Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
C1 |
SPFC |
Occupied room temperature setpoint |
Deg C |
20 |
10 to 35 |
C2 |
SPDB |
Setpoint Deadband |
Deg C |
1 |
0 to 10 |
C3 |
SPTR |
Setpoint Trim |
Deg C |
0 |
-10 to 10 |
C4 |
SPTY |
Setpoint type
0: Local from C1, occupancy supervised from a master Zone Controller
1: Setpoint (and occupancy) supervised from a master Zone Controller
2: Room temp control from a Zone Controller; VAV outputs controlled directly
from Zone's Heat%, Cool% Control Demands |
- |
1 |
0 to 2 |
C5 |
INMD |
Input mode for terminals 3-4 (/001 variant only)
0: Input not used (unless /002 variant for Actual Volume feedback)
1: Internal Occupancy AND External Occupation signal (short = occupied)
2: Internal Occupancy OR External Occupation signal
3: External Occupation signal only
4: Alarm Input |
- |
0 |
0 to 4 |
C6 |
MAXH |
Not used in this application |
Deg C |
30 |
0 to 90 |
C7 |
MINH |
Not used in this application |
Deg C |
20 |
0 to 90 |
C8 |
MAXC |
Not used in this application |
Deg C |
18 |
2 to 30 |
C9 |
MINC |
Not used in this application |
Deg C |
10 |
2 to 30 |
C10 |
MIND |
Supply minimum demand, used for switching between heating and cooling |
- |
4 |
0 to 10 |
C11 |
OCCO |
When set, controller will only run during the Occupied Period |
- |
0 |
0 to 1 |
C12 |
HPRD |
Not used in this application |
Secs/10 |
6 |
1 to 60 |
C13 |
HDLY |
Not used in this application |
Mins |
0 |
-30 to 30 |
C14 |
CPRD |
Not used in this application |
Secs/10 |
6 |
1 to 60 |
C15 |
CDLY |
Not used in this application |
Mins |
0 |
-30 to 30 |
C16 |
FPRD |
Not used in this application |
Secs/10 |
12 |
1 to 60 |
C17 |
FRPT |
Frost Protection
0: No Action,
1: Open Heating Valve to 50%
2: Open Heating Valve to 50% and run fan/pump (not used in this application) |
- |
0 |
0 to 2 |
C18 |
MANL |
Manual Level from Doorway |
- |
0 |
-100 to 100 |
C19 |
HTSC |
Heat Source |
- |
0 |
-1 to 100 |
C20 |
CLSC |
Cool Source |
- |
0 |
-1 to 100 |
C21 |
MAXV |
Maximum Box Volume during Occupancy |
% |
100 |
5 to 100 |
C22 |
MINV |
Minimum Box Volume during Occupancy |
% |
25 |
0 to 50 |
C23 |
REHT |
ReHeat (consult smartkontrols for special driver
settings when set to -1);
0: no ReHeat fitted; Desired Volume on Output B
-1: no ReHeat fitted; Desired Volume now on Output A; Main Supply Air
Temp checked before opening Box
1 to 100: Maximum Box Volume when ReHeating; ReHeat on Output A; Desired
Volume on Output B |
% |
0 |
-1 to 100 |
C24 |
ALRM |
Alarm Mode
0: Ignore alarms
1: Alarms reported no other action
2: Control output set to zero on alarm
3: STOP alarm recognised control set to zero |
- |
1 |
0 to 3 |
C25 |
ALST |
Alarm report sense (used with INMD=4)
0: Alarm if input = 0 (contact open)
1: Alarm if input = 1 (contact closed) |
- |
0 |
0 to 1 |
C26 |
MXVA |
Maximum Voltage output on Channel A (at
all times) |
% |
10 |
0 to 100 |
C27 |
MNVA |
Minimum Voltage output on Channel A (at
all times) |
% |
0 |
0 to 100 |
C28 |
MXVB |
Maximum Voltage output on Channel B (at
all times) |
% |
10 |
0 to 100 |
C29 |
MNVB |
Minimum Voltage output on Channel B (at
all times) |
% |
0 |
0 to 100 |
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
I1 (C30) |
EXTI |
Input A status; status of VFC input |
- |
- |
0 to 1 |
I2 (C31) |
OCCD |
Occupied |
- |
- |
0 to 1 |
I5 (C34) |
COOL |
Cooling Status |
- |
- |
0 to 1 |
I6 (C35) |
RLYA |
Not used in this application |
- |
- |
0 to 1 |
I7 (C36) |
RLYB |
Not used in this application |
- |
- |
0 to 1 |
I8 (C37) |
RLYC |
Not used in this application |
- |
- |
0 to 1 |
W1 (C38) |
AUTO |
Automatic/Manual Status |
- |
- |
0 to 1 |
W2 (C39) |
OVRD |
Override |
- |
- |
0 to 1 |
W5 (C42) |
HAND |
Manual Hand; use with MANL to set output level |
- |
0 |
0 to 1 |
W6 (C43) |
POT |
Set to a 1 if on-board pot fitted to PCB (SeaChange use) |
- |
0 |
0 to 1 |
W7 (C44) |
SERV |
Service Pin Msg (to Doorway +InSite, self resetting) |
- |
- |
0 to 1 |
W8 (C45) |
CGST |
Configuration Mode Status |
- |
- |
0 to 1 |
S1* (C50) |
BOXV |
Current Box Volume |
% |
- |
0 to 100 |
S2* (C51) |
RTNA |
Return Air Temperature |
Deg C |
- |
- |
S3* (C52) |
HCOP |
Heat Cool Output |
% |
- |
0 to 100 |
S4 (C53) |
SPSL |
Not used in this application |
Deg C |
- |
- |
S5 (C54) |
SPRT |
Current Return Setpoint |
Deg C |
- |
- |
S6 (C55) |
HDMD |
Heat Demand from Room Loop (or Zone Controller) |
% |
- |
0 to 100 |
S7 (C56) |
CDMD |
Cool Demand from Room Loop (or Zone Controller) |
% |
- |
0 to 100 |
K1 (C60) |
SPOC |
Occupation Setpoint |
Deg C |
20 |
5 to 35 |
K2 (C61) |
SPNO |
Non-Occupation Setpoint |
Deg C |
10 |
5 to 20 |
K3 (C62) |
SPSV |
Supervised Setpoint from Master Controller |
Deg C |
- |
0 to 35 |
K4 (C63) |
SPTR |
Maximum Temperature high limit |
Deg C |
0 |
-10 to 10 |
K5 (C64) |
MXVA |
Maximum Voltage output on Channel A (at
all times) |
% |
10 |
0 to 100 |
K6 (C65) |
MNVA |
Minimum Voltage output on Channel A (at
all times) |
% |
0 |
0 to 100 |
K7 (C66) |
MXVB |
Maximum Voltage output on Channel B (at
all times) |
% |
10 |
0 to 100 |
K8 (C67) |
MNVB |
Minimum Voltage output on Channel B (at
all times) |
% |
0 |
0 to 100 |
|
|
Engineering Parameters; only accessible via Doorway and InSite |
|
|
|
C90 |
NOAL |
No Alarms; all alarms cleared (when set to 1) |
- |
- |
0 or 1 |
C91 |
SENF |
Sensor Failed (when set to 1) |
- |
- |
0 or 1 |
C92 |
EXTN |
Volt-Free Contact alarm (when set to 1) |
- |
- |
0 or 1 |
C93 |
STOP |
STOP alarm received (when set to 1) |
- |
- |
0 or 1 |
|
|
* 24 hour plots available for these values by default |
|
|
|
|
|
Plotting interval and plotted variable changeable via Doorway or InSite |
|
|
|