The VAV controllers are registered in exactly the same way as Fan Coil controllers. For
the time being they are considered to be a special type of Fan Coil controller.
In order to talk to VAV controllers with Doorway the SLT
needs to be upgraded to issue 3a5 or later. It is possible to use the [#] addressing
method (last service pin pressed) if the SLT available is not 3a.
Zone controllers used with VAV's must be ZON3b1 or later running on latest large
memory hardware, earlier versions will not recognise FCU controllers for registration.
The registration procedure for all modes is the same as for
registering Slave Zones to a Master Zone. Put the Master Zone Controller into config then
register each VAV in turn. The zone will report SLVE 2 (for VAV 2, 3 for VAV 3 etc.) The
Master Zone will be set automatically to SPMD 3 when a Fan Coil is slaved to it, to
allow the Fan Coils to receive the Setpoint and Occupation information.
The VAVs are put into the same group as the Master Zone, any number of VAVs can be linked
to a single Master.
The Return air sensor must be fitted and the SPTY must be set
to 0 or 1.
Note the Occupation and Setpoint data is only updated every minute so be patient when
commissioning, operationally this is OK because the change will normally come from the
Optimum start routines which are checked every minute. If the setpoint is changed on the
Master Zone (with the knob) the new setpoint is sent straightaway.
Occupancy control SPTY 0
The VAV can be left to control from it's own setpoint but Occupancy is controlled from
a single Zone controller by registering the VAV to the Zone. The VAV will control to a
constant Return air setpoint regardless of the heating or cooling demands from the Zone.
Setpoint supervision SPTY 1
This is the default mode of operation. The VAV(s) will control the return air (during
optimum start and occupation) to the setpoint defined by the Zone Controller.
The VAV Return Air setpoints can be individually adjusted using the SPTR setpoint trim
config variable to adjust for local conditions.
The Return air sensor is not fitted. The mode must be set
to (SPTY) 2.
Box volume slaved to Zone or master VAV heat and cool demands SPTY 2
The Heat or Cool demand from the Zone will be used to directly control the output
stages, this mode is also used to 'slave a VAV' to another VAV (or FCU).
If the controller is regulating the supply of air from a plenum with a single damper (RiverMill House) the temperature of this plenham can be reported to the controller and the damper prevented from opening if the plenham temperature is not suitable for the control mode currently required. For example if the plenham is hot but the controller is being asked to cool the room. The Plenham temperature is compared with the current space setpoint setting (SPFC+/-SPDB/2) and if the temperature is unsuitable the damper is maintained at the minimum volume (MINV fresh air) setting. This mode can be selected by setting the Re Heat REHT config variable to -1.
The supply sensor can be replaced by a switch which when made
will force the FCU to Occupied. On FCF or BLR boards the external connection is made to
'input a', thus retaining the use of the supply sensor.
This is achieved by adding an extra config variable input mode INMD. The following values
are supported.
0 normal operation input measures Off Coil temperature
1 Occupied is External AND normal occupation (window contact)
2 Occupied is External OR normal occupation (outside normal hours)
3 Occupation controlled by external signal only
4 Input used as an external alarm, alarm state defined by ALST
If the switch is wired in series with a 10K resistor and a 10K potentiometer Occupied/ Non
occupied plus a 5 degree trim (operational only whilst occupied) is possible. The trim is
slightly non linear (the applied resistance is affected by the parallel resistance on the
board which helps linearise the thermistor when fitted, mechanical centre position of the
pot gives -0.7C) The zero point can be adjusted to give the correct (0 trim) by backing
off any error using the software trim SPTR. Suggest pot is marked Hotter/Colder or +/- !
A resistance between 0 and 20K ohm will be considered to be Occupied, non Occupied is
guaranteed for resistance values above 100K. The voltage generated by the pot will be
converted to a setpoint Trim only for control modes SPTY 0 or 1
This allows one 'master VAV (or FCU)' to provide the Return
Air control for a large space and to send its HeatOp and CoolOp outputs to one or more
'Slave FCU's'
The Master must be operating in mode SPTY 0 or 1, i.e. must be measuring and controlling
Return temperature.
The 'Slave' must be operating in mode SPTY 2. The registration process involves putting
the master into config mode and then pressing the registration button on all the 'Slave
FCU's'.
The Slaves are put into the same group as the Master VAV, any number of Slaves can be
linked to a single Master.
If a Slave VAV is subsequently linked to a Zone Controller the link to the Master VAV will
automatically be broken.
Any VAV can act as a source of setpoint (and occupancy)
information for a group of VAVs which are all controlling to their local Return Air
sensor.
This would be useful when one VAV has a local Trim Pot (or
Occupancy switch) and the same setpoint is required on other VAVs feeding the same area of
the building.
Put the 'master' into config and 'slave' the other VAVs. The Slave VAVs will receive the
mid point setpoint (C1 SPFC plus any external Trim) of the Master, local additional
trim can be applied to each VAV using SPTR. To maintain balance amongst the
VAVs the setpoint deadband SPDB should be the same in all units within the group.
In this way a Zone Controller can provide Setpoint and/or Occupancy information to a
'master VAV' within each separate space, these VAVs can have local User Adjustments (for
the cheapskates who won't buy Zone Controllers) or Occupancy overrides, these modified
conditions are then sent to all VAVs within the area.
There are no limits on the number of VAVs which can be slaved to a 'master VAV'. A Slave
VAV can also be a 'master' to a further group of VAVs, although this only makes sense if
these VAVs are operating in mode SPTY 2;either Off Coil only control or in Driver only
mode (no sensors fitted).
The controller will automatically control fan speed, if the
multi-speed fan driver is used. If either the heating or cooling demand is greater than
90% for a period longer than FPRD (seconds/10 to match other periods) then the fan speed
will be incremented up to the next speed. If both the heating and cooling demand is less
than 10% then the Fan Speed is reduced after the same delay time. While occupied the
controller will maintain a minimum of Fan Speed 1.
Provision is made for the fan speed to be controlled from a network variable
(nviFanSpeed), from a (hotel style) zone controller for example, if this network variable
is non zero then this will override the automatic fan speed control.
The FCU controller supports sensor fail SENF alarm, this is raised if
the Return Air sensor fails and the FCU is in a mode which requires the Return Air
temperature. The Input Mode can also be set up to generate an alarm for either a short or
open circuit on terminals 'temp a', see later.
Alarm mode and Alarm State config variables have been added to the config variable list.
ALMD | action |
0 | alarms ignored |
1 | alarms reported no other action |
2 | control output set to zero on alarm |
3 | STOP alarm recognised, control set to zero |
Alarm State determines which input state 0 or 1 is considered to be the alarm condition
when using external input for the alarm as set by INMD.
code | Hardware | Part Number | |
FCUAV3d1 | ACT-DIN-AOP | 0016/0003 issue E3 | 512 prom |
Secondary Supported Hardware (special order) |
|||
code | Hardware | Part Number | |
FCUDV3d1 | ACT-DIN-RLY | 0006/0001 issue J | 512 prom |
ACT-DIN-TOP | 0018/0001 issue E5 | 512 prom | |
FCT-DIN-RLY | 0020/0001 issue E4 | 512 prom | |
FCUFV3d1 | FCU-DIN-7R | 0023/0001 issue A | 512 prom address swapped |
FCUBV3d1 | BLR-DIN-RLY | 0004/0002 issue C5 | 512 prom address swapped |
This controller uses the universal output driver version 3d. which allows a range of output possibilities, although the VAV controller is primariliy designed to run on an AOP board other hardware options are possible.
The controller defaults to two analogue outputs, channel one for heating and channel two for box volume. The actual voltage levels which represent 0 and 100% can be set using MXVA, MNVA, MXVB, MNVB.
The maximum and minimum Box volumes can be set using MAXV and MINV.
If the VAV needs to control a re-heater when in heating mode, this is activated by
setting the config variable REHT to a value in the range 1 to 99%. The value set
determines the maximum box volume when in heating, this allows the heating mode to be more
energy efficient by heating a smaller volume of cold air. When using the Re Heat function
the reheater is connected to the Heating output HTYP and the Box volume control is
connected to the cooling output. Cooling operates by varing the air volume between minimum
volume and maximum volume, heating varies the heating output from 0 to 100% and the volume
output from minimum volume to the re heat volume REHT.
Interlocks
These have been changed to a new more flexible approach. A
single parameter for each driver type is provided which sets up the on delay or run on
time for the fan or pump.
HDLY
Typically negative values will be used for wet batteries to
provide start up protection against frost and positive (run on-) values would be used with
electric heating batteries.
The same features are available for cooling using CDLY.
The selection of OCC or OSS is now made by setting OCCO to
1 on controllers where the control is only required when the building is in occupation.
The default is for control during OSS and OCC.
This is defined with a config parameter FRPT and it defines the controllers action when
it receives a 'frost alarm' from the boiler controller.
FRPT | action |
0 | no action (default) |
1 | heating output to 50% |
2 | heating output to 50% and pump/fan enabled |
VAV Plots
There are three plots setup as normal on the first three
'sensors'.
Plot 1 Air Flow 0-100%
Plot 2 Return Air temperature
Plot 3 Heat/cool output -100 to +100 (negative for cooling)
The plot routine has been enhanced and the plotting period is now selectable
see configurable plots for details.
Will support registration of up to 8 Acuators, Acuator
Drivers, Pump ChangeOvers just like a regular Zone. This is not supported in version 3ax
0006 issue D boards due to lake of memory.
VAV Controllers are addressed with [Zn] where n is the VAV
Zone number 1-200. [Fn] is also supported.
Sub modules are addressed as follows
Actuators [Z1Am] m=1 to 8
Item codes follow the normal conventions