Calculation Mode:
0: Multiply the Factors
1: use Loweset Factor
-
0
0 to 1
C16
MANL
Manual level , from Doorway
%
0
-100 to 100
C17
CMDE
Control Mode:
0: driver only inputs used for monitoring or alarm
1: closed loop control, input b primary sensor
2: on/off control, heating or cooling demand will be 100% when controller is 'occupied'. Sensor inputs used for monitoring or alarm functions
-
0
0 to 2
C18
ALRM
Alarm mode:
0: ignore alarms
1: report alarms
2: report alarms, shut down all outputs on local alarm
3: report alarms, shut down all outputs on STOP alarm or local alarm
4: report alarms, shut down all outputs on STOP alarm only
-
0
0 to 4
C19
ALST
Sets alarm state
-
0
0 to 1
C20
MXVA
Maximum Voltage output a (for AOP types only)
V
10
0 to 10
C21
MNVA
Minimum Voltage output a (for AOP types only)
V
0
0 to 10
C22
MXVB
Maximum Voltage output b (for AOP types only)
V
10
0 to 10
C23
MNVB
Minimum Voltage output b (for AOP types only)
V
0
0 to 10

 

Monitoring Parameters

Doorway / InSite Code

Label

Description

Units

Default Value

Range

I1 (C30)
FRST
Frost Protection Mode (SPNO violated)
-
-
0 to 1
I2 (C31)
OCCD
Occupied
-
-
0 to 1
I3 (C32)
WMUP
Not used in this version
-
-
0 to 1
I4 (C33)
EXIP
External Input State
-
-
0 to 1
I5 (C34)
COOL
Cooling mode
-
-
0 to 1
I6 (C35)
RLYA
Triac A Status (3T versions only)
-
-
0 to 1
I7 (C36)
RLYB
Triac B Status (3T versions only)
-
-
0 to 1
I8 (C37)
RLYC
Triac C Status (3T versions only)
-
-
0 to 1
W1 (C38)
AUTO
Automatic/Manual Status
-
-
0 to 1
W2 (C39)
OVRD
Override
-
-
0 to 1
W5 (C42)
HAND
Manual Hand; use with MANL to set output level
-
0
0 to 1
W6 (C43)
POT
Selects whether the board mounted potentiometer option is fitted or not
-
0
0 to 1
W7 (C44)
SERV
Service Pin Msg (to Doorway +InSite, self resetting)
-
-
0 to 1
S1* (C50)
TEMP
Measured temperature
Deg C
-
0 to 95
S2* (C51)
HCOP
Heat cool output to drivers (cooling negative)
%
-
-100 to 100
S3 (C52)
REQD
Current setpoint
Deg C
-
5 to 90
S4 (C53)
HDMD
Heat demand from loop or from Zone Controller
%
-
0 to 100
S5 (C54)
CDMD
Cool demand from loop or from Zone Controller
%
-
0 to 100
S6 (C55)
FDMD
Fan demand
%
-
0 to 100
S7 (C56)
OSFR
Outside Temperature Override Factor
%
-
0 to 100
S8 (C57)
WSFR
Wind Speed Override Factor
%
-
0 to 100
S9 (C58)
WDFR
Wind Direction Override Factor
%
-
0 to 100
S10 (C59)
FACT
Overall Override Factor
%
-
0 to 100
K1 (C60)
MXWS
Maximum Wind Speed, speed at which Window is Overriden shut
m/sec
0
0 to 25
K2 (C61)
MNWS
Minimum Wind Speed, speed at which window is still allowed to be 100% open
m/sec
0
0 to 25
K3 (C62)
 
Reserved for supervised setpoint from master controller
-
-
-
K4 (C63)
WNWD
Window Direction, compass bearing looking directly out of the window
Degrees
0
0 to 360
K5 (C64)
DDEV
Wind Direction deviation, deviation from dead down wind where window must be shut
Degrees
0
0 to 160
K6 (C65)
NOWS
No Wind, below this Wind Speed the Wind Direction is ignored
m/sec
1
0 to 25
K7 (C66)
MNFA
Minimum Fresh Air setting for the Window opening
%
10
0 to 100
K8 (C67)
OUTT
Outside Temperature Top limit, at which the window can be fully open
Deg C
0
0 to 25
K9 (C68)
OUTB
Outside Temperature Bottom limit, at or below which the window will be shut
Deg C
0
0 to 25
 
 
Engineering Parameters; only accessible via Doorway and InSite
 
 
 
C180
DI A
Input 3-4 digital status
-
-
0 or 1
C181
DI B
Input 5-6 digital status
-
-
0 or 1
 
 
* 24 hour plots available for these values by default
 
 
 
 
 
Plotting interval and plotted variable changeable via Doorway or InSite
 
 
 