Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
C1 |
ALRM |
Alarm Mode
0: Ignore alarms
1: Report all alarms to Doorway/InSite,
2: Report all alarms, shut down on STOP alarm, send special STOP alarm
to boiler on DPMF alarm |
- |
0 |
0 to 2 |
C2 |
ALST |
Alarm report sense
0: Alarm if input = 0 (contact open), pump running if input = 1 (closed)
1: Alarm if input = 1 (contact closed), pump running if input = 0 (open) |
- |
0 |
0 to 1 |
C3 |
FMD |
Failure Mode
1: Both pumps remain enabled
2: Last pump remains enabled
3: Both pumps disabled
|
- |
2 |
1 to 3 |
C4 |
DLAY |
Delay to wait for proof of flow |
Secs |
10 |
1 to 250 |
C5 |
MXHR |
Maximum hours run before duty pump changeover |
Hrs |
24 |
1 to 200 |
C6 |
MNON |
Minimum on time |
Mins |
5 |
0 to 200 |
C7 |
MXDY |
Maximum days off time for pump exercise |
Days |
7 |
0 to 10 |
C8 |
NPMP |
Number of pumps controlled |
- |
2 |
1 to 2 |
C9 |
TYPE |
Output type (for SeaChange use only) |
- |
- |
1 to 12
|
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
I1 (C30) |
FL A |
Flow status pump A |
- |
- |
0 to 1 |
I2 (C31) |
FL B |
Flow status pump B |
- |
- |
0 to 1 |
I3 (C32) |
EN A |
Do not adjust (for smartkontrols use only)
|
- |
- |
- |
I4 (C33) |
EN B |
Do not adjust (for smartkontrols use only)
|
- |
- |
- |
I5 (C34) |
FAIL |
Single or Dual Pump Failure |
- |
- |
0 to 1 |
I6 (C35) |
PMPA |
Triac output 1 status Pump A |
- |
- |
0 to 1 |
I7 (C36) |
PMPB |
Triac output 2 status Pump B |
- |
- |
0 to 1 |
I8 (C37) |
ALRS |
Triac output spare status Alarm Sounder |
- |
- |
0 to 1 |
W1 (C38) |
AUTO |
Automatic/Manual Status |
- |
- |
0 to 1 |
W2 (C39) |
OVRD |
Override |
- |
- |
0 to 1 |
W3 (C40) |
RSTA |
Reset hours run pump A |
- |
- |
0 to 1 |
W4 (C41) |
RSTB |
Reset hours run pump B |
- |
- |
0 to 1 |
W5 (C42) |
RNON |
Enable pump run on |
- |
1 |
0 to 1 |
W6 (C43) |
ACLR |
Automatically clear alarms |
- |
1 |
0 to 1 |
W7 (C44) |
SERV |
Service Pin Message (to Doorway and InSite, self resetting) |
- |
- |
0 to 1 |
S1* (C50) |
HRSA |
Hours run pump A |
Hrs |
- |
- |
S2* (C51) |
HRSB |
Hours run pump B |
Hrs |
- |
- |
S3 (C52) |
MXDM |
Control demand from parent module |
% |
- |
-100 to 100 |
|
|
Engineering Parameters; only accessible via Doorway and InSite |
|
|
|
C90 |
NOAL |
No Alarms; all alarms cleared when set to 1 |
- |
- |
0 or 1 |
C91 |
FLFA |
Flow Failed pump A (when set to 1) |
- |
- |
0 or 1 |
C92 |
FLFB |
Flow Failed pump B (when set to 1) |
- |
- |
0 or 1 |
C93 |
DPMF |
Dual Pump Failure (when set to 1) |
- |
- |
0 or 1 |
C94 |
STOP |
STOP alarm received (when set to 1) |
- |
- |
0 or 1 |
|
|
* 24 hour plots available for these values by default |
|
|
|
|
|
Plotting interval and plotted variable changeable via Doorway or InSite |
|
|
|